    							CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
    GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-9
    Table 3-2:  Types of f iles generated by EnerVista 650 Setup software, online 
    Settings & Conf iguration File *.650Logic Conf iguration Files (*.pep, *.aut , *.lib)
    *.pep*.aut*.lib
    Description Settings and Conf iguration Section Header for Logic 
    pr
    
    oject Graphical edition 
    cont
    ainer. Logic 
    equations (Virtual 
    Outputs) in FDB 
    format . User programmable 
    lo
    gic objects
    Created by EnerVista 650 Setup Logic configuration 
    grap
    
    hic editor (PLC 
    Editor) Logic conf iguration 
    graph
    ic editor (PLC 
    Editor) Logic conf iguration 
    graph
    ic editor (PLC 
    Editor)
    Contents Relay conf iguration f ile containing all  elements, 
    settings, input/output and LE
    
    Ds conf iguration, graphic 
    display conf iguration, etc.
    Equations corresponding to the logic created and 
    compiled in the PL
    
    C Editor PLC project f ile 
    cont
    
    aining the 
    necessary 
    information 
    relative to the relay 
    model, logic 
    libraries included in 
    the project (*.lib), 
    graphic file name 
    (*.aut), etc. PLC Project f ile 
    cont
    aining all the 
    drawings used by 
    the logic, required 
    by 650 relay based 
    on IEC 61131-3 
    standard. 
    Functional block 
    diagram (FDB). Library f ile to be 
    i
    ncluded as an object 
    in a PLC project . 
    Logic packages that 
    can be stored into 
    libraries and be 
    distributed in 
    different PLC 
    projects.
    How to 
    tra
     nsfer to 
    relay Connect with the relay (
    Comm unications > Computer)Connect with the relay ( Communica tions > Computer)
    Send settings and conf iguration from f ile Launch 650 Logic equations editor (Se
     tpoint > Logic 
    Conf iguration )
    Open the created PLC project ( F
     ile > Open Project)
    Compile the project ( Run > Compile)
    Now the logic (virtual outputs) can be sent directly to relay 
    ( Run > Send 
    
    Equations to Relay ). Texts of virtual outputs are 
    not stored in the relay, only in the logic conf iguration f iles to be 
    edited.
    Modify settings and configuration directly in the relay:
    How to save EnerVista 650 Setup:
    File > Get info from relay . User de
     finable texts retrieved 
    are operations, events, and LEDs. PLC Editor:
    File > Save Project
    File > Save Library
    The relay does not 
    pr
     ovide this 
    information unless 
    the *.pep f ile is 
    stored in the relay  The relay does not 
    pr
    ovide this 
    information unless 
    the *.pep f ile is 
    stored in the relay. The relay does not 
    pr
    ovide this 
    information unless 
    the *.pep f ile is 
    stored in the relay.
    To store the logic conf iguration f iles in the relay use the 
    Communication > Upload info f iles to relay  op
     tion
    How to store 
    in the r
     elay Communication > Upload info f iles to relay
     thr ough 
    Ethernet Communication > Upload info f iles to relay
     thr ough Ethernet 
    How to 
    re
     trieve from 
    the relay Communication > Download info f iles fr
    om relay 
    through Ethernet Communication > Download info f iles from relay
     thr ough 
    Ethernet
    REMINDER:
    Logic programming support files (*.pep, *.aut, *. lib) CANNOT be retrieved directly from the relay.
    It is necessary to do one of the following to store support files:
    * Store in the PC 
    * Upload to the relay (Communication > Upload info files to relay), after which they can be retrieved from the relay 
    						
    							3-10F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
    3.1.5  EnerVista 650 Setup menu
    The EnerVista 650 Setup menu structure is shown in Table 3-3: EnerVista 650 Setup menu structure. 
    Unless specified, options are available in both online and offline mode.
    (*) indicates options enabled only in online mode.  (**) indicates options enabled only in offline mode.
    Table 3-3: EnerVista 650 Setup menu structure
    NOTICEThe View > Language submenu allows the user to change the default language for the EnerVista 
    650 Setup program. This feature is only enabled when the relay is not communicating and no file has 
    been opened.
    FileSetpointActualOperations(*)CommunicationIEC 61850 
    CONFIGURATORSecurityViewHelp
    New (**) Product 
    SetupFront 
    Pa
    nel Fixed 
    comm
    ands Computer
    Login userTracesInstruction 
    Ma
    nual
    Open (**) System 
    SetupStatus
    Modem (*) Change 
    Pa
    
    ssword ModBus 
    Mem
    ory 
    Map GE Multilin 
    on the web
    Save (**) Protection 
    Elem
    
    ents Metering
    Troubleshooti
    ng
     (*) User 
    M
    anageme
    nt Languages 
    (**
    ) About 
    Ener
    Vista 
    650 Setup
    Save As (**) Control 
    Elem
    
    ents Inputs/
    Output
    s Calibration (*)
    Close (**) Inputs/
    Output
    
    s 
    Quick 
    Settings Records 
    (*)
    Upgrade 
    Rel
    ay (*)
    Conf ig File
    (* 650) 
    Conver
     ter Relay 
    Conf
    iguratio
    n
    Compare to 
    sett
     ings f ile
    Properties (**) Logic 
    Conf
    
    iguratio
    n Upgrade 650 
    W
    eb Server
    Procome 
    Conf
     iguratio
    n Update 
    M
    agnetic 
    Module
    IEC103 
    Conf
     iguratio
    n
    Get info from 
    re
     lay (*) Clock (*)
    Upload info 
    f
    iles to relay
    Send info to 
    re
     lay (*) Download 
    info f
    iles from 
    relay
    Print Setup (**)
    Print Preview (**)
    Print (**)
    Print to f ile
    PLC Checksum 
    Calculation
    Settings 
    Checksum
      
    Calculation
    Order Code
    Exit 
    						
    							CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
    GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-11
    3.1.6  File menu
    (*) indicates online only, (**) indicates offline only
    File
    New (**) Create a new settings and conf iguration f ile, with the default relay 
    setti
    ngs and no conf iguration 
    Open (**) Open a settings and conf iguration f ile for offline working. 
    Save (**)Save *.650 settings and conf iguration f ile 
    Save As (**)Save as *.650 settings and conf iguration f ile.
    Close (**)Close the opened *.650 f ile in EnerVista 650 Setup. 
    Conf ig File (*.650) Converter Tool to convert the *.650 files from one version to another
    Compare to settings f ile Compare online unit or opened settings f ile to another settings f ile
    Properties (**)File properties for *.650.
    Get info from relay (*)Retrieve the *.650 settings and relay conf iguration compiled equations 
    fr
    om the relay.
    Send info to relay (*) Send and write the *.650 settings and configuration to the relay. 
    Print Setup (**)To conf igure printer settings.
    Print Preview (**)Preview of settings and conf iguration f ile printing format .
    Print (**)Launch the *.650 f ile to be printed.
    Print to f ile (*.xls) (**)*.650 printed to f ile in excel format . 
    PLC Checksum CalculationCalculate the CRC of PLC equations of the .650 f ile (When a .650 is 
    uploa
    ded to the relay, the calculate PLC CRC and the actual value of the 
    PLC CRC read from the relay must match).
    Settings Checksum 
    Calculation Calculate the CRC of settings of the .650 f ile (When a .650 is uploaded to 
    the r
    elay, the calculate Setting CRC and the actual value of the Setting 
    CRC read from the relay must match).
    Order code(*) Option available for F650 with f irmware version 7.00 or above. This 
    allows a mode
    l to have special functionality (see model selection) with 
    password requirements. For detailed information go to section 9.6.3.3 
    ORDER CODE UPGRADE PROCESS in chapter 9. 
    Exit Quit the application closing all the open windows. 
    						
    							3-12F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
    3.1.6.1   New, Open, Save, Save as, and Close
    In these options, the EnerVista 650 Setup program opens a dialog box (with default path to Files > Config program folder) 
    where the setting and configuration files  can be selected from offline files. To access this menu, there must be no 
    communication between the PC program and the relay (offline mode).
    Figure 3-5: Open f ile menu
    Once the *.650 file for the appropriate  relay model (FXGX) is selected, the EnerVista 650 Setup program enables the offline 
    options to fully program the unit. The enabled menus in the EnerVista 650 Setup program are: File, Setpoint, Actual, 
    Communication, View and Help.
    Offline mode displays the File, Setpoint, Actual, Communication , Security, View and Help submenus in order to program the 
    unit. The Actual values submenus are for structure purposes only. Values are not refreshed while the relay is not 
    communicating.
    The Save as and Close file options are used to save the *.650 file into the computer and to close the current file. To work in 
    offline mode for settings and configuration editing, a new *.650  file can be opened without closing the previous file. The 
    Close option is instead used to clear all data in EnerVista 650 Setup program, enabling the Language, Upgrade firmware 
    version and Upgrade Operating system menu options. 
    						
    							CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
    GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-13
    3.1.6.2  Conf iguration f ile converter 
    The configuration file converter tool provides automatic conversion of configuration files from and older firmware version 
    to a newer version. In order to convert a configuration file, follow these steps:
    1. Working in offline mode, go to File > Conf ig File (*.650) Converter
    2. Select the f ile to be converted.
    3. After source f ile selection is complete, select  c
     onversion settings. Make the following selections:
    Source Model: Indicates source F650 model and original version of selected file.
    Destination model:Drop-down list of available F650 models  and firmware versions. Select a 
    destination model and firmware version. In the bottom part of this section, a 
    brief description of all models affected is displayed in green after selecting one 
    model in the list. 
    Source file pathIndicates the path where source model file is located.
    Figure 3-6: Conf ig f ile (*650) converter menu
    It is possible to change the model type (FXGX) using the conversi on tool. It must be taken into account that part of the logic 
    can be readjusted to fit the new input and output board selection. Notice also that the external wiring of inputs and 
    outputs boards is different for type 1, 2, 4 and 5.
    File conversion to version 7.50 or above   
    The file conversion tool has been modified to include the increased number of setting groups available in firmware version 
    7.50 and above. In firmware version 7.50, the maximum number of setting groups (SG) available increased from 3 to 6.   
    Some considerations must be taken into  account previous to convert (*.650) files from firmware version below 7.50 to 
    firmware version 7.50 or above. In these  cases, the tool internally checks if setting groups functionality is enabled or 
    disable at Setpoint > Control Elements > Setting group in the source file and depend on its value, different conversions 
    are performed in elements affected by setting groups.
    Source Model
    Destination Model
    Source file path 
    						
    							3-14F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
    For example, if the Phase TOC High element is config ured in the source *.650 file as described below:
                         1. Note that fields in blue contain default values
    CASE 1: If the setting groups option is disabled (Setpoint > Control Elements > Setting group) in the source file, conversion 
    is performed in the destination file as follows:
    • Settings of different elements (Phase TOC High 1, 2 and 3)  that belong to Setting group 1(SG1) in the source f ile are 
    copied into elements that belong to Setting Group 1 in the destination f ile.
    • Elements in the other setting groups are conf igured with default values in the conf iguration f ile.
    CASE 2: If the setting groups option is enabled (Setpoint > Control Elements > Setting group) in the source file, conversion 
    to the destination file is as follows:
    • Settings of different elements (Phase TOC High 1, 2 and 3) th at belong to different setting groups in the source f ile are 
    copied into elements that belong to f irst group of f irst three setting groups in the destination f ile 
    • Protection elements in the other groups/setting groups ar e conf
     igured with default values in the destination f ile.
    Phase TOC HighPhase TOC High 1 (G1)Phase TOC High 2 
    (G2)Phase TOC High 3(G3)
    Function ENABLED ENABLEDENABLED
    InputPHASOR(DFT)PHASOR(DFT)PHASOR(DFT)
    Pickup Level 0.10 1.502.00
    Curve Def inite time Def inite timeDef inite time
    TD Multiplier 0.02 0.050.1
    Reset
    INSTANTANEOUSINSTANTANEOUSINSTANTANEOUS
    Voltage Restraint
    DISABLEDDISABLEDDISABLED
    Snapshot Events
    ENABLEDENABLEDENABLED
    SG1SG2SG3SG4SG5SG6
    Phase TOC HighG1G2G3G1G2G3G1G2G3G1G2G3G1G2G3G1G2G3
    FunctionENABLEDDISABLED
    Input                                         PHASOR(DFT)
    Pickup Level0.101.502.001.00
    CurveDef inite timeIEEE Ext Inv
    TD Multiplier0.020.050.101.00
    Reset                                      INSTANTANEOUS
    Voltage 
    Restraint                                     DISABLED
    Snapshot Events                                    ENABLED
    SG1 SG2 SG3SG4SG5 SG6
    Phase TOC High G1G2G3 G1 G2G3 G1G2G3 G1G2 G3G1 G2G3 G1G2 G3
    Function
    ENABLEDDISABLEDENABLEDDISABLEDENABLEDDISABLED
    Input                                                                                                                      PHASOR(DF T)
    Pickup Level
    0.101.001.501,002.001.00
    Curve
    Definite  timeIEEE Ext  InvDef inite timeIEEE Ext InvDef inite timeIEEE Ext Inv
    TD Multiplier
    0.021.000.051,000.101.00
    ResetINSTANTANEOUS
    Voltage 
    RestraintDISABLED
    Snapshot 
    EventsENABLED 
    						
    							CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
    GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-15
    3.1.6.3  Properties
    When this option is selected, the program displays the relay  model information, firmware version, etc. of the file being 
    edited, as shown:
    Figure 3-7: File properties menu
    3.1.6.4  Print options
    The printing options are active only in offline mode with a file open, and not in online mode, connected with the relay.
    Print setup
    Option to configure the printer options and settings.
    Print preview
    Option to preview the whole settings and configuration f ile (*.650) in paper format to be printed as shown:
    Figure 3-8: Print preview of settings f ile 
    						
    							3-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
    Print
    Option to print the relay configuration using the PC default (activ e) printer on port COMx or LPT. This option is active only in 
    offline mode and in file edition (not in online mode while connected to the relay).
    Print to f ile (*xls)
    Option to export the configuration file to an Excel file.
    3.1.6.5  Compare to settings f ile
    This tool provides an automatic comparison  of two different configuration files, or of an online unit to one settings file.
    Open the source *.650 file and select the version and model to compare against. The results of the comparison are 
    displayed as shown:
    Figure 3-9: Compare to settings f ile
    3.1.6.6  PLC checksum calculation
    When working in offline mode, the PLC Checksum calculation option calculates the CRC of the PLC equations and Relay 
    configuration section for the open *.650 file. When a *.650 file  is uploaded to the relay, the calculated PLC Checksum and 
    the actual value of the PLC Checksum read from the relay (Actual values > Status > System Info) must match.
    In order to calculate this checksum, the following sections of the * .650 file are considered:
    • All equations compiled in the f ile and located in EnerVista 650 Setup  Setpoint > Logic conf iguration
    • Conf iguration available in the f ile and located in EnerVista 650 Setup  Setpoint > Relay conf
     iguration, excluding:
    – HMI tab conf iguration
    – All configured text
    – Opening and closing time in the Switchgear section 
    						
    							CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE
    GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-17
    3.1.6.7  Setting checksum calculation
    When working in offline mode, the Settings Checksum calcul ation option calculates the CRC of different configured 
    settings for the open *.650 file. When a *.650 file is uploaded to the relay, the calculated Sett ings Checksum and the actual 
    value of the Settings Checksum read from the relay (Actual values > Status > System Info) must match.
    In order to calculate this checksum, the following sections of the * .650 file are considered:
    • All settings in the relay conf iguration section (Setpoint > Relay conf iguration) excluding:
    – Those communication settings:  Setpoint > Pr
     oduct Setup > Communication settings > SerialPorts  or
    Network  (Ethernet)  or Mod
     bus Protocol or Routing
    – Relay calibration factors
    – Opening and closing time in the Switchgear section
    3.1.7  Setpoint menu
    (*) indicates online only,  (**) indicates offline only
    Setpoint
    Product Setup Communications settings for all protocols and physical mediums. ModBus user map 
    def
    inition, fault report , oscillography, data logger  demand settings and T ime Settings.
    System Setup General Settings, Flex Curves Def inition, Breaker settings, maintenance, switchgear 
    snapshot event
    s management and Miscellaneous Settings.
    Protection Elements Phase, Neutral, Ground, Sensitive Ground and Negative Sequence Current Settings. 
    V
    oltage Elements settings and Power Settings management .
    Control Elements Setting groups, under- and over-frequency settings, synchrocheck, autoreclose, breaker 
    failur
    e, VT fuse failure, broken conductor, locked rotor settings management , Pulse 
    Counters, Analog comparators, Frequency Rate of Change, Load encroachment , max 
    number of starts, Digital Counters, Cold Load Pickup and PLC T imer Masks
    Inputs/Outputs Contact I/O settings for all boards available in device, Remote Comms Force Outputs and 
    V
    irtual inputs.
    Quick Settings Menu that encompass the most important settings to conf igure the device such as; 
    Curr
    ent and Voltage sensing or current protection element .
    Relay Conf iguration Conf iguration of Outputs, LEDs, Operations, Protection Elements, Oscillography, Control 
    Event
    s, Control Elements, Switchgear, Inputs, Virtual Inputs, Operations and HMI. Whole 
    relay conf iguration with internal relay signals or user-def inable ones as logic (virtual 
    outputs).
    Logic Conf iguration Logic conf iguration graphic editor (PLC Editor). It is a PLC Project f ile editor that contains all 
    the int
    ernal drawings used to make the logic (virtual outputs) based on IEC 61131-3 
    standard. Functional block diagram (FDB).
    Procome 
    Conf iguration Procome Configuration tool. Only available for Procome models (5) when communicating 
    thr
    ough Ethernet with EnerVista 650 Setup
    IEC103 Conf iguration  IEC103 settings for available IEC103 models (3) when communicating through Ethernet 
    with Ener
    vista 650 Setup
    Clock (*) Relay synchronization to computer clock or to user-def inable date and time. Online mode 
    only. 
    						
    							3-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    3.1 ENERVISTA 650 SETUP SOFTWARECHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
    3.1.7.1  Product setup menu
    (*) indicates online only,  (**) indicates offline only
    3.1.7.2  Communication settings menu
    This section details the settings related to communication  parameters for the different protocols available in the F650.
    (*) indicates online only, (**) indicates offline only
    Product Setup
    Communication 
    Settings Serial Ports, Network (Ethernet), ModBus Protocol, DNP Slave, IEC 870-5-104,  SNTP settings 
    a
    nd procome (if available on model selection), PTP1588 and Routing (for f irmware version 
    7.00 and higher) 
    ModBus User Map ModBus user map definition. The ModBus user map is formed by 256 records, selectable 
    fr
    om the complete relay ModBus map.
    Fault Report Fault report settings. Possibility to show fault reports on HMI screen.
    OscillographyOscillography settings (trigger position, samples per cycle, etc.). The trigger and digital 
    c
    hannels (up to 16) must be conf igured in  Setpoint > Relay conf iguration.
    Data LoggerData logger conf iguration
    DemandDemand settings. The demand trigger and demand reset signals must be conf igured in 
    Setpoint > R
    elay conf iguration
    Time Settings Time settings.
    COMMUNICATIoN 
    SETTINGS
    Serial PortsBaud rate and parity for COM1 and COM2 serial communication ports.
    Network (Ethernet)Ethernet communication parameters for ETH_1/ETH2 or ETH_E/ETH_A/ETH_B 
    (Depend
    ing on model) (IP Address, Netmask, Gateway IP)
    NOTE: The ModBus Slave address used by Ethernet ports is the one set for 
    C
     OM2.EnerVista 650 Setup software allows programming two different Ethernet 
    addresses, but the f irst IP has always to be set as the second IP Address is an Alias.
    ModBus Protocol ModBus Slave Addresses for serial and Ethernet communication and the ModBus port 
    num
    ber used for ModBus TCP/IP
    DNP3 Slave Physical port , Slave Address for DNP, IP Addresses for Masters, TCP/UDP Port , 
    Un
    solicited Response parameters, Analog scale factors and deadbands, message 
    fragment size, Binary input block.Available for standard and IEC61850 models.
    IEC 870-5-104  TCP Port , Common Addr of ASDU, Cyclic Meter Period and, Synchronization Event 
    settings.
    Available for standard and IEC61850 models.
    SNTP (*) Synchronization over Ethernet settings
    PROCOMEComm port and slave number for procom e protocol. Only available forprocome models (5).
    PTP 1588Precission T ime Protocol 1588 settings. (Available on fw version 7.00 or higher)
    RoutingA default route and a maximum number of 6 static routes may be configured. The 
    de
    fault route is used as the last choice, if no other route towards a given destination is 
    found.This option is only available for version 7.00 and higher. 
    						