CHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-9 Table 3-2: Types of f iles generated by EnerVista 650 Setup software, online Settings & Conf iguration File *.650Logic Conf iguration Files (*.pep, *.aut , *.lib) *.pep*.aut*.lib Description Settings and Conf iguration Section Header for Logic pr oject Graphical edition cont ainer. Logic equations (Virtual Outputs) in FDB format . User programmable lo gic objects Created by EnerVista 650 Setup Logic configuration grap hic editor (PLC Editor) Logic conf iguration graph ic editor (PLC Editor) Logic conf iguration graph ic editor (PLC Editor) Contents Relay conf iguration f ile containing all elements, settings, input/output and LE Ds conf iguration, graphic display conf iguration, etc. Equations corresponding to the logic created and compiled in the PL C Editor PLC project f ile cont aining the necessary information relative to the relay model, logic libraries included in the project (*.lib), graphic file name (*.aut), etc. PLC Project f ile cont aining all the drawings used by the logic, required by 650 relay based on IEC 61131-3 standard. Functional block diagram (FDB). Library f ile to be i ncluded as an object in a PLC project . Logic packages that can be stored into libraries and be distributed in different PLC projects. How to tra nsfer to relay Connect with the relay ( Comm unications > Computer)Connect with the relay ( Communica tions > Computer) Send settings and conf iguration from f ile Launch 650 Logic equations editor (Se tpoint > Logic Conf iguration ) Open the created PLC project ( F ile > Open Project) Compile the project ( Run > Compile) Now the logic (virtual outputs) can be sent directly to relay ( Run > Send Equations to Relay ). Texts of virtual outputs are not stored in the relay, only in the logic conf iguration f iles to be edited. Modify settings and configuration directly in the relay: How to save EnerVista 650 Setup: File > Get info from relay . User de finable texts retrieved are operations, events, and LEDs. PLC Editor: File > Save Project File > Save Library The relay does not pr ovide this information unless the *.pep f ile is stored in the relay The relay does not pr ovide this information unless the *.pep f ile is stored in the relay. The relay does not pr ovide this information unless the *.pep f ile is stored in the relay. To store the logic conf iguration f iles in the relay use the Communication > Upload info f iles to relay op tion How to store in the r elay Communication > Upload info f iles to relay thr ough Ethernet Communication > Upload info f iles to relay thr ough Ethernet How to re trieve from the relay Communication > Download info f iles fr om relay through Ethernet Communication > Download info f iles from relay thr ough Ethernet REMINDER: Logic programming support files (*.pep, *.aut, *. lib) CANNOT be retrieved directly from the relay. It is necessary to do one of the following to store support files: * Store in the PC * Upload to the relay (Communication > Upload info files to relay), after which they can be retrieved from the relay
3-10F650 DIGITAL BAY CONTROLLER GEK-113000-AF 3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES 3.1.5 EnerVista 650 Setup menu The EnerVista 650 Setup menu structure is shown in Table 3-3: EnerVista 650 Setup menu structure. Unless specified, options are available in both online and offline mode. (*) indicates options enabled only in online mode. (**) indicates options enabled only in offline mode. Table 3-3: EnerVista 650 Setup menu structure NOTICEThe View > Language submenu allows the user to change the default language for the EnerVista 650 Setup program. This feature is only enabled when the relay is not communicating and no file has been opened. FileSetpointActualOperations(*)CommunicationIEC 61850 CONFIGURATORSecurityViewHelp New (**) Product SetupFront Pa nel Fixed comm ands Computer Login userTracesInstruction Ma nual Open (**) System SetupStatus Modem (*) Change Pa ssword ModBus Mem ory Map GE Multilin on the web Save (**) Protection Elem ents Metering Troubleshooti ng (*) User M anageme nt Languages (** ) About Ener Vista 650 Setup Save As (**) Control Elem ents Inputs/ Output s Calibration (*) Close (**) Inputs/ Output s Quick Settings Records (*) Upgrade Rel ay (*) Conf ig File (* 650) Conver ter Relay Conf iguratio n Compare to sett ings f ile Properties (**) Logic Conf iguratio n Upgrade 650 W eb Server Procome Conf iguratio n Update M agnetic Module IEC103 Conf iguratio n Get info from re lay (*) Clock (*) Upload info f iles to relay Send info to re lay (*) Download info f iles from relay Print Setup (**) Print Preview (**) Print (**) Print to f ile PLC Checksum Calculation Settings Checksum Calculation Order Code Exit
CHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-11 3.1.6 File menu (*) indicates online only, (**) indicates offline only File New (**) Create a new settings and conf iguration f ile, with the default relay setti ngs and no conf iguration Open (**) Open a settings and conf iguration f ile for offline working. Save (**)Save *.650 settings and conf iguration f ile Save As (**)Save as *.650 settings and conf iguration f ile. Close (**)Close the opened *.650 f ile in EnerVista 650 Setup. Conf ig File (*.650) Converter Tool to convert the *.650 files from one version to another Compare to settings f ile Compare online unit or opened settings f ile to another settings f ile Properties (**)File properties for *.650. Get info from relay (*)Retrieve the *.650 settings and relay conf iguration compiled equations fr om the relay. Send info to relay (*) Send and write the *.650 settings and configuration to the relay. Print Setup (**)To conf igure printer settings. Print Preview (**)Preview of settings and conf iguration f ile printing format . Print (**)Launch the *.650 f ile to be printed. Print to f ile (*.xls) (**)*.650 printed to f ile in excel format . PLC Checksum CalculationCalculate the CRC of PLC equations of the .650 f ile (When a .650 is uploa ded to the relay, the calculate PLC CRC and the actual value of the PLC CRC read from the relay must match). Settings Checksum Calculation Calculate the CRC of settings of the .650 f ile (When a .650 is uploaded to the r elay, the calculate Setting CRC and the actual value of the Setting CRC read from the relay must match). Order code(*) Option available for F650 with f irmware version 7.00 or above. This allows a mode l to have special functionality (see model selection) with password requirements. For detailed information go to section 9.6.3.3 ORDER CODE UPGRADE PROCESS in chapter 9. Exit Quit the application closing all the open windows.
3-12F650 DIGITAL BAY CONTROLLER GEK-113000-AF 3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES 3.1.6.1 New, Open, Save, Save as, and Close In these options, the EnerVista 650 Setup program opens a dialog box (with default path to Files > Config program folder) where the setting and configuration files can be selected from offline files. To access this menu, there must be no communication between the PC program and the relay (offline mode). Figure 3-5: Open f ile menu Once the *.650 file for the appropriate relay model (FXGX) is selected, the EnerVista 650 Setup program enables the offline options to fully program the unit. The enabled menus in the EnerVista 650 Setup program are: File, Setpoint, Actual, Communication, View and Help. Offline mode displays the File, Setpoint, Actual, Communication , Security, View and Help submenus in order to program the unit. The Actual values submenus are for structure purposes only. Values are not refreshed while the relay is not communicating. The Save as and Close file options are used to save the *.650 file into the computer and to close the current file. To work in offline mode for settings and configuration editing, a new *.650 file can be opened without closing the previous file. The Close option is instead used to clear all data in EnerVista 650 Setup program, enabling the Language, Upgrade firmware version and Upgrade Operating system menu options.
CHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-13 3.1.6.2 Conf iguration f ile converter The configuration file converter tool provides automatic conversion of configuration files from and older firmware version to a newer version. In order to convert a configuration file, follow these steps: 1. Working in offline mode, go to File > Conf ig File (*.650) Converter 2. Select the f ile to be converted. 3. After source f ile selection is complete, select c onversion settings. Make the following selections: Source Model: Indicates source F650 model and original version of selected file. Destination model:Drop-down list of available F650 models and firmware versions. Select a destination model and firmware version. In the bottom part of this section, a brief description of all models affected is displayed in green after selecting one model in the list. Source file pathIndicates the path where source model file is located. Figure 3-6: Conf ig f ile (*650) converter menu It is possible to change the model type (FXGX) using the conversi on tool. It must be taken into account that part of the logic can be readjusted to fit the new input and output board selection. Notice also that the external wiring of inputs and outputs boards is different for type 1, 2, 4 and 5. File conversion to version 7.50 or above The file conversion tool has been modified to include the increased number of setting groups available in firmware version 7.50 and above. In firmware version 7.50, the maximum number of setting groups (SG) available increased from 3 to 6. Some considerations must be taken into account previous to convert (*.650) files from firmware version below 7.50 to firmware version 7.50 or above. In these cases, the tool internally checks if setting groups functionality is enabled or disable at Setpoint > Control Elements > Setting group in the source file and depend on its value, different conversions are performed in elements affected by setting groups. Source Model Destination Model Source file path
3-14F650 DIGITAL BAY CONTROLLER GEK-113000-AF 3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES For example, if the Phase TOC High element is config ured in the source *.650 file as described below: 1. Note that fields in blue contain default values CASE 1: If the setting groups option is disabled (Setpoint > Control Elements > Setting group) in the source file, conversion is performed in the destination file as follows: • Settings of different elements (Phase TOC High 1, 2 and 3) that belong to Setting group 1(SG1) in the source f ile are copied into elements that belong to Setting Group 1 in the destination f ile. • Elements in the other setting groups are conf igured with default values in the conf iguration f ile. CASE 2: If the setting groups option is enabled (Setpoint > Control Elements > Setting group) in the source file, conversion to the destination file is as follows: • Settings of different elements (Phase TOC High 1, 2 and 3) th at belong to different setting groups in the source f ile are copied into elements that belong to f irst group of f irst three setting groups in the destination f ile • Protection elements in the other groups/setting groups ar e conf igured with default values in the destination f ile. Phase TOC HighPhase TOC High 1 (G1)Phase TOC High 2 (G2)Phase TOC High 3(G3) Function ENABLED ENABLEDENABLED InputPHASOR(DFT)PHASOR(DFT)PHASOR(DFT) Pickup Level 0.10 1.502.00 Curve Def inite time Def inite timeDef inite time TD Multiplier 0.02 0.050.1 Reset INSTANTANEOUSINSTANTANEOUSINSTANTANEOUS Voltage Restraint DISABLEDDISABLEDDISABLED Snapshot Events ENABLEDENABLEDENABLED SG1SG2SG3SG4SG5SG6 Phase TOC HighG1G2G3G1G2G3G1G2G3G1G2G3G1G2G3G1G2G3 FunctionENABLEDDISABLED Input PHASOR(DFT) Pickup Level0.101.502.001.00 CurveDef inite timeIEEE Ext Inv TD Multiplier0.020.050.101.00 Reset INSTANTANEOUS Voltage Restraint DISABLED Snapshot Events ENABLED SG1 SG2 SG3SG4SG5 SG6 Phase TOC High G1G2G3 G1 G2G3 G1G2G3 G1G2 G3G1 G2G3 G1G2 G3 Function ENABLEDDISABLEDENABLEDDISABLEDENABLEDDISABLED Input PHASOR(DF T) Pickup Level 0.101.001.501,002.001.00 Curve Definite timeIEEE Ext InvDef inite timeIEEE Ext InvDef inite timeIEEE Ext Inv TD Multiplier 0.021.000.051,000.101.00 ResetINSTANTANEOUS Voltage RestraintDISABLED Snapshot EventsENABLED
CHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-15 3.1.6.3 Properties When this option is selected, the program displays the relay model information, firmware version, etc. of the file being edited, as shown: Figure 3-7: File properties menu 3.1.6.4 Print options The printing options are active only in offline mode with a file open, and not in online mode, connected with the relay. Print setup Option to configure the printer options and settings. Print preview Option to preview the whole settings and configuration f ile (*.650) in paper format to be printed as shown: Figure 3-8: Print preview of settings f ile
3-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF 3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES Print Option to print the relay configuration using the PC default (activ e) printer on port COMx or LPT. This option is active only in offline mode and in file edition (not in online mode while connected to the relay). Print to f ile (*xls) Option to export the configuration file to an Excel file. 3.1.6.5 Compare to settings f ile This tool provides an automatic comparison of two different configuration files, or of an online unit to one settings file. Open the source *.650 file and select the version and model to compare against. The results of the comparison are displayed as shown: Figure 3-9: Compare to settings f ile 3.1.6.6 PLC checksum calculation When working in offline mode, the PLC Checksum calculation option calculates the CRC of the PLC equations and Relay configuration section for the open *.650 file. When a *.650 file is uploaded to the relay, the calculated PLC Checksum and the actual value of the PLC Checksum read from the relay (Actual values > Status > System Info) must match. In order to calculate this checksum, the following sections of the * .650 file are considered: • All equations compiled in the f ile and located in EnerVista 650 Setup Setpoint > Logic conf iguration • Conf iguration available in the f ile and located in EnerVista 650 Setup Setpoint > Relay conf iguration, excluding: – HMI tab conf iguration – All configured text – Opening and closing time in the Switchgear section
CHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-17 3.1.6.7 Setting checksum calculation When working in offline mode, the Settings Checksum calcul ation option calculates the CRC of different configured settings for the open *.650 file. When a *.650 file is uploaded to the relay, the calculated Sett ings Checksum and the actual value of the Settings Checksum read from the relay (Actual values > Status > System Info) must match. In order to calculate this checksum, the following sections of the * .650 file are considered: • All settings in the relay conf iguration section (Setpoint > Relay conf iguration) excluding: – Those communication settings: Setpoint > Pr oduct Setup > Communication settings > SerialPorts or Network (Ethernet) or Mod bus Protocol or Routing – Relay calibration factors – Opening and closing time in the Switchgear section 3.1.7 Setpoint menu (*) indicates online only, (**) indicates offline only Setpoint Product Setup Communications settings for all protocols and physical mediums. ModBus user map def inition, fault report , oscillography, data logger demand settings and T ime Settings. System Setup General Settings, Flex Curves Def inition, Breaker settings, maintenance, switchgear snapshot event s management and Miscellaneous Settings. Protection Elements Phase, Neutral, Ground, Sensitive Ground and Negative Sequence Current Settings. V oltage Elements settings and Power Settings management . Control Elements Setting groups, under- and over-frequency settings, synchrocheck, autoreclose, breaker failur e, VT fuse failure, broken conductor, locked rotor settings management , Pulse Counters, Analog comparators, Frequency Rate of Change, Load encroachment , max number of starts, Digital Counters, Cold Load Pickup and PLC T imer Masks Inputs/Outputs Contact I/O settings for all boards available in device, Remote Comms Force Outputs and V irtual inputs. Quick Settings Menu that encompass the most important settings to conf igure the device such as; Curr ent and Voltage sensing or current protection element . Relay Conf iguration Conf iguration of Outputs, LEDs, Operations, Protection Elements, Oscillography, Control Event s, Control Elements, Switchgear, Inputs, Virtual Inputs, Operations and HMI. Whole relay conf iguration with internal relay signals or user-def inable ones as logic (virtual outputs). Logic Conf iguration Logic conf iguration graphic editor (PLC Editor). It is a PLC Project f ile editor that contains all the int ernal drawings used to make the logic (virtual outputs) based on IEC 61131-3 standard. Functional block diagram (FDB). Procome Conf iguration Procome Configuration tool. Only available for Procome models (5) when communicating thr ough Ethernet with EnerVista 650 Setup IEC103 Conf iguration IEC103 settings for available IEC103 models (3) when communicating through Ethernet with Ener vista 650 Setup Clock (*) Relay synchronization to computer clock or to user-def inable date and time. Online mode only.
3-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF 3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES 3.1.7.1 Product setup menu (*) indicates online only, (**) indicates offline only 3.1.7.2 Communication settings menu This section details the settings related to communication parameters for the different protocols available in the F650. (*) indicates online only, (**) indicates offline only Product Setup Communication Settings Serial Ports, Network (Ethernet), ModBus Protocol, DNP Slave, IEC 870-5-104, SNTP settings a nd procome (if available on model selection), PTP1588 and Routing (for f irmware version 7.00 and higher) ModBus User Map ModBus user map definition. The ModBus user map is formed by 256 records, selectable fr om the complete relay ModBus map. Fault Report Fault report settings. Possibility to show fault reports on HMI screen. OscillographyOscillography settings (trigger position, samples per cycle, etc.). The trigger and digital c hannels (up to 16) must be conf igured in Setpoint > Relay conf iguration. Data LoggerData logger conf iguration DemandDemand settings. The demand trigger and demand reset signals must be conf igured in Setpoint > R elay conf iguration Time Settings Time settings. COMMUNICATIoN SETTINGS Serial PortsBaud rate and parity for COM1 and COM2 serial communication ports. Network (Ethernet)Ethernet communication parameters for ETH_1/ETH2 or ETH_E/ETH_A/ETH_B (Depend ing on model) (IP Address, Netmask, Gateway IP) NOTE: The ModBus Slave address used by Ethernet ports is the one set for C OM2.EnerVista 650 Setup software allows programming two different Ethernet addresses, but the f irst IP has always to be set as the second IP Address is an Alias. ModBus Protocol ModBus Slave Addresses for serial and Ethernet communication and the ModBus port num ber used for ModBus TCP/IP DNP3 Slave Physical port , Slave Address for DNP, IP Addresses for Masters, TCP/UDP Port , Un solicited Response parameters, Analog scale factors and deadbands, message fragment size, Binary input block.Available for standard and IEC61850 models. IEC 870-5-104 TCP Port , Common Addr of ASDU, Cyclic Meter Period and, Synchronization Event settings. Available for standard and IEC61850 models. SNTP (*) Synchronization over Ethernet settings PROCOMEComm port and slave number for procom e protocol. Only available forprocome models (5). PTP 1588Precission T ime Protocol 1588 settings. (Available on fw version 7.00 or higher) RoutingA default route and a maximum number of 6 static routes may be configured. The de fault route is used as the last choice, if no other route towards a given destination is found.This option is only available for version 7.00 and higher.