CHAPTER 8: F650 TROUBLESHOOTING GUIDE8.1 SYMPTOMS AND RECOMMENDED ACTIONS GEK-113000-AFF650 DIGITAL BAY CONTROLLER 8-3 CategorySymptomPossible causeRecommended action Communications Cannot see properly the web server in F650 with Windows XP. Some windows are in gr ey with a red cross mark. 1.- Disabled Java options in Advanced In ternet Explorer properties or high level of security 2.- Nor Java Virtual Machine installed. 1.1- Go to Advanced in Internet options for Internet explorer and select the three selections in Microsoft VM (Java Virtual Machine) and deselect any other virtual machine not Microsoft , for example SUN. In case Microsoft VM is not installed in the computer, the user must install it using the Microsoft VM installation program msjavx86.exe For internet explorer 6.0 or higher it is not included by default . 1.2.- Try to set a lower level of security in internet explorer options. 1.3.-Delete temporary internet f iles in General screen in internet explorer options. Communication Enervista 650 Setup does not retrieve osc, fault reports and Data Logger f iles Bad communication in TFTP using Windows 2000 Disable and Enable the Ethernet connection on Control Panel inside Windows 2000. Try again 2.1- Install either Microsoft or Sun Jav a Virtual Machine Communication Enervista 650 Setup does not r etrieve osc, fault reports and Data Logger f iles Bad communication in TFTP using W indows 2000 Disable and Enable the Ethernet connection on Co ntrol Panel inside Windows 2000. Try again to retrieve files from relay Firmware and bootware upgrade Bootware The relay gets stuck during the upg rading process after switching off and on the relay, giving the following error message: “ERROR Setting relay in conf iguration mode. Retry? - The relay does not communicate via the front RS232 port To perform the bootware upgrading pr ocess it is necessary to connect the unit thought the front RS232 port . check: • Seri al cable correct(straightthrouhg) and undamaged. • Setti ngs selection in Enervista 650 Setup: Communication > Computer Settings”: o Co m port selected must be the one that is being used to perform this procedure o P arity set to NONE o Baud rate set to 19200 o Control type: No control type o Modbus slave number: any Note: if the bootware upgrade pr ocedure got stuck at this point the relay will not be upgraded. After reboot the relay will continue working with the former f irmware and bootware versions .
8-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF 8.1 SYMPTOMS AND RECOMMENDED ACTIONS CHAPTER 8: F650 TROUBLESHOOTING GUIDE CategorySymptomPossible causeRecommended action Bootware The relay gets stuck at “Send ing f ile imagen_kernel...” -The Ethernet connection does not work pr operly. Serial communications work properly and the fla sh memory has been erased but Ethernet communication does not work properly, check: • R J45 cable used (crossover cable for back-to-back connection and straight through Ethernet cable for hub or switch) • IP a ddress and netmask, gateway are correct and correspond to the ones used in the computer performing the procedure. • E thernet board parameters selection, check that: o 802.1p QOS i s Enabled o Flow contr ol is Auto o Speed & Duplex is Auto (or 10 Mb Full) • If the above points are correct but the problem persists: o Fo rce the Speed & Duplex to 10 Mb Full o Disable and enable the Ethernet connection while the f iles are being sent (during the “sending f ile...” message Note: if the bootware upgrade p rocedure is stuck at this point , the relay flash memory has been erased and the upgrade procedure must be completed to start working with the unit . If the procedure is not completed, the HMI shows the message “Os Loading...” and the relay does not start up . Firmware The procedure can not st art due to ethernet problems -The Ethernet connection does not work pr operly. • Check the same as in the point above for bootware. Note: if the f irmware upgrade pr ocedure is stuck at this point the relay will not be upgraded. After switching it off and on it will continue working with the former firmware and bootware versions. Firmware Program messages “file” do not exist in l ocal drive - File path is too long - File has no f ile attributes • Check the path length, copy the f iles in a shorter path and restart the upgrade procedure. • Chec k the unzip process to see if the file properties are properly set to “File”. • Not e: if the f irmware upgrade procedure is stuck after having been started, the former f irmware has been erased and the upgrade procedure must be completed to start working with the unit . If the procedure is not completed, the HMI shows the message “Os Loading...” and the relay does not start up.
CHAPTER 8: F650 TROUBLESHOOTING GUIDE8.1 SYMPTOMS AND RECOMMENDED ACTIONS GEK-113000-AFF650 DIGITAL BAY CONTROLLER 8-5 FirmwareIt is not possible to to upgra de models without IEC 61850 to models with IEC 61850 automatically - IEC 61850 upgrade from standard mo dels is password protected. • To upgrade from a standard model to a 6 model, ask the factory for an upgrade package, depending on the hardware the existing unit has. If it is hardware 00 a hardware and firmware change is required (password protected), if it is hardware 01 or above only a f irmware change is required (password protected). Firmware During the upgrading pr occes for models with IEC 61850 sometimes it ask for password and sometimes not . - Communication problems during the upgrade procecure. -Th e procedure has been not performed in a continuous way. • EnerV ista 650 Setup program does not ask for a password if the relay model is IEC61850 and the procedure is completed. • If duri ng the process there is any problem and it has to be restarted, this second time the program will ask to conf irm the IEC password. • If the EnerV ista 650 Setup program is closed and started again during the bootware and firmware upgrade process, the program will ask to conf irm the IEC password. Firmware Password for IEC 61850 incorrect - Model change - Incorrect mac or serial number • The password is tied to the model, MAC Address and serial number, so a change in any of these requires a password change. • If the model has been modif ied to add or replace any boards or communication protocol, the IEC 61850 passwords needs to be updated (contact the factory). EnerVista 650 Setup InstallShield Setup Initial ization Error 6001 A previous installation of any product using Inst allShield for installation may have corrupted some of the InstallShield f iles used in the EnerVista 650 Setup installation Delete (or rename) the 0701 folder lo cated in C:\Program Files\Common Files\InstallShield\Professional\RunT i me\ and retry installation
8-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF 8.1 SYMPTOMS AND RECOMMENDED ACTIONS CHAPTER 8: F650 TROUBLESHOOTING GUIDE
GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-1 F650 Digital Bay Controller Appendix A: GE Grid Solutions LOGIC OPERANDS A.1 Operands - F650 - model FX - GX OPERANDS - F650 - MODEL FX - GX Internal System Status autocheck internal states (critical) DSP Internal States (Critical to metering and pr otection) DSP COMM ERROR DSP Communication Error: (0) Rignt communications between DSP and ma in processor; (1) Communication Error between DSP and main processor MAGNETIC MODULE ERR OR Magnetic Module Error: (0) Right Communication between DSP and ma gnetic module processor; (1) Communication Error between DSP and magnetic module processor CALIBRATION ERROR Calibration Error: (0) Right calibration values stored; (1) The calibration values stored are out of the calibration limits. Flash Internal States (Critical to Relay conf iguration and st ored data) E2PROM STATUSE2prom status :(0) Not conf igured or problems during wr iting process ; (1) Conf igured and OK IO Board States (Critical to operation and pr otection) BOARD F STATUS Board F status: (0) Inactive - There is no communication with the boar d (1) Active - There is communication with the board. BOARD G STATUS Board G status: (0) Inactive - There is no communication with the boar d (1) Active - There is communication with the board. BOARD H STATUS Board H status: (0) Inactive - There is no communication with the boar d (1) Active - There is communication with the board. BOARD J STATUS Board J status: (0) Inactive - There is no communication with the boar d (1) Active - There is communication with the board. IEC61850 INTERNAL STATES (NON CRITICAL)
A-2F650 DIGITAL BAY CONTROLLER GEK-113000-AF A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A: IEC61850 Internal StatesICD STATUSUNKNOWN: when the relay has not the IEC61850 pr otocol in the relay model the ICD status is unknow to the unit ICD ERROR: There is an error in the ICD file and the re lay ICD is not operative. To solve this issue it is necessary to send a correct ICD to the relay using the IEC61850 configurator tool. When the ICD error is raised the IEC 61850 will not be operative (the IEC 61850 client, reports and gooses will not work). It is advisable to include the ICD ERROR in the main error signal configured for specific applications. MODIFIED: The settings have been changed in the icd but th ey are still not written in the icd file in the relay IN PROGRESS: The icd setting are being written to the file in the relay OK WITHOUT DAIS: The relay has not got the Use DOI &DAI setting enab led (true) and it is working properly with the ICD file. OK: The relay has got the Use DOI &DAI setting enabled ( true) and it is working properly with the ICD file. When that setting is set to true the icd setting prevails over the relay settings. OTHER INTERNAL STATES (NON CRITICAL) Other internal states USER MAP STATUS User map status: (0) Not conf igured ; (1) Conf igured FACTORY CALIBRATION Calibration status (0) Relay calibrated; (1) Not calibrated FLEXCURVE A STATUS User curve A: (0) Not conf igured (1) Conf igured FLEXCURVE B STATUS User curve B: (0) Not conf igured (1) Configured FLEXCURVE C STATUS User curve C: (0) Not conf igured (1) Conf igured FLEXCURVE D STATUS User curve D: (0) Not conf igured (1) Configured Green Zone Memory internal status Yellow Zone Memory internal status Orange Zone Memory internal status Red Zone Memory internal status UpT ime System T ime Autocheck Internal States (Not available) TIMER STATUS Real time clock autocheck (not available) GRAPHIC STATUS Graphic display status (not available) ALARM TEXT ARRAY Text display status (not available) OPERANDS - F650 - MODEL FX - GX Internal System Status
APPENDIX A: A.1 OPERANDS - F650 - MODEL FX - GX GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-3 Note: It is advisable to use the critical alarms to raise an event or to light a warning LED for maintenance purposes. See the example below, the Board X Status depends on the relay model. Figure A–1: Protection Alarm Signal Conf igurable Logic Outputs (512 elements) VIRTUAL OUTPUT 000 Configurable logic output 000 VIRTUAL OUTPUT 001 Configurable logic output 001 ... ... VIRTUAL OUTPUT 511 Configurable logic output 511 Operation Bits (24 elements) OPERATION BIT 1 Operation bit 001: (0) the configured time expires or whe n success conditions are met;(1) operation 1 is executed and interlocks are fulf illed. OPERATION BIT 2 Operation bit 002: (0) the configured time expires or whe n success conditions are met;(1) operation 2 is executed and interlocks are fulf illed. ... ... OPERATION BIT 24 Operation bit 024: (0) the configured time expires or when success conditions are met;(1) operation 24 is executed and interlocks are fulf illed. OPERANDS - F650 - MODEL FX - GX Internal System Status
A-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A: Control Event Bits (128 elements)CONTROL EVENT 1 Control Event 1 Activation Bit CONTROL EVENT 2 Control Event 2 Activation Bit ... ... CONTROL EVENT 128 Control Event 128 Activation Bit Latched Virtual Inputs (32 elements) LATCHED VIRT IP 1 Latched virtual input 1 LATCHED VIRT IP 2 Latched virtual input 2 ... ... LATCHED VIRT IP 32 Latched virtual input 32 Self Reset Virtual Inputs (32 elements) SELF-RST VIRT IP 1 Self reset virtual input 1 SELF-RST VIRT IP 2 Self reset virtual input 2 ... ... SELF-RST VIRT IP 32 Self reset virtual input 32 Contact Inputs Type 1Board CONT IP_X_CC1 Input 1 (CC1) in Board X CONT IP_X_CC2 Input 2 (CC2) in Board X ... ... CONT IP_X_CC16 Input 16 (CC16) in Board X Contact Inputs Type 2 Board CONT IP_X_CC1 Input 1 (CC1) in Board X CONT IP_X_CC2 Input 2 (CC2) in Board X ... ... CONT IP_X_CC8 Input 8 (CC8) in Board X CONT IP_X_CC9 (V a_COIL1) Contact Input 09 (Va_COIL1) for slot X. Input voltage (Va) det ected, Circuit 1. Complete circuit supervised CONT IP_X_CC10 (V b_COIL1) Contact Input 10 (Vb_COIL1) for slot X. Input voltage (Vb) det ected, Circuit 1. Complete circuit supervised CONT IP_X_CC11 (V a_COIL2) Contact Input 11 (Va_COIL2) for slot X. Input voltage (Va) det ected, Circuit 1. Complete circuit supervised CONT IP_X_CC12 (V b_COIL2) Contact Input 12 (Vb_COIL2) for slot X. Input voltage (Vb) det ected, Circuit 2. Complete circuit supervised CONT IP_X_CC13 (O 7_SEAL) Contact Input 13 (07_SEAL) for slot X. Current detected. Con tact output associated with current flow > 100 mA latched CONT IP_X_CC14 (O 8_SEAL) Contact Input 14 (08_SEAL) for slot X. Current detected. Con tact output associated with current flow > 100 mA latched CONT IP_X_CC15 (S UP_COIL1) Contact Input 15 (SUP_COIL1) for slot X. Output for cir cuit 1 supervision element CONT IP_X_CC16 (S UP_COIL2) Contact Input 16 (SUP_COIL2) for slot X. Output for cir cuit 2 supervision element Contact Inputs Type 4 Board CONT IP_X_CC1 Input 1 (CC1) in Board X CONT IP_X_CC2 Input 2 (CC2) in Board X ... ... CONT IP_X_CC32 Input 32 (CC32) in Board X OPERANDS - F650 - MODEL FX - GX Internal System Status
APPENDIX A: A.1 OPERANDS - F650 - MODEL FX - GX GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-5 Contact Inputs Type 5 Board (Digital Values)CONT IP_X_CC1 Input 1 (CC1) in Board X CONT IP_X_CC2 Input 2 (CC2) in Board X ... ... CONT IP_X_CC16 Input 16 (CC16) in Board X Contact Inputs Type 5 Board (Analog Values) ANALOG_INP_X_01 Analog Input 01 in Board X ANALOG_INP_X_02 Analog Input 02 in Board X ANALOG_INP_X_03 Analog Input 03 in Board X ... ... ANALOG_INP_X_08 Analog Input 08 in Board X Contact Outputs Type 1 & 2 Board Activation si gnals CONT OP OPER_X_01 Logic signal for Output 1 activation. Board X CONT OP OPER_X_02 Logic signal for Output 2 activation. Board X ... ... CONT OP OPER_X_08 Logic signal for Output 8 activation. Board X Contact Outputs Type 1 & 2 Board Reset signals CONT RESET_X_01 board X, 01 latched output reset CONT RESET_X_02 board X, 02 latched output reset ... ... CONT RESET_X_08 board X, 08 latched output reset Contact Outputs Type 1 & 2 Board Status CONT OP_X_01 Contact output 1 Board X operation CONT OP_X_02 Contact output 2 Board X operation ... ... CONT OP_X_8 Contact output 8 Board X operation Board Status BOARD X STATUSBoard X status: (0) Inactive - There is no communication with the board (1) Active - There is communication with the board Switchgear status (16 elements) SWITCH 1 A INPUT Contact input type A to switchgear Function 1 SWITCH 1 B INPUT Contact input type B to switchgear Function 1 SWITCH 2 A INPUT Contact input type A to switchgear Function 2 SWITCH 2 B INPUT Contact input type B to switchgear Function 2 ... ... SWITCH 16 A INPUT Contact input type A to switchgear Function 16 SWITCH 16 B INPUT Contact input type B to switchgear Function 16 Switchgear outputs (16 elements) SWITCH 1 A STATUS Contact logic output type A from switchgear Function 1 SWITCH 1 B STATUS Contact logic output type B from switchgear Function 1 SWITCH 2 A STATUS Contact logic output type A from switchgear Function 2 SWITCH 2 B STATUS Contact logic output type B from switchgear Function 2 ... ... SWITCH 16 A STATUS Contact logic output type A from switchgear Function 16 SWITCH 16 B STATUS Contact logic output type B from switchgear Function 16 OPERANDS - F650 - MODEL FX - GX Internal System Status
A-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A: Switchgear states (16 elements)SWITCH 1 OPEN switchgear 1 open SWITCH 1 CLOSED switchgear 1 closed SWITCH 1 00_ERROR Error 00 switchgear 1 (contact A = 0, contact B = 0) SWITCH 1 11_ERROR Error 11 switchgear 1 (contact A = 1, contact B = 1) SWITCH 2 OPEN Switchgear 2 open SWITCH 2 CLOSED Switchgear 2 closed SWITCH 2 00_ERROR Error 00 switchgear 2 (contact A = 0, contact B = 0) SWITCH 2 11_ERROR Error 11 switchgear 2 (contact A = 1, contact B = 1) ... ... SWITCH 16 OPEN Switchgear 16 open SWITCH 16 CLOSED Switchgear 16 closed SWITCH 16 00_ERROR Error 00 switchgear 16 (contact A = 0, contact B = 0) SWITCH 16 11_ERROR Error 11 switchgear 16 (contact A = 1, contact B = 1) Switchgear Open-Close Initializing States SWITCH 1 OPEN INIT Switchgear 1 opening initiation SWITCH 1 CLOSE INIT Switchgear 1 closing initiation SWITCH 2 OPEN INIT Switchgear 2 opening initiation SWITCH 2 CLOSE INIT Switchgear 2 closing initiation ... ... SWITCH 16 OPEN INIT Switchgear 16 opening initiation SWITCH 16 CLOSE INIT Switchgear 16 closing initiation Switchgear Fail States SWGR 1 FAIL TO OPEN Failure to open Switchgear 1 SWGR 2 FAIL TO OPEN Failure to open Switchgear 2 ... ... SWGR 16 FAIL TO OPEN Failure to open Switchgear 16 SWGR 1 FAIL TO CLOSE Failure to close Switchgear 1 SWGR 2 FAIL TO CLOSE Failure to close Switchgear 2 ... ... SWGR 16 FAIL TO CLOSE Failure to close Switchgear 16 OPERANDS - F650 - MODEL FX - GX Internal System Status