ND-46248 (E) CHAPTER 3Page 51 Revision 2.0 INSTALLATION 4.4.5 PWR CNT CA-A and PWR CA-WK Connection Wh en the – 48 PWR unit is e qi upped f o r NEAX1000 I V S, con nect the PWR CNT CA-A cable a nd the P W R CA -W K as s h own in Figu re 3 -21 . Figure 3-21 Connection of PWR CNT CA-A and PWR CA-WK MAIN POWER SUPPLY CARD BWB (Back Wiring Board) PWR0C PIM 0,1 PWR1 PWR0A (SIG) CARD SLOTS PWR CA-WK –48V PWR UNIT PWR CNT CA-A Note:“SIG Connector ” is not labeled on the Main Power Supply card.
CHAPTER 3 ND-46248 (E) Pag e 52 Revision 2.0 INSTALLATION 4.5 Connection of BUS Cables STEP 1: When the system is a multiple-PIM configuration, mount the BS00 card in the BUS slot of PIM0. Mount the BS01 card in each BUS slot of PIM1 through PIM7. When the system is a single-PIM configuration, neither BS00 nor BS01 card is needed. Figure 3-22 Mounting of BUS Cards B S 0 1 B S 0 1 B S 0 1 B S 0 0 B S 0 1 B S 0 1 B S 0 1 B S 0 1 PIM3 PIM2 PIM1 PIM0PIM7 PIM6 PIM5 PIM4 BUS SLOT
ND-46248 (E) CHAPTER 3Page 53 Revision 2.0 INSTALLATION STEP 2: When the system is a multiple-PIM configuration, connect all the BUS cards to each other using BU S ca b les, as show n in Figu re 3 -23 a nd Figu re 3-24 . Figure 3-23 BUS Cable 700 mm (27.6 inch) 48-TW-0.7 CONN CA
CHAPTER 3 ND-46248 (E) Pag e 54 Revision 2.0 INSTALLATION Figure 3-24 Connection of BUS Cables PIM7 PIM6 PIM5 PIM4 PIM3 PIM2 PIM1 PIM0BS01 CN2 CN1 CN2 CN1 CN2 CN1 CN2 CN1BS01 CN2 CN1 CN2 CN1 CN2 CN1 CN2 CN1 48-TW-0.7 CONN CA BS01 BS01 BS00BS01 BS01 BS01
ND-46248 (E) CHAPTER 3Page 55 Revision 2.0 INSTALLATION 4.6 Switch Settings of Circuit Cards T able 3 -2 sh ows the cir cu it ca rds to be e xpl ain ed in this s e c tio n. * MB = Make Busy For the other circuit cards, refer to the Circuit Card Manual. Table 3-2 List of Circuit Cards NAME SWITCHES X: PROVIDED — : NOT PROVIDED LAMPS X: PROVIDED — : NOT PROVIDED EXTRACTION/INSERTION WITH POWER ON X: ALLOWED ∆ : ALLOWED AFTER MB* — : NOT ALLOWED REFERENCE PW91 cardXX— Section 4.6.1 PW00 card XX∆ Section 4.6.2 CSH card XX∆ Section 4.6.3 CSI card XX XSection 4.6.4
CHAPTER 3 ND-46248 (E) Pag e 56 Revision 2.0 INSTALLATION4.6.1 Switch Settings of PW91 Card On the P W 91 c ard, set t h e sw itches as sh ow n in Fi gure 3 -25 and Ta ble 3-3 . T able 3 -4 s hows la mp ind ica ti o ns on the PW91 ca rd. Figure 3-25 Locations of Switches, Lamps and Connectors on PW91 Card CAUTION When the operating power is being supplied to this circuit card, do not plug/unplug this circuit card into/from its mounting slot. Set the appropriate voltage by using the AC voltage select switch (slide switch) before powering on. FRONT VIEW SIDE VIEW SW ON BAT OPE OFFON 240V AC 100/120V AC 1 2 PWR ALM BATT2 BATT1 AC INPUT SIG MODE DCOUT
ND-46248 (E) CHAPTER 3 Page 57 Revision 2.0 INSTALLATION The figure in the SWITCH NAME column and the position in in the SETTING POSITION column indicate the standard setting of the switch. When the switch is not set as shown by the figure and , the setting of the switch varies with the system concerned. Table 3-3 Switch Settings on PW91 Card SWITCH NAMESWITCH NUMBERSETTING POSITIONFUNCTION CHECK BAT OPE PRESS MOMENTARILYTo start each PIM on battery power, when AC power is not provided (Switch “SW” must be ON). MODE 1Not used 2Standard setting for equalize battery charg- ing (Set to equalize for Gel cell or no bat- tery. Typically 54.6V (52.7 ~ 56.5V)) OFFFor float battery charging Typically 51.6V (49.8 ~ 53.5V) SW ON For turning AC source power on OFF For turning AC source power off AC INPUT: 90 V - 138 V DOWN AC INPUT: 180 V - 276 V Table 3-4 Lamp Indications on PW91 Card LAMP NAME COLOR FUNCTION PWR ALM Red Lights upon occurrence of a major trouble ON Green Remains lit while the operating power is being supplied 1 2ON OFF ON ON OFF 100/120VAC 240VACUP
CHAPTER 3 ND-46248 (E) Pag e 58 Revision 2.0 INSTALLATION4.6.2 Switch Settings of PW00 Card On the P W 00 c ard, set t h e sw itches as sh ow n in Fi gure 3 -26 and Ta ble 3-5 . T able 3 -6 s hows la mp ind ica ti o ns on the PW00 ca rd. Figure 3-26 Locations of Switches, Lamps and Connectors on PW00 Card RUN MB CONN
ND-46248 (E) CHAPTER 3 Page 59 Revision 2.0 INSTALLATION The figure in the SWITCH NAME column and the position in in the SETTING POSITION column indicate the standard setting of the switch. When the switch is not set as shown by the figure and , the setting of the switch varies with the system concerned. Note:When the power is on, flip the MB switch to ON (UP position) before plugging/unplugging the circuit card. Table 3-5 Switch Settings on PW00 Card SWITCH NAMESWITCH NUMBERSETTING POSITIONFUNCTION CHECK MB (Toggle SW) Note UPFor make-busy (–48 V power off) For normal operation (–48 V power on) Table 3-6 Lamp Indication on PW00 Card LAMP NAME COLOR FUNCTION RUN Green Remains lit while –48 V power is being supplied ON DOWN
CHAPTER 3 ND-46248 (E) Pag e 60 Revision 2.0 INSTALLATION4.6.3 Switch Settings of CSH Card On the CSH ca rd, se t t h e sw it c hes as shown in Fig ure 3- 27 and Tab le 3-7 . T able 3 -8 s hows la mp ind ica ti o ns on the CSH ca rd . Figure 3-27 Locations of Switches and Lamps on CSH Card SENSE RUN MB DOPE7 DOPE6 DOPE5 DOPE4 DOPE3 DOPE2 DOPE1 DOPE0