ATT System 25 Installation And Maintenance Manual
Have a look at the manual ATT System 25 Installation And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 164 ATT manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
NOTES : 1. 2. 3. 4. 5.115V AC, 60 Hz, 15 AMP OUTLETS (HUBBELL 5262 OR EQUIVALENT) MUST BE LOCATED WITHIN 4 FEET OF SYSTEM CABINETS. MULTIPLE CABINET SYSTEMS REQUIRE TWO QUAD OUTLETS, SINGLE CABINET SYSTEMS REQUIRE ONE QUAD OUTLET. ALLOW AT LEAST 24 INCHES OF SPACE IN FRONT OF CABINETS. TABLE MUST BE ABLE TO SUPPORT 250 POUNDS. BACKBOARD IS 3/4 INCHES THICK BY 48 INCHES WIDE BY 96 INCHES LONG (FOR MAXIMUM SYSTEM). SYSTEM 25 CABINETS AND BACKBOARD MUST BE LOCATED IN A RESTRICTED ACCESS AREA. RESTRICTED ACCESS AREA (NOTE 5) Figure 2-8.Typical System 25 Floor Plan 2-17
INSTALLATION AC Power All cabinets and any locally-connected System 25 peripheral equipment (System Administration Terminal [SAT], Station Message Detail Recording [SMDR] device, Digital Tape Unit [DTU]), and Customer Service Unit (CSU) used for DS1 connections must be plugged into the common ac power outlet. This outlet must have an associated ground block connected to an approved building ground, using #6 AWG copper wire. (This ground block is the system’s single-point ground.) A 1-cabinet system requires one quad ac outlet. A 2- or 3-cabinet system requires a second quad outlet and two separately fused 15-ampere circuits. Additional ac outlets may be needed for auxiliary equipment. All ac outlets must have the safety ground (green wire) cross-connected to the single-point ground block on the first quad outlet. (See Figure 2-9.) Local options may require that surge protectors be used for all peripheral equipment used with the System 25, including the Customer Service Unit (CSU). Grounding For proper grounding instructions, refer to the AT&T System 25 Electrical Protection and Exposure Check List (555-500-1 20). Warning:Verify that the building ground has been provided by one of the methods listed below, that ac power uses approved building ground for its primary ground, and that all voltage limiting devices are grounded to building approved ground.Improper ground can result in equipment failures and service outages from lightning induced surges on the power lines. An approved building ground for System 25 may be one of the following, listed in decreasing order of preference: 1.Building steel. 2. Acceptable water pipe— a metal underground water pipe at least 1/2 inch in diameter, in direct contact with the earth for at least 10 feet. The pipemust be electrically continuous (or made electrically continuous by bonding around insulated joints, plastic pipe, or plastic water meters) to the point where the protector ground is connected. A metallic underground water pipe must be supplemented by the 2-18
INSTALLATION 3. 4. metal frame of the building, a concrete encased ground, or a ground ring. If these grounds are not available, the water pipe ground can be supplemented by one of the following types of grounds. l Metal underground gas piping system—an electrically continuous metal underground gas piping system that is uninterrupted with insulating sections or joints and without an outer nonconductive coating. l Other local metal underground systems or structures—local underground structures such as tanks and piping systems. l Rod and pipe electrodes— a 5/8-inch (solid rod) or 3/4-inch (conduit or pipe) electrode driven to a minimum depth of 8 feet. lPlate electrode—expose a minimum of 2 square feet of metallic surface to the exterior soil. Concrete encased ground—defined to be an electrode, consisting of at least 20 feet of one or more steel reinforcing rods at least 1/2 inch in diameter, or 20 feet of bare copper conductor not smaller than #4 AWG encased in 2 inches of concrete. This electrode must be located within and near the bottom of a concrete foundation or footing that is in direct contact with the earth. Ground ring consisting of at least 20 feet of bare copper conductor not smaller than must be in direct below the earth’s Lightning Protection #2 AWG encircling the building. The ground ring contact with the earth and buried at least 2.5 feet surface. System 25’s lightning protection plan involves five distinct but interdependent items required at every installation: lPrimary protection in the form of voltage limiters (typically carbon blocks or gas tubes) on all pairs that leave the building, whether aerial or buried. These devices bypass surges to approved building ground and limit potential differences between T/R pairs and building ground to less than 1500 volts. 2-19
INSTALLATION l A single-point ground (SPG) system in which the green wire ground (system ground) and the telephone company ground are connected to approved building ground. l The coupled bonding conductor must be connected between the telephone company ground at the building entrance and System 25’s SPG. l Surge protection on the ac power to System 25. For greater than 99 percent of all lightning strikes, the protection outlined above will do the job.However, there are a few locations where the described protection may not be sufficient. External secondary protection, located at the trunk access area of the System 25 cross-connect field, can be employed. Several commercial units are available.If 66-type block terminations are used, a very convenient device is the LP5-230-220 Fused Lightning Protector. This unit plugs into the 66-block (in place of the shorting bars) and includes the sneak current fuse. One unit is required per protected pair. A ground bar is provided with the lightning protection units or can be ordered separately (Comcode 901-007-120). All lightning protectors located in the System 25 cross-connect area must be grounded to System 25’s SPG via a #6AWG copper wire. In addition, an AC Surge Suppressor (Tll Model 428) may be required. Local practice should be followed.The unit plugs directly into one of the quad outlets and provides a dual outlet to protected equipment. Sufficient units should be provided to protect all at-powered equipment. Each cabinet in the system requires a protected outlet, and in addition, a protected outlet is required for each auxiliary unit, such as the SAT, a tape unit, or a printer. When a Surge Suppressor is used,all peripheral equipment directly connected to System 25 must be connected to alternating current via the Surge Suppressor. 2-20
INSTALLATION Secondary Protection External secondary protection,located at the trunk access area of the System 25 cross-connect field, is required for all trunks and off-premises lines. Refer to Table 2-B for approved trunk protectors. FROM AC LOAD CENTER (TWO SEPARATELY FUSED 15 AMP CIRCUITS) SINGLE POINT GROUND HGROUNDI LOAD CENTER II (GREEN) (#14 AWG) I /TO CABINET NO. 1 GROUND BAR MOUNTED ‘GROUND BLOCK (MAX. ON 4“ BOX (SQUARE DLENGTH =20 FT.) PK9GTA OR APPROVED EQUIVALENT)4“ BOX (RACO 230 OR EQUIVALENT) HUBBELL RECPTS. ( 5262 15 AMP OR EQUIVALENT) 4“ COVER (RACO 807 OR EQUIVALENT) APPROVED BUILDING GROUND (#6 AWG, COPPER) Figure 2-9.AC Power Distribution—Multiple Cabinet System 2-21
INSTALLATION Building Wiring Building (station) wiring (must be 24 AWG or heavier) from voice and data terminals to the equipment location should already be in place. System 25 wiring requires that 4-pair circuits be distributed from the equipment location to each station’s wall jack.The SIP hardware (Figures 2-2 through 2-6), designed specifically for this purpose, is furnished with each system. Except in extraordinary circumstances, this cross-connect hardware must be used. In unusual circumstances where the 617A Panels are not used and some other cross-connect equipment that does not provide a modular jack interface to the port circuits is used, separate 4-pair circuits must be run for the voice and data terminal at the workstation. All examples and instructions in this The station wiring terminations inmanual assume the equipmentthat a SIP is used. area should have been labeled to indicate the room location and jack number of the other end of the line. When SIP connections are made, the connection information should be entered on the Voice and Data Station Records Form (see Install Equipment Room Station Cabling in this part for details). 2-22
INSTALLATION INSTALL SYSTEM CABINETS Before beginning the cabinet installation, position the cabinet table within 2 feet of the ac power receptacle. Make sure that the cabinets are easily accessible from both the front and the back. Position Cabinet(s) Caution:A fully-equipped cabinet weighs 80 pounds. 1. 2. 3. 4. Check Unscrew and remove the upper rear panel of each unscrew the lower part with the 12 connectors. cabinet. Do not Near the center of the backplane, note an address plug in one of the positions marked 1, 2, or 3 on the black address strip. (Position 4 is not used.) This indicates the cabinet number for software purposes. The position of the plug (1, 2, or 3) should agree with the position of the cabinet (Cabinet 1 on the bottom, etc.). Use the CAB 1, CAB 2, and CAB 3 labels from the cable label sheets (Figure 2-7) to label each cabinet.Position the cabinet label in the box adjacent to connector 12 on the lower back panel. (The number may have already been stamped by the factory.) Stack the cabinets on top of one another on the stand. If there is more than one cabinet, stack Cabinet 1 on the bottom arid Cabinet 3 on the top. Cabinet 1 contains the CPU/Memory (ZTN129 or ZTN130 [R3]), and Service (ZTN85 or ZTN131 [R3]) circuit packs (Figure 2-1 O). Do not replace the upper back panels yet. Cabinet Contents Check to make sure that the cabinets have been delivered with the correct circuit packs (CPs). Table 2-B lists available CPs, their functions, and their protectors.If the system has TN760B Tie Trunk CPs, you may also have to set the option switches on the CPs. See “Set TN760B Option Switches” in Appendix C for details. November 19952-23
INSTALLATION Table 2-B. Circuit Packs, Their Functions, and Protectors Approved SecondaryCircuit PackFunction Wiring Protector N/AZTN78Supports single-line voice terminals. (Must not be used on out-of-building circuits, ) SCP-1 or 79ATN742Supports off-premises, out-of- building, and bridged single-line voice terminals. lTW/LlNX343* I ROBZTN79Supports the 7300H Series voice terminals used with a MERLIN® system. (Requires local (set) power for distances beyond 1000 feet.) ITWILINX343* lROBTN735Supports MET sets. N/A TN726Supports data terminals and computers. N/ATN758Contains pooled modems. SCP-1 , SCP-2, SCP-3,ZTN76Supports ground start trunks. or LP5-230-220 SCP-1 , SCP-2, SCP-3,ZTN77 Supports bop start trunks. or LP5-230-220 SCP-1 or 79ATN753 Supports direct inward dialing trunks. (DID) SCP 1 or 79ATN760BSupports tie trunks. N/ATN763Supports auxiliary equipment. N/A ZTN130 (R3)Call processing/memory. N/ATN748BTone Detector. SCP-1 or 79ATN767Provides DS1 Interface. N/A ZTN131 (R3)Provides system clocks, tone generators, detectors, and DS1 synchronization. SCP-1 or 79ATN747E3Supports ground start or loop start trunks. lTW/LlNX343* I ROBTN762BSupports hybrid voice terminals. Must be vintage 4 or later. *Note: lROB unit ITW341 has been replaced. Use model lTW/LlNX343 only. 2-24 November 1995
INSTALLATION Two fans are located on the left-hand front side of each cabinet. The cabinet’s power supply is located behind the fans; to the right of the power supply are up to 12 CPs in individual slots.Each CP is identified by a label on the front. See Figure 2-10. 1.Remove the front cover of each cabinet. 2. Note any obviously bent or otherwise damaged circuit packs. 3. Check the CPs against the customer order. In case of irregularities or damage, follow established notification procedures. Danger:The System 25 cabinet contents are not user serviceable. Some voltages inside the cabinets are hazardous.This equipment is to be serviced only by qualified technicians. The CPU/Memory (ZTN129 or ZTN130 [R3]) circuit pack has two shorting plugs that are used for factory tests (see Figure 2-1 1). They should have been removed at the factory. If these shorting plugs have been accidentally left in by the factory, the system may cold start when it should warm start. Check the CPU/Memory CP; if the plugs are present, remove them. The shorting plugs are located on the component side of the circuit pack. 2-25
INSTALLATION Figure 2-10.Three-Cabinet System, Front View With Covers Removed 2-26