    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6503 Switch
    Table 1-2 Catalyst 6503 Switch Specifications 
    Item Specification
    Environmental
    Temperature, operating Certified for operation: 32° to 104°F (0° to 40°C)
    Designed and tested for operation: 32° to 130°F (0° to 55°C)
    NoteThe Catalyst 6500 series switches are equipped with internal air 
    temperature sensors that are triggered at 104°F (40°C) generating a 
    minor alarm and at 131°F (55°C) generating a major alarm.
    Temperature, nonoperating 
    and storage–4° to 149°F (–20° to 65°C)
    Thermal transition 0.5°C per minute (hot to cold)
    0.33°C per minute (cold to hot)
    Humidity (RH), ambient 
    (noncondensing) operating 10% to 85%
    Humidity (RH), ambient 
    (noncondensing) 
    nonoperating and storage 5% to 95% 
    Altitude, operating Certified for operation: 0 to 6500 feet (0 to 2000 m)
    Designed and tested for operation: –200 to 10,000 feet (–60 to 3000 m)
    Physical Characteristics
    Dimensions (H x W x D)7 x 17.37 x 21.75 in. (17.78 x 44.12 x 55.25 cm). 
    Chassis requires 4 RU.
    Chassis can be mounted in equipment racks that meet ANSI/EIA 310-D 
    and ETS 300-119 standards.
    Weight
    Chassis only: 27 lb (12.25 kg).
    Chassis fully configured with 1 supervisor engine, 2 modules, 
    2 AC-input PEMs, and 2 AC-input power supplies: 85.4  lb (38.7 kg).
    Airflow
    FAN-MOD-3 (standard fan tray)—170 CFM
    FAN-MOD-3HS (optional high-speed fan tray)—270 CFM
    NoteTo maintain proper air circulation through the Catalyst switch 
    chassis, we recommend that you maintain a minimum 6-inch (15  cm) 
    separation between a wall and the chassis air intake or a wall and the 
    chassis air exhaust. You should also allow a minimum separation of 
    12 inches (30.5 cm) between the hot air exhaust on one chassis and 
    the air intake on another chassis. Failure to maintain adequate air 
    space can cause the chassis to overheat and the system to fail. On 
    Catalyst chassis in which the airflow is from front to back, the 
    chassis may be placed side-by-side.  
    						
    							1-6
    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6503-E Switch
    Catalyst 6503-E Switch
    The Catalyst  6503-E switch is an enhanced version of the Catalyst  6503. Figure 1-3 shows the front view 
    of the chassis and Figure 1-4 shows the rear view of the chassis. Ta b l e  1 - 3 provides a description of the 
    major switch features. Table 1-4 lists the specifications of the Catalyst 6503-E switch chassis. 
    Figure 1-3 Catalyst 6503-E Switch—Front View
    Figure 1-4 Catalyst 6503-E Switch—Rear View
    91239
    Slots 1-3
    (top to bottom) Fan assemblyPEM 1 PEM 2
    ESD ground
    strap connection
    Supervisor
    Engine
    Modules
    W
    S-X
    6516-G
    E-T X 
    16 PO
    RT 1000 BA
    SE-T G
    E1234567
    8910
    111213 141516
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK LINK
    LINK
    LINK
    W
    S
    -X6516-G
    E-T X 
    16 P
    O
    RT 1000 B
    AS
    E-T G
    E12345
    67
    8910
    111213 141516
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK
    LINK LINK
    LINK
    LINK
    W
    S-S
    UP
    32-G
    E-3B
    ST
    A
    T
    US
    SYST
    EM
    ACT
    IVE
    PWR MGMT
    RESETCAT
    ALYST  
     6500
     SUPER
    VIS
    OR  
    ENGI
    NE
      
    32CO
    NSO
    LE
    EJECTDIS
    K 0PORT 
    1
    PO
    RT 2
    PO
    RT 
    3
    P
    O
    RT 4PO
    RT 5
    PO
    RT 
    6
    PO
    RT 
    7PO
    R
    T 8P
    O
    RT 9
    USB 
    2.
    0
    LI
    NK
    LINK
    LI
    NK
    LI
    NK
    LI
    NK
    LINK
    LI
    NK
    LIN
    K
    LINK
    63031 
    INPUT
    OKFA N
    OKOUTPUT
    FA I L
    INPUT
    OKFA N
    OKOUTPUT
    FA I L
    Power supply 2
    (redundant)
    Power supply 1 
    						
    							1-7
    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6503-E Switch
    Table 1-3 Catalyst 6503-E Switch Features 
    Feature Description
    Chassis Three horizontal slots. Slots are numbered from 1 (top) to 3 (bottom).
    Power supplies
    Supports one or two power supplies. The following power supplies are 
    supported:
     –PWR-950-AC (950 W AC-input power supply)
     –PWR-950-DC (950 W DC-input power supply)
     –PWR-1400-AC (1400 W AC-input power supply)
    NoteFor information and specifications for each of the supported power 
    supplies, refer to Appendix  A, “Power Supply Specifications,” in the 
    Catalyst 6500 Series Switches Installation Guide.
    Installed power supplies can be of different wattage ratings. Installed 
    power supplies can be both AC-input, both DC-input, or one AC-input 
    and one DC-input. Power supplies can be configured in either redundant 
    or nonredundant mode.
    All Catalyst 6500 series AC-input power supplies require single-phase 
    source AC. Source AC can be out of phase between multiple power 
    supplies or multiple AC-power plugs on the same power supply because 
    all AC power supply inputs are isolated.
    Supervisor Engine 2T requires a 1400 W power supply to operate.
    Single power supplies are installed in the lower power supply bay. The 
    second power supply is installed in the upper power supply bay. 
    						
    							1-8
    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6503-E Switch
    Supervisor enginesSupports Supervisor Engine 2, Supervisor Engine 32, Supervisor 
    Engine  32 PISA, Supervisor Engine  720, Supervisor Engine  720-10GE, 
    and Supervisor Engine 2T. 
     –Supervisor engines are installed in slot 1 and slot 2.
     –Supervisor Engine 720, Supervisor Engine 720-10GE, and 
    Supervisor Engine 2T have built-in switching fabric and do not 
    support Switch Fabric Modules (WS-C6500-SFM and 
    WS-X6500-SFM2).
     –Supervisor Engine 32 and Supervisor Engine 32 PISA do not 
    support the Switch Fabric Modules ((WS-C6500-SFM and 
    WS-X6500-SFM2).
    The uplink ports are fully functional on the redundant supervisor engine 
    when it is in standby mode. 
    NoteIn systems with redundant supervisor engines, both supervisor 
    engines must be the same model and have the same daughter card 
    configurations. Each supervisor engine must have the resources to 
    run the switch on its own, which means all supervisor engine 
    resources are duplicated. Identical supervisor engine memory 
    configurations are recommended, but are not required as long as the 
    supervisor engine with the smaller memory configuration is 
    sufficient to run the configured features of the switch. Additionally, 
    each supervisor engine must have its own flash device and console 
    port connections.
    Modules 
    Chassis supports up to two Catalyst 6500 series modules. 
    Chassis does not support the WS-C6500-SFM and WS-X6500-SFM2 
    Switch Fabric Modules.
    Some Catalyst 6500 series modules:
     –Are not supported
     –Require that you install a Supervisor Engine 720 or Supervisor 
    Engine 2T
     –Have chassis slot restrictions
     –Require a specific software release level
    Check your software release notes for specific information on module 
    support and restrictions.
    Table 1-3 Catalyst 6503-E Switch Features (continued)
    Feature Description 
    						
    							1-9
    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6503-E Switch
    Table 1-4 Catalyst 6503-E Switch Specifications 
    Item Specification
    Environmental
    Temperature, operating Certified for operation: 32° to 104°F (0° to 40°C)
    Designed and tested for operation: 32° to 130°F (0° to 55°C)
    NoteThe Catalyst 6500 series switches are equipped with internal air 
    temperature sensors that are triggered at 104°F (40°C) generating a 
    minor alarm and at 131°F (55°C) generating a major alarm.
    Temperature, nonoperating 
    and storage–4° to 149°F (–20° to 65°C)
    Thermal transition 0.5°C per minute (hot to cold)
    0.33°C per minute (cold to hot)
    Humidity (RH), ambient 
    (noncondensing) operating 10% to 85%
    Humidity (RH), ambient 
    (noncondensing) 
    nonoperating and storage 5% to 95% 
    Altitude, operating Certified for operation: 0 to 6500 feet (0 to 2000 m)
    Designed and tested for operation: –200 to 10,000 feet (–60 to 3000 m)
    Physical Characteristics
    Dimensions (H x W x D)7 x 17.37 x 21.75 in. (17.78 x 44.12 x 55.25 cm). 
    Chassis requires 4 RU.
    Chassis can be mounted in equipment racks that meet ANSI/EIA 310-D 
    and ETS 300-119 standards.
    Weight
    Chassis only: 33 lb (15 kg).
    Chassis fully configured with 1 supervisor engine, 2 modules, 
    2 AC-input PEMs, and 2 AC-input power supplies: 85.4  lb (38.7 kg).
    AirflowWS-C6503-E-FAN—282 CFM
    NoteTo maintain proper air circulation through the Catalyst switch 
    chassis, we recommend that you maintain a minimum 15  cm (6-inch) 
    separation between a wall and the chassis air intake or a wall and the 
    chassis air exhaust. You should also allow a minimum separation of 
    12 inches (30.5 cm) between the hot air exhaust on one chassis and 
    the air intake on another chassis. Failure to maintain adequate air 
    space can cause the chassis to overheat and the system to fail. On 
    Catalyst chassis in which the airflow is from front to back, the 
    chassis may be placed side-by-side.  
    						
    							1-10
    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6504-E Switch
    Catalyst 6504-E Switch
    The Catalyst 6504-E switch is a 4-slot horizontal enhanced chassis. Figure 1-5 shows the front view of 
    the chassis and Figure 1-6 shows the rear view of the chassis. Ta b l e  1 - 5 provides a description of major 
    switch features. Ta b l e  1 - 6 lists the specifications of the Catalyst 6504-E switch chassis. 
    Figure 1-5 Catalyst 6504-E Switch—Front View
    Figure 1-6 Catalyst 6504-E Switch—Rear View
    126559
    STATUS
    FAN
    STATUS
    STATUS
    Slots 1-4
    (top to bottom) Supervisor
    Engine
    OSMs
    Redundant
    Supervisor
    Engine
    126560
    P
    W
    R
    -2700-AC
    INPUT
    OKFA N
    OKOUTPUT
    FAIL
    ALL F
    ASTENERS MUST BE FULLY ENGAGED
    PRIOR TO OPERATING 
    THE POWER SUPP
    LY
    100-240
    V-16A 50/60Hz
    P
    W
    R
    -2700-AC
    INPUT
    OKF
    AN
    OKOUTPUT
    FAIL
    ALL F
    ASTEN
    ERS M
    UST BE FULLY ENGA
    G
    ED
    PRIOR TO OPER
    A
    TING 
    THE P
    OW
    ER SUPPL
    Y
    100-240V-16A 50/60Hz
    Power Supply 1Power Supply 2
    (redundant) 
    						
    							1-11
    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6504-E Switch
    Table 1-5 Catalyst 6504-E Switch Features 
    Feature Description
    Chassis Four horizontal slots. Slots are numbered from 1 (top) to 4 (bottom).
    Power supplies
    Supports one or two power supplies. The following power supplies are 
    supported:
     –PWR-2700-AC/4 (2700 W AC-input power supply)
     –PWR-2700-DC/4 (2700 W DC-input power supply)
    NoteFor information and specifications for each of the supported power 
    supplies, refer to Appendix  A, “Power Supply Specifications,” in the 
    Catalyst 6500 Series Switches Installation Guide.
    Installed power supplies can be both AC-input, both DC-input, or one 
    AC-input and one DC-input. Power supplies can be configured in either 
    redundant or nonredundant mode.
    All Catalyst 6500 series AC-input power supplies require single-phase 
    source AC. Source AC can be out of phase between multiple power 
    supplies or multiple AC-power plugs on the same power supply because 
    all AC power supply inputs are isolated.
    Single power supplies are installed in the lower power supply bay. The 
    second power supply is installed in the upper power supply bay. 
    						
    							1-12
    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6504-E Switch
    Supervisor enginesSupports Supervisor Engine 2, Supervisor Engine 32, Supervisor 
    Engine  32 PISA, Supervisor Engine  720, Supervisor Engine  720-10GE, 
    and Supervisor Engine 2T. 
     –Supervisor engines are installed in slot 1 and slot 2.
     –Supervisor Engine 720, Supervisor Engine 720-10GE, and 
    Supervisor Engine 2T have built-in switching fabric. Switch Fabric 
    Modules (WS-C6500-SFM and WS-X6500-SFM2) are not 
    supported by those supervisor engines.
     –Supervisor Engine 32 and Supervisor Engine 32 PISA do not 
    support the Switch Fabric Modules ((WS-C6500-SFM and 
    WS-X6500-SFM2).
    The uplink ports are fully functional on the redundant supervisor engine 
    when it is in standby mode. 
    NoteIn systems with redundant supervisor engines, both supervisor 
    engines must be the same model and have the same daughter card 
    configurations. Each supervisor engine must have the resources to 
    run the switch on its own, which means all supervisor engine 
    resources are duplicated. Identical supervisor engine memory 
    configurations are recommended, but are not required as long as the 
    supervisor engine with the smaller memory configuration is 
    sufficient to run the configured features of the switch. Additionally, 
    each supervisor engine must have its own flash device and console 
    port connections.
    Modules 
    Chassis supports up to three Catalyst 6500 series modules. 
    Chassis does not support the WS-C6500-SFM and WS-X6500-SFM2 
    Switch Fabric Modules.
    Some Catalyst 6500 series modules:
     –Are not supported
     –Require that you install a Supervisor Engine 720 or Supervisor 
    Engine 2T
     –Have chassis slot restrictions
     –Require a specific software release level
    Check your software release notes for specific information on module 
    support and restrictions.
    Table 1-5 Catalyst 6504-E Switch Features (continued)
    Feature Description 
    						
    							1-13
    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6504-E Switch
    Table 1-6 Catalyst 6504-E Switch Specifications 
    Item Specification
    Environmental
    Temperature, operating Certified for operation: 32° to 104°F (0° to 40°C)
    Designed and tested for operation: 32° to 130°F (0° to 55°C)
    NoteThe Catalyst 6500 series switches are equipped with internal air 
    temperature sensors that are triggered at 104°F (40°C) generating a 
    minor alarm and at 131°F (55°C) generating a major alarm.
    Temperature, nonoperating 
    and storage–4° to 149°F (–20° to 65°C)
    Thermal transition 0.5°C per minute (hot to cold)
    0.33°C per minute (cold to hot)
    Humidity (RH), ambient 
    (noncondensing) operating 10% to 85%
    Humidity (RH), ambient 
    (noncondensing) 
    nonoperating and storage 5% to 95% 
    Altitude, operating Certified for operation: 0 to 6500 feet (0 to 2000 m)
    Designed and tested for operation: –200 to 10,000 feet (–60 to 3000 m)
    Physical Characteristics
    Dimensions (H x W x D)8.7 x 17.5 x 21.6 in. (22.09 x 44.45 x 54.86 cm). 
    Chassis requires 5 RU.
    Chassis can be mounted in equipment racks that meet ANSI/EIA 310-D 
    and ETS 300-119 standards.
    Weight
    Chassis only: 27 lb (12.25 kg).
    Chassis fully configured with 2 supervisor engines, 2 modules, and 
    2 AC-input power supplies: 97 lb (43.99 kg).
    AirflowFAN-MOD-4HS—300 CFM
    NoteTo maintain proper air circulation through the Catalyst switch 
    chassis, we recommend that you maintain a minimum 6-inch (15  cm) 
    separation between a wall and the chassis air intake or a wall and the 
    chassis air exhaust. You should also allow a minimum separation of 
    12 inches (30.5 cm) between the hot air exhaust on one chassis and 
    the air intake on another chassis. Failure to maintain adequate air 
    space can cause the chassis to overheat and the system to fail. On 
    Catalyst chassis in which the airflow is from front to back, the 
    chassis may be placed side-by-side.  
    						
    							1-14
    Catalyst 6500 Series Ethernet Modules Installation Guide
    OL-6265-04
    Chapter 1      Catalyst 6500 Series Switch Chassis Overview
      Catalyst 6506 Switch
    Catalyst 6506 Switch
    The Catalyst 6506 switch is a 6-slot horizontal chassis. Figure 1-7 shows a front view of the chassis. 
    Table 1-7 provides a description of the major switch features. Ta b l e  1 - 8 lists the specifications of the 
    Catalyst 6506 switch chassis. 
    Figure 1-7 Catalyst 6506 Switch 
    18224
    INPUT
    OKFA N
    OKOUTPUT
    FA I
    L
    o
    INPUT
    OKFA N
    OKOUTPUT
    FA I
    L
    o
    1
    2
    3
    FA N
    STATUS
    4
    5
    68
     P
    O
    R
    T G
    IG
    A
    B
    I
    T
     E
    TH
    E
    R
    N
    E
    TWS-X64081LINKSTA
    TUS2
    3
    4
    56
    7
    8LINKLINKLINKLINKLINKLINKLINK
    8
     P
    O
    R
    T G
    IG
    A
    B
    IT
     E
    TH
    E
    R
    N
    E
    TWS-X64081LIN
    KSTA
    TUS2
    3
    4
    5
    6
    7
    8LI
    NKLINKLINKLIN
    KLI
    NKLINKLI
    NK
    8
     P
    O
    R
    T 
    G
    IG
    A
    B
    IT
     E
    TH
    E
    R
    N
    E
    TWS-X64081LIN
    KSTA
    TUS2
    3
    4
    56
    7
    8LI
    NKLINKLINKLIN
    KLI
    NKLINKLI
    NK
    8
     P
    O
    R
    T G
    IG
    A
    B
    IT
     E
    TH
    E
    R
    N
    E
    TWS-X64081LINKSTA
    TUS2
    3
    4
    5
    6
    7
    8LINKLINKLINKLINKLINKLINKLINKW
    S
    -
    S
    U
    P
    32
    -G
    E-3
    BST
    AT
    U
    S
    SYS
    TEM
    ACTIVE
    PW
    R MGM
    T
    R
    ESE
    TC
    ATA
    LY
    S
    T   
    65
    00
     
    SUP
    ER
    V
    IS
    O
    R
      E
    N
    G
    IN
    E
      3
    2CONSOLE
    EJEC
    TDISK 0PORT 1
    PORT 2
    PORT 3
    PORT 4PORT 5
    POR
    T 6
    PO
    RT 7PO
    RT 8POR
    T
     9
    USB 2.0
    LIN
    K
    L
    INK
    L
    I
    NK
    LI
    NK
    LI
    NK
    LI
    NK
    LI
    NK
    LIN
    K
    LINKW
    S
    -S
    U
    P
    32
    -G
    E-3
    BST
    AT
    U
    S
    SYSTEM
    ACTIVE
    PW
    R MG
    M
    T
    R
    ESETC
    AT
    A
    LY
    S
    T   
    65
    00
     
    S
    UP
    ER
    V
    IS
    O
    R
      E
    N
    G
    IN
    E
      3
    2CONSOL
    E
    EJECTDISK 0PORT 1
    PORT
     2
    PORT 3
    PORT 4PORT 5
    PORT 6
    PO
    RT 7PO
    RT 8POR
    T 9
    USB 
    2.0
    LINK
    L
    IN
    K
    L
    I
    NK
    LI
    NK
    LI
    N
    K
    LI
    NK
    LI
    NK
    LINK
    LINK
    Fan assembly
    Supervisor engine
    Redundant supervisor
    engine Switching
    modules
    Power supply 2
    (redundant)Power supply 1
    ESD ground strap 
    connector 
    						