CHAPTER 6: COMMISSIONING6.12 TIME OVERCURRENT (51PH, 51PL, 51N, 51G, 46) GEK-113000-AF F650 DIGITAL BAY CONTROLLER 6-13 6.12 Time overcurrent (51PH, 51PL, 51N, 51G, 46) Set the relay to trip for the protection element being tested. Configure any of the outputs to be activated only by the protection element being tested. Apply 0.9 times the Pickup current and check that the relay does not trip. Apply 1.5 times the Pickup current. The relay should trip according to the time corresponding to its set curve. Apply 5 times the Pickup current. The relay should trip according to the time corresponding to its set curve. Protection Element Settings (51PH, 51PL, 51N, 51G and 46) SettingValueUnit FunctionEnabled InputPhasor (DFT) Pickup Level1A CurveModify for each test TD MultiplierModify for each test Voltage RestraintDisabled ElementPhaseCurve typeDialTimes IpickupTripping times (sec) EXPECTEDAdmissible 51PH IAIEEE Ext Inv 0.50.9NA 1.5 11.34 [11.00 – 11.90] 5 0.648 [0.600 – 0.710] IB IEC Curve A 0.050.9NA 1.5 0.860 [0.750 – 0.950] 5 0.214 [0.200 – 0.300] 51PL ICIEEE Ext Inv 0.50.9NA 1.5 11.34 [11.00 – 11.60] 5 0.648 [0.600 – 0.710] IB IEC Curve A 0.050.9NA 1.5 0.860 [0.750 – 0.950] 5 0.214 [0.200 – 0.300] 51N ICIEEE Ext Inv 0.50.9NA 1.5 11.34 [11.00 – 11.60] 5 0.648 [0.600 – 0.710] 51G IGDef inite T ime 20.9NA 5 2.000 [1.900 – 2.100] 46 I2IEC Curve A 0.050.9NA 1.5 0.860 [0.750 – 0.950] 5 0.214 [0.200 – 0.300]
![](/img/blank.gif)
6-14F650 DIGITAL BAY CONTROLLER GEK-113000-AF 6.13 DIRECTIONAL ELEMENTS (67P, 67N, 67G, 67SG) CHAPTER 6: COMMISSIONING 6.13 Directional elements (67P, 67N, 67G, 67SG) In order to test directional units in the relay, instantaneous trips are commanded. Two points are tested, per phase, test element. In order to test the directional units, configure (in the Setpoint > Relay Configuration > Protection Elements screen of the EnerVista 650 Setup program), some overcurrent element to be su pervised by a directional unit. This way, if the directional element is enabled and detects the fault in the block direction, then the overcurrent unit does not operate. If the directional element is not enabled or if it is enabled and it detects a fault in a trip direction, then the overcurrent unit operates if the set current level is exceeded. 6.13.1 67P element Activate only protection elements 50PH and 67P and set the relay as follows: Configure one of the outputs to be activated only by unit 50PH. Apply the following tests: 6.13.2 67N element Activate only protection elements 50N and 67N and set the relay as follows: Configure one of the outputs to be activated only by unit 50G. 67P Settings50PH Settings Function ENABLEDFunction ENABLED MTA 45 DegInput PHASOR (DFT) Direction FORWARDPickup Level 0.50 A Block Logic PERMISSIONTrip Delay 0.30 Pol V Threshold 30 VReset Delay 0.00 ElementsPhase under testPolarization PhaseElement trip ChannelMagnitudeChannelMagnitude ModArgModArg 50PH/67P IA2 A0º VIII 60 V0º NO 60 V180ºYES IB 2 A0º VI 60 V0º NO 60 V180ºYES IC 2 A0º VII 60 V0º NO 60 V180ºYES 67N Settings50N Settings Function ENABLEDFunction ENABLED MTA -45 DegInput PHASOR (DFT) Direction FORWARDPickup Level 0.50 A Polarization VOTrip Delay 0.30 Block Logic PERMISSIONReset Delay 0.00 Pol V Threshold 10 V
![](/img/blank.gif)
CHAPTER 6: COMMISSIONING6.13 DIRECTIONAL ELEMENTS (67P, 67N, 67G, 67SG) GEK-113000-AF F650 DIGITAL BAY CONTROLLER 6-15 Apply the following tests: 6.13.3 67G element Activate only protection elements 50G and 67G and set the relay as follows: Configure one of the outputs to be activated only by unit 50G. Apply the following tests: 6.13.4 67SG element Activate only protection elements 50SG and 67SG and set the relay as follows: ElementsPhase under testPolarization PhaseElement trip ChannelMagnitudeChannelMagnitude ModArgModArg 50N/67N IA2 A0º VI 60 V0º NO 60 V 180º YES IB 0 A0º VII 0 V0º IC 0 A0º VIII 0 V0º 67G Settings50G Settings Function ENABLEDFunction ENABLED MTA -45 DegInput PHASOR (DFT) Direction FORWARDPickup Level 0.50 A Polarization VOTrip Delay 0.30 Block Logic PERMISSIONReset Delay 0.00 Pol V Threshold 10 V ElementsPhase under testPolarization PhaseElement trip ChannelMagnitudeChannelMagnitude ModArgModArg 50G/67G IG2 A0º VI 60V0º NO 60V180ºYES VII 0º VIII 0º 67SG Settings50SG Settings Function ENABLEDFunctionENABLED MTA -45 DegInputPHASOR (DFT) Direction FORWARDPickup Level0.50 A Polarization VOTrip Delay0.30 Block Logic PERMISSIONReset Delay0.00
![](/img/blank.gif)
6-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF 6.13 DIRECTIONAL ELEMENTS (67P, 67N, 67G, 67SG) CHAPTER 6: COMMISSIONING Configure one of the outputs to be activated only by unit 50SG. Apply the following tests: Pol V Threshold10 V ElementsPhase under testPolarization PhaseElement trip ChannelMagnitudeChannelMagnitude ModArgModArg 50SG/67SG ISG2 A0º VI 60 V0º NO 60 V 180º YES VII 0 V0º VIII 0 V0º
![](/img/blank.gif)
CHAPTER 6: COMMISSIONING6.14 UNDERVOLTAGE ELEMENTS (27P, 27X) GEK-113000-AFF650 DIGITAL BAY CONTROLLER 6-17 6.14 Undervoltage elements (27P, 27X) 6.14.1 27P element Set the relay to trip for the protection element being tested. Configure any of the outputs to be activated only by the protection element being tested. Set the relay as follows: Apply voltage as indicated on the table over the undervoltage setting level and verify that the relay does not trip. Decrease voltage level gradually and verify that the relay trips for the set voltage (with an admissible error of 5%). 6.14.2 27X element Set the relay to trip for the protection element being tested . Configure any of the outputs to be activated only by the protection element being tested. Set the relay as follows Apply voltage as indicated on the table over the undervoltage setting level and verify that the relay does not trip. Decrease voltage level gradually and verify that the relay trips for the set voltage (with an admissible error of 5%). PHASE UV (27P) FunctionENABLED ModePHASE-GROUND Pickup Level50 V CurveDEFINITE TIME Delay2.00 sec Minimum Voltage30 V LogicANY PHASE Supervised by 52DISABLED ElementPhaseCurvePickup LevelDelayApplied VoltageTripping times (s) EXPECTEDAdmissible 27P VIDEFINITE TIME 50 V 255 V NO TRIPNA 45 V 2.000 sec[2.000 – 2.100] GENERAL SETTINGS Auxiliary Voltage VX AUXILIARY UV (27X) FunctionENABLED Pickup Level50 V CurveDEFINITE TIME Delay2.00 sec ElementInputCurvePickup LevelDelayApplied VoltageTripping time (s) EXPECTEDAdmissible 27X VXDEFINITE TIME 50 V 255 V NO TRIPNA 45 V 2.000 sec[2.000 – 2.100]
![](/img/blank.gif)
6-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF 6.15 OVERVOLTAGE ELEMENTS (59P, 59X, 59NH, 59NL, 47) CHAPTER 6: COMMISSIONING 6.15 Overvoltage elements (59P, 59X, 59NH, 59NL, 47) 6.15.1 59P element Set the relay to trip for the protection element being tested. Configure any of the outputs to be activated only by the protection element being tested. Set the relay as follows: Apply voltage as indicated on the table under the overvoltag e setting level and verify that the relay does not trip. Verify that the relay trips for the set voltage (with an admissible error of 5%). 6.15.2 59X element Set the relay as follows: Apply voltage as indicated on the table under the overvoltag e setting level and verify that the relay does not trip. Verify that the relay trips for the set voltage (with an admissible error of 5%). PHSE OV (59P) FunctionENABLED Pickup Level120 V Trip Delay2.00 Reset Delay0.00 LogicANY PHASE ElementPhasePickup Level (volts)Trip Delay(seconds)Applied Voltage (V)Tripping time (s) EXPECTEDAdmissible 59P VII120 2 114 NO TRIPNA 132 2[1.9–2.1 ] 132 2[1.9 – 2.1] GENERAL SETTINGS Auxiliary Voltage VX AUXILIARY OV (59P) FunctionENABLED Pickup Level120 V Trip Delay2.00 Reset Delay0.00 LogicANY PHASE ElementInputPickup Level (volts)Trip Delay(seconds)Applied Voltage (V)Tripping time (s) EXPECTEDAdmissible 59X VX120 2 114 NO TRIPNA 132 2[1.9–2.1] 132 2[1.9 – 2.1]
![](/img/blank.gif)
CHAPTER 6: COMMISSIONING6.15 OVERVOLTAGE ELEMENTS (59P, 59X, 59NH, 59NL, 47) GEK-113000-AFF650 DIGITAL BAY CONTROLLER 6-19 6.15.3 59NH and 59NL elements Set the relay as follows Apply voltage as indicated on the table under the overvoltage setting level and verify that the relay does not trip. Verify that the relay trips for the set voltage (with an admissible error of 5%). This element can also be tested by applying only phase voltages . For this purpose, it is necessary to set Auxiliary Voltage = VX. In this condition, Vn voltage is calculated as a sum of the phase voltages. 6.15.4 47 element - Neg Seq OV Set the relay as follows: Apply voltage as indicated on the table under the overvoltage setting level and verify that the relay does not trip. Verify that the relay trips for the set voltage (with an admissible error of 5%). GENERAL SETTINGS Auxiliary VoltageVN NEUTRAL OV HIGH/LOW (59NH/59NL) FunctionENABLED Pickup Level120 V Trip Delay2.00 Reset Delay0.00 ElementsInputPickup Level (volts)Trip Delay(seconds)Applied Voltage (V)Tripping time (s) EXPECTEDAdmissible 59NH/59NL VX120 2 114 NO TRIPNA 132 2[1.9–2.1 ] 132 2[1.9 – 2.1] NEG SEQ OV (47) FunctionENABLED Pickup Level50 V Trip Delay2.00 Reset Delay 0.00 CHANNELApplied Voltage (V)AngleTripping time (s) EXPECTEDAdmissible VI 650ºNO TRIPNA VII 65120º VIII 65240º VI 550º2[1.9–2.1] VII 55240º VIII 55120º VI 450ºNO TRIP NA VII 45240º VIII 45120º
![](/img/blank.gif)
6-20F650 DIGITAL BAY CONTROLLER GEK-113000-AF 6.15 OVERVOLTAGE ELEMENTS (59P, 59X, 59NH, 59NL, 47) CHAPTER 6: COMMISSIONING NOTE: All angles mentioned on the tables are delay angles, where a balanced ABC system would be composed by: CHANNELApplied Voltage (V)Angle VI 65 0º VII 65 120º VIII 65 240º
![](/img/blank.gif)
CHAPTER 6: COMMISSIONING6.16 FREQUENCY ELEMENTS (81O/81U) GEK-113000-AF F650 DIGITAL BAY CONTROLLER 6-21 6.16 Frequency elements (81O/81U) Set the relay to trip for the protection element being tested. Configure any of the outputs to be activated only by the protection element being tested. Set the relay as follows: Apply voltage as indicated on the table, modifying frequenc y from the maximum threshold (48 Hz) to the minimum (46 Hz) for 81U, and from the minimum (52 Hz) to the maximum (54 Hz) for 81O, in steps of 10 mHz. Verify that the relay trips at the set frequency in the corresponding element with an error of 3% ó ±50 mHz. Apply a voltage that is lower than the “Minimum Voltage” se tting, with a frequency under (81U) or over (81O) the setting, and verify that the relay does not trip. GENERAL SETTINGS Nominal Frequency50 Hz ELEMENT SETTINGS FREQUENCY (81)81U81O FunctionENABLEDENABLED Pickup Level47.50 Hz52.50 Hz Trip Delay2.00 sec2.00 sec Reset Delay0.00 sec0.00 sec Minimum Voltage30 V30 V ElementsPhasePickup Level (Hz)Trip Delay(seconds)Applied Voltage (V)Frequency ThresholdsTripping Time (s) EXPECTEDAdmissible 81U VII47.5 2 8048 Hz No tripNA 46 Hz 2[1.9 -2.1] 25 46 Hz No tripNA 81 O VII52.5 28052 Hz No tripNA 54 Hz 2[1.9 –2.1] 25 54 Hz No tripNA
![](/img/blank.gif)
6-22F650 DIGITAL BAY CONTROLLER GEK-113000-AF 6.17 RECLOSER (79) CHAPTER 6: COMMISSIONING 6.17 Recloser (79) Set protection element 79 as follows: Set the relay to trip by 50PH, and configure the signals necessary to test the 79 element: Configure one output as AR RECLOSE Configure the AR INITIATE signal with the 50PH trip Configure the AR LEVEL BLOCK signal with a digital input Configure the AR CONDS INPUT with the digital signal desired 6.17.1 Reclosing cycle Connect a latching relay simulating the breaker managed by the F650 unit. Once the relay is set, close the breaker and wait for 5 seconds. After this time, the recloser is re ady to initiate the reclosing cycle. Command a 50PH trip and verify that the breake r opens and the relay recloses in 2.1 seconds. Command a 50PH trip and verify that the breaker opens and the relay recloses in 4.1 seconds. Command a 50PH trip and verify that the breaker opens and the relay recloses in 6.1 seconds. Command a 50PH trip and verify that the breaker opens and the relay recloses in 8.1 seconds. Command a 50PH trip and verify that the breaker opens and the recloser passes to Lockout. Verify the correct operation of programmed outputs Tripping times must be within the following values: RECLOSER FunctionENABLED Max Number Shots 4 Dead T ime 1 2.10 sec Dead T ime 2 4.10 sec Dead T ime 3 6.10 sec Dead T ime 4 8.10 sec Reclaim T ime 3.00 sec Cond. Permission ENABLED Hold T ime 7.00 sec Reset T ime 5.00 sec 50PH Settings FunctionENABLED Input RMS Pickup Level 3 A Trip Delay 0.00 s Reset Delay 0.00 s Reclosing Cycle Nº shot Expected timeAdmissible time 1 2.1 sec [1.8 – 2.3] 2 4.1 sec [3.8 – 4.3] 3 6.1 sec [5.8 – 6.3] 4 8.1 sec [7.8 – 8.3]