ATT System 25 Installation And Maintenance Manual
Have a look at the manual ATT System 25 Installation And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 164 ATT manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
INSTALLATION Figure 2-11.Position of Shorting Plugs on CPU/Memory Circuit Pack 2-27
INSTALLATION Required Circuit Pack Positions The required CP positions for Cabinet 1 are: SLOTCP 1ZTN129 or ZTN130 (R3) I2IZTN85 or ZTN131 (R3) Also, all DID Trunk circuit packs should be installed in Cabinet 1. There are no other restrictions on CP position in a single-cabinet or multicabinet system; however, you should refer to the power supply unit load requirements for the maximum unit loads for each CP type within a single cabinet. Caution:Be careful not to exceed unit load restrictions on each cabinet. Label Connectors on Back Cover Each cabinet has twelve 25-pair receptacles across the bottom of the rear panel.These connectors link the CPs inside the cabinet to the Station Interconnect Panel (SIP) and Trunk Access Equipment (TAE). The connectors are numbered from 1 to 12 and correspond to the CP slots. Using a felt-tipped pen, write the CP code for each slot in the box above the connector number on the lower rear cover. 2-28
INSTALLATION Install 4A Retainer Clips The 4A retainer clips must be installed on each of the 12 receptacles on the lower rear panel of the cabinets.To install a clip, position it and insert the legs in the cabinet as shown in Figure 2-12. Figure 2-12.4A Retainer Clip Installation 2-29
INSTALLATION Connect Cabinets The Time Division Multiplex (TDM) bus extender cable and the intercabinet #6 AWG ground wire must be connected between cabinets. The TDM bus terminates on each side of the cabinet, and the intercabinet #6 AWG ground wire connects to the ground block at the rear of each cabinet. Note:Make certain that the address plug is installed in the rear pin field of each cabinet (see Figure 2-13). TDM Bus Connections One end of the TDM bus is terminated by resistors mounted on the ZTN129 or ZTN130 (R3) CP. This CP is always in slot 1 of Cabinet 1. The other end of the TDM bus is terminated by a Bus Terminator that plugs into the upper pin field of the topmost carrier (which may, of course, be the only cabinet). These connections are shown in Figure 2-13. Whenever a cabinet is added, the Bus Terminator must be moved to the end of the bus on the new top cabinet.This can be either slot 1 or slot 12, depending on the number of cabinets and how the TDM bus extender cable is run. When removing a Bus Terminator and TDM bus extender cable, to bend the backplane pins. 1.Verify that the Bus Terminator is in the proper position: l Slot 12 of Cabinet 1 for 1-cabinet systems l Slot 1 of Cabinet 2 for 2-cabinet systems l Slot 12 of Cabinet 3 for 3-cabinet systems. take care not 2. See Note. For 2- and 3-cabinet systems, install extender cable between slot 12 of Cabinet 1 and slot 12 of Cabinet 2. For 3-cabinet systems, install another extender cable between slot 1 of Cabinet 2 and slot 1 of Cabinet 3. Note:When properly installed, the light blue stripe on the extender cable is at the bottom of the cable and the lettering on the cable (SER=1, for example, is right 2-30
INSTALLATION side up). 3.Install the upper rear panels.Route the extender cable between the slots formed by the upper and lower rear panels. 2-31
INSTALLATION TDM BUS TERM CARD ADDR PLUG TDM B EXTEN CABLE ADD PLU PLUG Figure ~CABINET 3 ON/OFF .SWITCH AC POWER # 6 AWG BUILDING GROUND WIRE CABINET 2 AC POWER . #6 AWG 2-13.TDM Bus Terminations (Rear View of 3-Cabinet System) 2-32
INSTALLATION Ground Wire Connections The cabinets are connected to the single-point ground with #6 AWG copper wires. (Building ground requirements aredescribed in Preinstallation Requirements in this section.) Warning:The cabinet power switches must be set to off. 1.In 2- or 3-cabinet systems, connect a #6 AWG wire between the ground blocks of Cabinets 1 and 2 and Cabinets 1 and 3. 2. Connect a #6 AWG wire between the ground block of Cabinet 1 and the single-point ground. (See Figures 2-9 and 2-1 3.) POWER UP AND INITIALIZE SYSTEM Separate power cords for each cabinet must be plugged into the designated quad outlets.Peripheral equipment (SAT, SMDR [Station Message Detail Recording], or CAS [Call Accounting System], DTU and CSU [Customer Service Unit]) collocated with the switch cabinet(s) must also be plugged into these ac outlets. Connect Power 1. 2. 3. 4. Make sure the rear panel is in place on each cabinet. Connect the receptacle end of a 3-wire power cord to the plug at the rear of each cabinet. Connect the power cord’s plug end to the quad ac outlet for each cabinet. Recheck the electrical and ground connections. Danger: Once power is applied, do not put your hands or any tools into the cabinet. 2-33
INSTALLATION 5.Starting with Cabinet 2 or 3, turn on the power switch on each cabinet [Cabinet 1 must be last). IMPORTANT: If power to Cabinet 1 is not turned cold start initialization may not occur properly. 6.Check to be sure that the cabinet fans are rotating. Connect Administration Equipment on last, the Connect the SAT and DTU to their respective modular jacks on an 858A Adapter at the SIP. If the SIP has not yet been installed, connect an octopus cable to Cabinet 1, slot 1. Make temporary connections as shown in Figure 2-14 to the SAT and Note:The direct octopus cable connections are only temporary. All permanentconnections to peripheral and station LEGEND : ZTN129 - cl - 355A ADAPTER - 355AF ADAPTER - NOTE :CPU/MEMORY CP OCTOPUS CABLE ( WP90780 ) RS-232 PLUG TO MODULAR JACK RS-232 RECEPTACLE TO MODULAR JACK LEG 1 CONNECTS TO SAT; LEG 3 CONNECTS TO DTU. Figure 2-14.Temporary SAT and DTU Connections 2-34
INSTALLATION Cold Start the System To ensure that the system recognizes the current position of the CPs, you must cold start the system before beginning initialization. A cold start causes the system to check all slots for valid CP types and assign default translations to ail ports (except auxiliary trunk ports). A limited cold start is available. The limited cold start does not assign default translations to ports. The limited cold start is useful if the customer’s dial plan is significantly different from the System 25 default plan. You do not have to delete the default codes before you enter the true dial plan. See the Administration Manual (555-540-500) for a listing of default translations provided in Release 3 systems. The time required for a cold start depends on the number of CPs in the system, but is usually several minutes.A limited cold start takes about 30 seconds. Follow these steps to manually start the system from the SAT: 1. 2. 3. 4. 5. 6. Connect the SAT to the CPU/Memory CP administration port, (leg 1 of the octopus cable). If the SAT has a selectable baud rate, set it to 1200 baud. Be sure transmission parity is set to none, with the parity bit set to space (0). Turn the terminal on and press the carriage return key once or twice. On most terminals, this key is or . After communication with the system is established, a prompt is displayed: Enter Password -> Enter SYSTEM25 and press . The main menu will now be displayed along with the prompt: Make one selection from menu -> Enter 9 (for the SAVE/RESTORE selection) and press . 2-35
INSTALLATION 7. The system will respond with: Action= 8. Enter 20 for a cold start. The system will respond with: Save/Restore: Action=20 Data= 9. Enter D. The system will complete the word Data followed by the = sign. 10.Enter 1 for a cold start or 2 for a limited cold start. The system will respond with: Save/Restore: Action=20 Data=1 (or You are about to initiate a cold start . c to continue, any other key to abort 11.Enter c to initiate the cold start. Data=2) Typing errors can be erased by pressing the backspace key. Each time you press the backspace key, one character is erased. 2-36