    							CHAPTER 8:  F650 TROUBLESHOOTING GUIDE8.1 SYMPTOMS AND RECOMMENDED ACTIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 8-3
    CategorySymptomPossible causeRecommended action
    Communications Cannot see properly 
    the web 
    
    server in F650 
    with Windows XP. 
    Some windows are in 
    gr
     ey with a red cross 
    mark. 1.- Disabled Java options in Advanced 
    In
    
    ternet Explorer properties or high 
    level of security
    2.- Nor Java Virtual Machine installed. 1.1- Go to Advanced in Internet 
    options
    for Internet explorer and select the
    three selections in Microsoft VM (Java
    Virtual Machine) and deselect any
    other virtual machine not Microsoft , 
    for
    example SUN.
    In case Microsoft VM is not installed in
    the computer, the user must install it
    using the Microsoft VM installation
    program msjavx86.exe
    For internet explorer 6.0 or higher it is
    not included by default .
    1.2.- Try to set a lower level of security 
    in
    internet explorer options.
    1.3.-Delete temporary internet f iles in
    General screen in internet explorer
    options.
    Communication Enervista 650 Setup
    does not retrieve osc,
    fault reports and Data
    Logger f iles
    Bad communication in TFTP using
    Windows 2000
    Disable and Enable the Ethernet
    connection on Control Panel inside
    Windows 2000. Try again
    2.1- Install either Microsoft or Sun 
    Jav
    
    a Virtual Machine
     
    Communication Enervista 650 Setup 
    does not r
    
    etrieve osc, 
    fault reports and Data 
    Logger f iles Bad communication in TFTP using 
    W
    indows 2000 Disable and Enable the Ethernet 
    connection on Co
    ntrol Panel inside 
    Windows 2000. Try again to retrieve 
    files from relay
    Firmware and bootware upgrade
    Bootware The relay gets stuck 
    during the upg
    
    rading 
    process after 
    switching off and on 
    the relay, giving the 
    following error 
    message: “ERROR 
    Setting relay in 
    conf iguration mode. 
    Retry? - The relay does not communicate via 
    the 
    front RS232 port To perform the bootware upgrading 
    pr
    ocess it is necessary to connect the 
    unit thought the front RS232 port . 
    check:
    •  Seri
    al cable correct(straightthrouhg) 
    and undamaged.
    • Setti
    ngs selection in Enervista 650 
    Setup: Communication > Computer 
    Settings”:
    o Co
    m port selected must be the 
    one that is being used to perform 
    this procedure
    o  P
    arity set to NONE
    o  Baud rate set to 19200 
    o Control type: No control type
    o Modbus slave number: any
    Note: if the bootware upgrade 
    pr ocedure got stuck at this point the 
    relay will not be upgraded. After 
    reboot the relay will continue 
    working with the former f irmware 
    and bootware versions . 
    						
    							8-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    8.1 SYMPTOMS AND RECOMMENDED ACTIONS CHAPTER 8:  F650 TROUBLESHOOTING GUIDE
    CategorySymptomPossible causeRecommended action
    Bootware The relay gets stuck at 
    “Send
    
    ing f ile 
    imagen_kernel...” -The Ethernet connection does not 
    work pr
    operly. Serial communications work properly 
    and the fla
    sh memory has been 
    erased but Ethernet communication 
    does not work properly, check:
    •   R
    J45 cable used (crossover cable for 
    back-to-back connection and straight 
    through Ethernet cable for hub or 
    switch)
    •  IP a
    ddress and netmask, gateway 
    are correct and correspond to the 
    ones used in the computer performing 
    the procedure. 
    •  E
    thernet board parameters 
    selection, check that:
    o 802.1p QOS i
     s Enabled
    o Flow contr ol is Auto
    o Speed & Duplex  is Auto (or 
    10     Mb Full)
    •   If 
    the above points are correct but 
    the problem persists: 
    o Fo
    rce the Speed & Duplex to 
    10 Mb Full
    o 
     Disable and enable the 
    Ethernet connection while the 
    f iles are being sent (during the 
    “sending f ile...” message
    Note: if the bootware upgrade 
    p
     rocedure is stuck at this point , the 
    relay flash memory has been erased 
    and the upgrade procedure must be 
    completed to start working with the 
    unit . If the procedure is not 
    completed, the HMI shows the 
    message “Os Loading...” and the 
    relay does not start up .
    Firmware The procedure can not 
    st
    
    art due to ethernet 
    problems -The Ethernet connection does not 
    work pr
    operly. • 
    Check the same as in the point 
    above for bootware.
    Note: if the f irmware upgrade 
    pr
    
    ocedure is stuck at this point the 
    relay will not be upgraded. After 
    switching it off and on it will continue 
    working with the former firmware and 
    bootware versions.
    Firmware Program messages
    “file” do not exist in 
    l
    
    ocal drive - File path is too long
    - File has no f ile attributes
    •  Check the path length, copy the f iles 
    in a shorter path and restart the 
    upgrade procedure.
    •  Chec
    k the unzip process to see if the 
    file properties are properly set to “File”.
    • 
    Not
    e: if the f irmware upgrade 
    procedure is stuck after having been 
    started, the former f irmware has 
    been erased and the upgrade 
    procedure must be completed to 
    start working with the unit . If the 
    procedure is not completed, the HMI 
    shows the message “Os Loading...” 
    and the relay does not start up. 
    						
    							CHAPTER 8:  F650 TROUBLESHOOTING GUIDE8.1 SYMPTOMS AND RECOMMENDED ACTIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 8-5
    FirmwareIt is not possible to to 
    upgra
    de models 
    without IEC 61850 to 
    models with IEC 61850 
    automatically - IEC 61850 upgrade from standard 
    mo
    dels is password protected. • 
    To upgrade from a standard model 
    to a 6 model, ask the factory for an 
    upgrade package, depending on the 
    hardware the existing unit has. If it is 
    hardware 00 a hardware and 
    firmware change is required 
    (password protected), if it is hardware 
    01 or above only a f irmware change is 
    required (password protected).
    Firmware During the upgrading 
    pr
    
    occes for models 
    with IEC 61850 
    sometimes it ask for 
    password and 
    sometimes not . - 
    Communication problems during the 
    upgrade procecure.
    -Th
    e procedure has been not 
    performed in a continuous way. • 
    EnerV
    ista 650 Setup program does 
    not ask for a password if the relay 
    model is IEC61850 and the procedure 
    is completed.
    •   If duri
    ng the process there is any 
    problem and it has to be restarted, this 
    second time the program will ask to 
    conf irm the IEC password.
    •  If the EnerV
     ista 650 Setup program 
    is closed and started again during the 
    bootware and firmware upgrade 
    process, the program will ask to 
    conf irm the IEC password.
    Firmware Password for 
    IEC
    
    61850 incorrect - Model change
    - Incorrect mac or serial number •  
    The password is tied to the model, 
    MAC Address and serial number, so a 
    change in any of these requires a 
    password change.
    •  If the 
    model has been modif ied to 
    add or replace any boards or 
    communication protocol, the IEC 
    61850 passwords needs to be 
    updated (contact the factory).
    EnerVista 650 Setup InstallShield Setup 
    Initial
    
    ization Error 
    6001 A previous installation of any product 
    using Inst
    allShield for installation may 
    have corrupted some of the 
    InstallShield f iles used in the EnerVista 
    650 Setup installation Delete (or rename) the 0701 folder 
    lo
    cated in  C:\Program Files\Common 
    Files\InstallShield\Professional\RunT i
    me\ and retry installation 
    						
    							8-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    8.1 SYMPTOMS AND RECOMMENDED ACTIONS CHAPTER 8:  F650 TROUBLESHOOTING GUIDE 
    						
    							GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-1
    F650 Digital Bay Controller
    Appendix A:  
    GE
    Grid Solutions
    LOGIC OPERANDS
    A.1  Operands - F650 - model FX - GX
    OPERANDS - F650 - MODEL FX - GX
    Internal System Status
    autocheck internal states (critical)
    DSP Internal States (Critical to metering and 
    pr
    
    otection) DSP COMM ERROR
    DSP Communication Error: (0) Rignt communications 
    between DSP and ma
    
    in processor; (1) Communication 
    Error between DSP and main processor
    MAGNETIC MODULE 
    ERR
     OR Magnetic Module Error: (0) Right Communication 
    between DSP and ma
    gnetic module processor; (1) 
    Communication Error between DSP and magnetic 
    module processor
    CALIBRATION ERROR Calibration Error: (0) Right calibration values stored; (1) 
    The
    
     calibration values stored are out of the calibration 
    limits.
    Flash Internal States (Critical to Relay conf iguration 
    and st
     ored data) E2PROM STATUSE2prom status :(0) Not conf igured or problems during 
    wr
    iting process ; (1) Conf igured and OK
    IO Board States (Critical to operation and 
    pr
     otection) BOARD F STATUS
    Board F status: (0) Inactive - There is no communication 
    with the boar
    
    d (1) Active - There is communication with 
    the board. 
    BOARD G STATUS Board G status: (0) Inactive - There is no communication 
    with the boar
    
    d (1) Active - There is communication with 
    the board. 
    BOARD H STATUS Board H status: (0) Inactive - There is no communication 
    with the boar
    
    d (1) Active - There is communication with 
    the board. 
    BOARD J STATUS Board J status: (0) Inactive - There is no communication 
    with the boar
    
    d (1) Active - There is communication with 
    the board. 
    IEC61850 INTERNAL STATES (NON CRITICAL) 
    						
    							A-2F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A:  
    IEC61850 Internal StatesICD STATUSUNKNOWN: when the relay has not the IEC61850 
    pr
    
    otocol in the relay model the ICD status is unknow to 
    the unit
    ICD ERROR: There is an error in the ICD file and the 
    re
     lay ICD is not operative. To solve this issue it is 
    necessary to send a correct ICD to the relay using the 
    IEC61850 configurator tool. When the ICD error is raised 
    the IEC 61850 will not be operative (the IEC 61850 
    client, reports and gooses will  not work). It is advisable to 
    include the ICD ERROR in the main error signal 
    configured for specific applications.
    MODIFIED: The settings have been changed in the icd 
    but th
     ey are still not written in the icd file in the relay
    IN PROGRESS: The icd setting are being written to the 
    file in the relay
    OK WITHOUT DAIS: The relay has not got the Use DOI 
    &DAI setting enab
     led (true) and it is working properly 
    with the ICD file.
    OK: The relay has got the Use DOI &DAI setting 
    enabled (
     true) and it is working properly with the ICD file. 
    When that setting is set to true the icd setting prevails 
    over the relay settings.
    OTHER INTERNAL STATES (NON CRITICAL)
    Other internal states USER MAP STATUS
    User map status:  (0) Not conf igured ; (1) Conf igured
    FACTORY CALIBRATION Calibration status (0) Relay calibrated; (1) Not calibrated
    FLEXCURVE A STATUS User curve A: (0) Not conf igured (1) Conf igured
    FLEXCURVE B STATUS User curve B: (0) Not conf igured (1) Configured
    FLEXCURVE C STATUS User curve C: (0) Not conf igured (1) Conf igured
    FLEXCURVE D STATUS User curve D: (0) Not conf igured (1) Configured
    Green Zone Memory internal status
    Yellow Zone Memory internal status
    Orange Zone Memory internal status
    Red Zone Memory internal status
    UpT ime System T ime
    Autocheck Internal States (Not available) TIMER STATUS
    Real time clock autocheck (not available)
    GRAPHIC STATUS Graphic display status (not available)
    ALARM TEXT ARRAY
    Text display status (not available)
    OPERANDS - F650 - MODEL FX - GX
    Internal System Status 
    						
    							APPENDIX A:  A.1 OPERANDS - F650 - MODEL FX - GX
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-3
    Note: It is advisable to use the critical alarms to raise an event or to light a warning LED for maintenance purposes. See 
    the example below, the Board X Status depends on the relay model.
    Figure A–1: Protection Alarm Signal
    Conf igurable Logic Outputs (512 elements) VIRTUAL OUTPUT 000
    Configurable logic output 000
    VIRTUAL OUTPUT 001 Configurable logic output 001
    ... ...
    VIRTUAL OUTPUT 511 Configurable logic output 511
    Operation Bits (24 elements) OPERATION BIT 1
    Operation bit 001: (0) the configured time expires or 
    whe
    
    n success conditions are met;(1) operation 1 is 
    executed and interlocks are fulf illed. 
    OPERATION BIT 2 Operation bit 002: (0) the configured time expires or 
    whe
    
    n success conditions are met;(1) operation 2 is 
    executed and interlocks are fulf illed. 
    ... ...
    OPERATION BIT 24
    Operation bit 024: (0) the configured time expires or 
    when success conditions are met;(1) operation 24 is 
    executed and interlocks are fulf illed. 
    OPERANDS - F650 - MODEL FX - GX
    Internal System Status 
    						
    							A-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A:  
    Control Event Bits (128 elements)CONTROL EVENT 1
    Control Event 1 Activation Bit
    CONTROL EVENT 2 Control Event 2 Activation Bit
    ... ...
    CONTROL EVENT 128 Control Event 128 Activation Bit
    Latched Virtual Inputs (32 elements) LATCHED VIRT IP 1
    Latched virtual input 1
    LATCHED VIRT IP 2 Latched virtual input 2
    ... ...
    LATCHED VIRT IP 32 Latched virtual input 32
    Self Reset Virtual Inputs (32 elements) SELF-RST VIRT IP 1
    Self reset virtual input 1
    SELF-RST VIRT IP 2 Self reset virtual input 2
    ... ...
    SELF-RST VIRT IP 32 Self reset virtual input 32
    Contact Inputs Type 1Board CONT IP_X_CC1
    Input 1 (CC1) in Board X
    CONT IP_X_CC2 Input 2 (CC2) in Board X
    ... ...
    CONT IP_X_CC16 Input 16 (CC16) in Board X
    Contact Inputs Type 2 Board  CONT IP_X_CC1
    Input 1 (CC1) in Board X
    CONT IP_X_CC2 Input 2 (CC2) in Board X
    ... ...
    CONT IP_X_CC8 Input 8 (CC8) in Board X
    CONT IP_X_CC9 
    (V
     a_COIL1) Contact Input 09 (Va_COIL1) for slot X. Input voltage (Va) 
    det
    ected, Circuit 1. Complete circuit supervised
    CONT IP_X_CC10 
    (V
     b_COIL1) Contact Input 10 (Vb_COIL1) for slot X. Input voltage (Vb) 
    det
    ected, Circuit 1. Complete circuit supervised
    CONT IP_X_CC11 
    (V
     a_COIL2) Contact Input 11 (Va_COIL2) for slot X. Input voltage (Va) 
    det
    ected, Circuit 1. Complete circuit supervised
    CONT IP_X_CC12 
    (V
     b_COIL2) Contact Input 12 (Vb_COIL2) for slot X. Input voltage (Vb) 
    det
    ected, Circuit 2. Complete circuit supervised
    CONT IP_X_CC13 
    (O
     7_SEAL) Contact Input 13 (07_SEAL) for slot X. Current detected. 
    Con
    tact output associated with current flow > 100 mA 
    latched 
    CONT IP_X_CC14 
    (O
     8_SEAL) Contact Input 14 (08_SEAL) for slot X. Current detected. 
    Con
    tact output associated with current flow > 100 mA 
    latched
    CONT IP_X_CC15 
    (S
     UP_COIL1) Contact Input 15 (SUP_COIL1) for slot X. Output for 
    cir
    cuit 1 supervision element 
    CONT IP_X_CC16 
    (S
     UP_COIL2) Contact Input 16 (SUP_COIL2) for slot X. Output for 
    cir
    cuit 2 supervision element
    Contact Inputs Type 4 Board CONT IP_X_CC1
    Input 1 (CC1) in Board X
    CONT IP_X_CC2 Input 2 (CC2) in Board X
    ... ...
    CONT IP_X_CC32
    Input 32 (CC32) in Board X
    OPERANDS - F650 - MODEL FX - GX
    Internal System Status 
    						
    							APPENDIX A:  A.1 OPERANDS - F650 - MODEL FX - GX
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-5
    Contact Inputs Type 5 Board (Digital Values)CONT IP_X_CC1
    Input 1 (CC1) in Board X
    CONT IP_X_CC2 Input 2 (CC2) in Board X
    ... ...
    CONT IP_X_CC16 Input 16 (CC16) in Board X
    Contact Inputs Type 5 Board (Analog Values) ANALOG_INP_X_01
    Analog Input 01 in Board X
    ANALOG_INP_X_02 Analog Input 02 in Board X
    ANALOG_INP_X_03 Analog Input 03 in Board X
    ... ...
    ANALOG_INP_X_08 Analog Input 08 in Board X
    Contact Outputs Type 1 & 2 Board  Activation 
    si
     gnals CONT OP OPER_X_01
    Logic signal for Output 1 activation. Board X
    CONT OP OPER_X_02 Logic signal for Output 2 activation. Board X
    ... ...
    CONT OP OPER_X_08 Logic signal for Output 8 activation. Board X
    Contact Outputs Type 1 & 2 Board  Reset signals CONT  RESET_X_01
    board X, 01 latched output reset
    CONT  RESET_X_02 board X, 02 latched output reset
    ... ...
    CONT  RESET_X_08 board X, 08 latched output reset
    Contact Outputs Type 1 & 2 Board  Status CONT OP_X_01
    Contact output 1 Board X operation
    CONT OP_X_02 Contact output 2 Board X operation
    ... ...
    CONT OP_X_8 Contact output 8 Board X operation
    Board Status BOARD X STATUSBoard X status: (0) Inactive - There is no communication 
    with the 
    
    board  (1) Active - There is communication with 
    the board
    Switchgear status (16 elements) SWITCH 1 A INPUT
    Contact input type A to switchgear Function 1
    SWITCH 1 B INPUT Contact input type B to switchgear Function 1
    SWITCH 2 A INPUT Contact input type A to switchgear Function 2
    SWITCH 2 B INPUT Contact input type B to switchgear Function 2
    ... ...
    SWITCH 16 A INPUT Contact input type A to switchgear Function 16
    SWITCH 16 B INPUT Contact input type B to switchgear Function 16
    Switchgear outputs (16 elements) SWITCH 1 A STATUS
    Contact logic output type A from switchgear Function 1 
    SWITCH 1 B STATUS Contact logic output type B from switchgear Function 1 
    SWITCH 2 A STATUS Contact logic output type A from switchgear Function 2 
    SWITCH 2 B STATUS Contact logic output type B from switchgear Function 2 
    ... ...
    SWITCH 16 A STATUS Contact logic output type A from switchgear Function 
    16 
    SWITCH 16 B STATUS
    Contact logic output type B from switchgear Function 
    16 
    OPERANDS - F650 - MODEL FX - GX
    Internal System Status 
    						
    							A-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A:  
    Switchgear states (16 elements)SWITCH 1 OPEN
    switchgear 1 open
    SWITCH 1 CLOSED switchgear 1 closed
    SWITCH 1 00_ERROR Error 00 switchgear 1 (contact A = 0, contact B = 0)
    SWITCH 1 11_ERROR Error 11 switchgear 1 (contact A = 1, contact B = 1)
    SWITCH 2 OPEN Switchgear 2 open
    SWITCH 2 CLOSED Switchgear 2 closed
    SWITCH 2 00_ERROR Error 00 switchgear 2 (contact A = 0, contact B = 0)
    SWITCH 2 11_ERROR Error 11 switchgear 2 (contact A = 1, contact B = 1)
    ... ...
    SWITCH 16 OPEN Switchgear 16 open
    SWITCH 16 CLOSED Switchgear 16 closed
    SWITCH 16 00_ERROR Error 00 switchgear 16 (contact A = 0, contact B = 0)
    SWITCH 16 11_ERROR Error 11 switchgear 16 (contact A = 1, contact B = 1)
    Switchgear Open-Close Initializing States SWITCH 1 OPEN INIT
    Switchgear 1 opening initiation
    SWITCH 1 CLOSE INIT Switchgear 1 closing initiation
    SWITCH 2 OPEN INIT Switchgear 2 opening initiation
    SWITCH 2 CLOSE INIT Switchgear 2 closing initiation
    ... ...
    SWITCH 16 OPEN INIT Switchgear 16 opening initiation
    SWITCH 16 CLOSE INIT Switchgear 16 closing initiation
    Switchgear Fail States SWGR 1 FAIL TO OPEN
    Failure to open Switchgear 1
    SWGR 2 FAIL TO OPEN Failure to open Switchgear 2
    ... ...
    SWGR 16 FAIL TO OPEN Failure to open Switchgear 16
    SWGR 1 FAIL TO CLOSE Failure to close Switchgear 1
    SWGR 2 FAIL TO CLOSE Failure to close Switchgear 2
    ... ...
    SWGR 16 FAIL TO CLOSE
    Failure to close Switchgear 16
    OPERANDS - F650 - MODEL FX - GX