Home > Comdial > Communications System > Comdial Executech 2000 Telephone System Instructions Manual

Comdial Executech 2000 Telephone System Instructions Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Comdial Executech 2000 Telephone System Instructions Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 133 Comdial manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							IMI66-068Installation
    Table 2.4-continued-
    :...., _’‘.
    25-PAIR CABLE CONNECTIONS 14-WIRE CONNECTIONS1 J-3 CONNECTIONS1PIN1CLIP11WIRE
    1WIRE COLOR1 PAIR1 NO.1TERM.1PAIR1COLOR(STA.1LOCATION
    ITE-BLUE
    11126I11VOICE1GREEN
    AiGE‘I, riE”
    22;YHITE2N328E
    a3315_a.c
    934
    9‘101035191020
    BLUE-BLACK
    1122
    BLACK-ORANGE123723.DATAYELLOW1E-BLACK1224BL
    K-GREEN
    133825VOICE_.I m, 1f.Y,?e)c
    NGiACKJ&/gGREEN 40GREEwm, rrtinIII ‘cl
    BLACK-BROWN_-- 1 14 1 i I 27I, REDI DATA 1 YELLOW
    BROWN-BLACKiREEN 41 ACK
    BLACK-SLATE
    SLATE-BLACK
    YELLOW-BLUE14 28 BL,15
    _40 29 VOICE 215 30 RED1641 31 DATA YELLOW
    spare Pairs
    Not Used
    CAJSO57A
    2-15 
    						
    							Installation
    2.7ConnectingA DSWBLF Console
    IMZ66-068
    You can install a DSS/BLF Console at any port in the system as a companion to a station installed at the data-p~red
    port (e.g.; ports 20 and 21). When installing a DSS/BLF, make sure that you consider all of the following:l
    The maximum number of consoles that you may install on a system is equal to one-half of the total station
    capacity of the system.l
    The installed distance limit between the common equipment and the console is the same as allowed for a
    telephone.
    Connect all four wires (voice and data pairs) of the console cable to the station connector block,l
    When you install a console, you must also program the port as a console port (see chapter 3, section 3.7.30).l
    The first 32 buttons of an installed console are defaulted as blank autodial buttons available for user
    programming.On installed 
    78button consoles, the remaining 32 buttons are fixed as DSS buttons for station
    ports beginning with port 42 at button C42.l
    The voice pair connections of the station port at which a console is installed can be used simultaneously to
    enable a station PA port function employing an external PA system-2.8.5.If 
    YOU do this programming, the
    station port 
    mzut be dej%zed as a External Paging Interface (see chapter 3, section 3.7.18)
    2-16 
    						
    							IMI66-068
    :
    Irlstauation
    2.8 Installing System Options
    The ExecuTech 2000 system offers several options that are not part of the regular installation of the common
    equipment. You may consider an expansion port or a power failure station connection, for example, as a
    non-mandatory installation option. Section 2.8 covers all of these non-mandatory options. The following is a list of
    those features:l
    Key System / Hybrid Systeml
    Power Failure Stationl Auxiliary Interface
    lCommon Audible and Auxiliary Station Interfacel
    External Paging Interface-Station PA Portl
    External Paging Interface-Line Portl Data Device
    l Music Interface
    l
    Cassette Tape Recorder Interface
    2.8.1Connecting a Key System or Hybrid System
    In the past, the Federal Communications Commission (FCC) required that telephone system manufacturers provide a
    hardware strap that installers could move to distinguish between hybrid and key system operation. Recent rulings by
    the FCC have eliminated the need for the hardware strap.Beginning with software release 11A of the ExecuTech
    2000, the telephone system automatically assumes the hybrid mode whenever a programmer assigns lines to line
    groups, and the system no longer includes a hardware strap that the installer must move. The hybrid system may
    have a higher monthly tariff from the telephone company, so the FCC requires that the installer report the equipment
    category designation number 
    (KF for key system MF for hybrid system) to the telephone company at the time of
    installation.
    2-17 
    						
    							ZMZ66-068
    2.8.2Connecting A Power Failure Station
    The system provides a tip and ring pair connected to line 1 as an emergency, power failure circuit. This circuit is
    active during a commercial AC power failure. You can connect an industry standard, single-line telephone, such as
    a Comdial model 
    250Qxx, to a power failure pair and use that station to provide communications capability until the
    AC power to the system is restored.
    The power failure is detailed in Figure 2.6, below.l
    Connect the 6&e, 1Zstation and 8 line, 20-station base unit directly to Clip terminals 49 and $0 on connector
    block J- 1.
    (
    Industry-standardnon-electronic telephone(Power fail interface)
    Il
    Connect the 16-line, 32-station base unit directly to the special power failure modular jack on the KSU.
    Industry-standard
    non-electronic telephone
    (Power fail interface)
    tW
    2-18 
    						
    							IMZ66-068
    2.8.3Connecting An Auxiliary Interface
    Instal!ktion
    You can connect a non-key system telephone device or a data device, such as a modem or fax machine, onto a line
    ahead of the common equipment. The system can detect an off-hook condition in the connected device and turn on
    the line status light at the key system telephones to indicate that the line is busy.In other words, all stations would
    know that the fax or modem line is in use and would not pick up that line and risk damaging the fax or modem
    transmission. Table 2.1, page 2-8, and Figure 2.7, below, detail the auxiliary interface connections.
    NOTE: When the auxiliary interface feature is being employed, the line to line port reassignment, as discussed in
    section 2.5.2, can only be used to reassign line 2 to line port 4 and line 4 to line port 2l
    Connection is across tip and ring of lines 2 (aux 1) and 4 (aux 2). Use the auxiliary interface connections
    provided at terminals 1 and 6 of common equipment Line Jacks 1 and 2.
    device. (Xo A-lead
    Figure 2.7. Auxiliary Interface Connection
    2-19 
    						
    							znstallationZMZ6G0682.8.4 Connectin A Common Audible
    And Auxi
    19uuy Station Interface
    You can connect an external audible ringer, such as a loud bell or flashing light, that will operate when the system
    receives an outside call.
    The contact points for this operation are dry, meaning that the external ringer or light must
    have its own power supply.
    There are two different ways to install an external ring indicator device.The two sets of relay closures with dry
    contact points are as follows:l
    One set (common audible) provides a dry-contact closure whenever any of the outside lines, connected to the
    common equipment, ring.l
    The other set (station 17 audible) provides a dry-contact closure whenever station I7 rings. You must program
    the lines that you want to ring on station 17 (station 17 defaults to all lines, and you must remove the lines that
    you do not want to ring the external ringer).
    These contact closures track the ringing pattern in both cases.The contacts are closed during the ringing period and
    are open during the silent period.
    Do not exceed a I amp at 24 volts (0.5 amp at 48 volts) load on these control terminals.If the load requirements
    exceed this limit, connect the load through an external slave relay.Do not connect these control terminals directly
    to the 
    117vac line.
    Refer to the section 2.8.5 for a discussion on using these terminals in an alternate paging function.
    Contact closure connections are located as follows.l
    Hine, 12-station and lo-line and 32-station base unit: Screw terminals l-2 and 3-4 on barrier-type terminal
    strip.l
    8-line, 20-station base unit: Clip terminals 4748 and 49-50 on connector block J-2
    2-20 
    						
    							IMI66-068Instauutionr--------
    Connect to either Station 17 Audible
    or Common Audible terminalst
    24V @ 1AMax.output asLOWA
    -or-Required byVoltage
    Relay CoilPower(A
    48V @ SA Max.SUPPlYAC----------I
    Voltage Clamping
    Diode Recommended
    II
    uuuuu, (~
    \ J-Slave I
    RelaySignalling
    DeviceSignalling ,
    Device0
    Power
    Source0
    J-2 Connector Block
    (8;Line,20-Statio;)
    1--I--* --I--3---I--1-,--
    :1;::
    I--l--
    8-4--g--l--:tIjzI12--4--::1:::1:IjXI
    2 -j--47 -+--g 1:::50 --I--CLIPTERMINALS
    AudibleIJ
    Station 17Audible
    Common
    Audible
    Barrier Strip(6-Line, 
    12-Staton and
    16&e, 32-Station)
    . .. .
    cAJso41
    Figure 2.8. Common Audible Auxiliary Interface
    2-21 
    						
    							znst4luutionZMZ66-0682.8.5Connecting An External Paging
    InteTface-Station PA Port
    You can program any station port, except for station 10, as a PA port.The station port that you choose can then
    couple a station voice path to an external paging amplifier.If you configure the PA port so that music plays over the
    PA until someone voices over, you must use either station 17 or common audible, station 15. No other station
    connection will allow the voice-over. Refer to Chapter 3, section 3.7.18 for more information on programming a PA
    port.Before you configure a port as a PA port, consider the following:l
    The audio input connection must be isolated with a 600 ohm to 600 ohm audio matching transformer.
    Terminate the audio input of the paging amplifier with a 620 ohm (nominal value) resistor.l
    If you program station port 17 as a PA port, the Auxiliary Station Interface (station 17 audible) contact points
    are automatically reconfigured as PA enable terminals.The contact closure now occurs when a user dials PA
    station 17. The normal auxiliary station interface function, as discussed in section 2.8.3, is disabled as long as
    station 17 is a PA station.
    Connect the audio input of an external paging amplifier to the audio pair of the desired station port (refer to Tables
    2-2 through 24 for station connection details). If the paging amplifier needs to be enabled in order to function,
    connect the audio input to station port 17 and the enabling leads according to the following discussion and as
    illustrated below.l
    6&e, 1Zstation and 16-line, 32-station base unit: Screw terminals 1 - 2 on barrier-type terminal strip..
    8-line, 20-station base unit: Clip terminals 47 - 48 on connector block J-2.
    Station
    ‘onnector Block
    To station port 17
    if enable is required .
    or to any unused
    station port if enable
    is not required.
    60011 to 600 n (1:l)
    AudioPA System
    audible terminals
    Iif enable is required.----/
    j 
    i---
    \----------/ 
    ‘---------
    Barrier Strip
    (6-Line, 12-Staton and
    16-line, 3ZStation)
    52 Connector Bloc
    (8-Line, 20.~Station,
    CLIPTERMIINALS
    CAJSO42
    Figure 2.8. Typical PA Connection--Station Port
    2-22 
    						
    							IMZ66-068Instauation
    2.8.6Connecting An External PagingInterface-Line Port
    You can program a line port to be an Auxiliary port.As an Auxiliary port, the line port can be used to couple a
    station voice path to an external paging device.Any station with that line appearance can use the PA port simply by
    selecting the line. Users can dial 
    DTMP tones or dial pulses through the Auxiliary port. If users need to be able to
    voice-over PA music, you must use station 17 or common audible, station 15, as the PA port. For more information,
    see Chapter 3, section 3.6.8.When configuring a line port as a PA port, consider the following:
    ,:::.:l
    The audio input of an external paging amplifier can be connected to the tip and ring leads of the Auxiliary port
    as shown below.l
    A DTMF tone select, zone-paging amplifier can be employed if desired. If you install this type of amplifier,
    users must dial the zone-select code after pressing the Auxiliary port line select key.
    RING 1TIP 1TIP.? -
    RING 4RING 3
    TIP 3TIP4
    COlPSXRING 6
    LINESRING5
    TIP 5
    TIP 6
    RING 
    0RING 7TIP7
    TIP 8
    .INETERMINATION‘l-‘fPEIMXXCONNECTOR BLOCKOR’ INDIVIDUALE-PQSITION
    MODULAR JACKS
    CAJSOII
    Figure 2.9 Typical PA Connection-Line Port
    2-23 
    						
    							ZMZ66-0682.8.7Connecting A Data Device
    The system provides two RS232 Data Ports for use in connecting a data printer, video display terminal (VDT), or
    modem for remote programming.
    Before you connect anything to a data port, consider all of the following:l
    When you use a video display terminal (VDT) or a personal computer to perform class of service programming,
    connect it to RS232 Data Port A.l
    When you use a serial data printer for SMDR, MDA, and COS printout, COMeCt it to the RS232 Data Port B.l
    The distance between the data device and the common equipment can be up to 500 feet in a quiet electrical
    environment. Shielded cable may be required at some sites for long runs. For longer distances, a limited
    distance modem must be used to relay the data communications between the common equipment and the data
    device.
    2.8.7.1Wiring The Data Device
    When preparing a cable for connection to a data device, refer to the manufacturer’s manual for the equipment being
    interfaced, and make the following wiring connections:l
    Wire the common equipment RD (data from device to common equipment) connection to the device TD
    (transmit data) connection.l
    Wire the common equipment TD (data to device from common equipment) connection to the device RD
    (receive data) connection.l
    Wire the common equipment SG (signal ground) connection to the device SG (signal ground) connection.l
    If required for proper operation, wire the common equipment CTS (clear-to-send status from device to common
    equipment) connection to the device RTS (request-to-send) connection.NOTE: The common equipment requires a positive voltage, with respect to signal 
    ground in order to send data.
    2.8.7.2Conjiguting The Data Device
    The default data format is as follows.
    Configure the data device to match this data format for initial operation..
    7-bit data with 2 stop bits and no parityl
    Baud rate of 300 baud
    The following is a list of data port locations.
    6&e, 1Zstation and 16-line, 32-station base units: Special modular jacks are available as data ports.
    8-line, 20-station base unit: Clip terminals 37 - 40 (data port 1) and 41- 44 (data port 2) on connector block J-2,
    2-24 
    						
    All Comdial manuals Comments (0)

    Related Manuals for Comdial Executech 2000 Telephone System Instructions Manual