    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-11
    SENSITIVE GROUND INSTANTANEOUS OVERCURRENT (50SG)
    Current Input:.............................................................................phasor (without harmonics) or RMS
    Rated Current: ........................................................................... for connection to 1 or 5 A CTs
    Pickup Level:............................................................................... 0.005 to 16.000 A in steps of 0.001 A
    Level Accuracy: ........................................................................ values at nominal frequency:
    ±1.5% of the reading ± 1 mA from 0.005 to 16.000 A
    Overreach: .................................................................................. < 2%
    Trip Delay: ................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ............................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Operate T ime:............................................................................ < 50 ms at 3 x pickup at 50 Hz, typically
    T iming Accuracy: ..................................................................... at 0 ms time delay (no intentional delay): 50 ms
    at non-zero time delay: ±3% of operate time or 50 ms
    (whichever is greater)
    Snapshot Events: ..................................................................... selectable by setting
    ISOLATED GROUND INSTANTANEOUS OVERCURRENT (50IG)
    Current Input:.............................................................................fundamental phasor (without harmonics)
    Voltage Input: ............................................................................ fundamental phasor (without harmonics)
    Current Pickup Level:.............................................................. 0.005 to 0.400 A in steps of 0.001 A
    Voltage Pickup Level: ............................................................. 2 to 70 V in steps of 1 V
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Level Accuracy: ........................................................................ ±1.5% of the reading ± 1 mA from 0.005 to 16.000 A
    Trip Delay: ................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    T ime to Instantaneous: ......................................................... 0.00 to 900.00 s in steps of 0.01 s
    Operate T ime:............................................................................ < 50 ms at 3 x pickup at 50 Hz, typically
    T iming Accuracy: ..................................................................... at 0 ms time delay (no intentional delay): 50 ms
    at non-zero time delay: ±3% of operate time or 50 ms
    (whichever is greater)
    Snapshot Events: ..................................................................... selectable by setting
    NEGATIVE SEQUENCE CURRENT (46)
    Current Input:.............................................................................fundamental phasor (without harmonics)
    Pickup Level:............................................................................... 0.05 to 160.00 A in steps of 0.01 A
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Level Accuracy: ........................................................................ values at nominal frequency:
    ±0.5% of the reading ±10 mA from 0.05 to 10.00 A
    ±1.5% of the reading for higher values
    Curve Shape:.............................................................................. IEEE extremely/very/moderately inverse 
    IEC A/B/C/long-time inverse/short time inverse curve
    IAC extremely/very/moderately inverse
    ANSI extremely/very/normally/moderately inverse
    I
    2t
    Def inite time
    Rectif ier curve
    FlexCurve
    TM A/B/C/D user curve
    Curve Multiplier (T ime Dial): ................................................ 0.00 to 900.00 s in steps of 0.01 s
    Reset Type: ................................................................................. instantaneous or time delayed, according to IEEE
    T iming Accuracy: ..................................................................... Operate at > 1.03 times the pickup ±3% of operate time or 50 ms
    (whichever is greater)
    Saturation Level: ...................................................................... 48 times the pickup level
    Snapshot Events: ..................................................................... selectable by setting 
    						
    							2-12F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    PHASE DIRECTIONAL (67P)
    Directionality: ............................................................................. forward and reverse selectable by setting
    Polarizing:..................................................................................... quadrature voltage:
    ABC seq: Phase A (VBC), Phase B (VCA), Phase C (VAB)
    ACB seq: Phase A (VCB), Phase B (VAC), Phase C (VBA)
    Polarizing Voltage Threshold:.............................................. 0 to 300 Vac in steps of 1 V
    Current Sensitivity Threshold:............................................. 50 mA
    Characteristic Angle:............................................................... -90º to +90º in steps of 1º
    Block Logic: ................................................................................. permission or block selectable by setting
    Angle Accuracy: ........................................................................ ±3º for I > 0.1 A and V > 5 Vac
    Voltage Memory T ime:........................................................... 0.00 to 3.00 s in steps of 0.01 s
    Operate T ime: ............................................................................ < 30 ms, typically
    GROUND DIRECTIONAL (67G)
    Directionality: .............................................................................forward and reverse selectable by setting
    Polarizing:..................................................................................... voltage, current , dual
    Polarizing Voltage:.................................................................... V
    N (measured or calculated, selected by setting)
    Polarizing Current:.................................................................... I
    sg (measured from 5th current transformer)
    Operating Current: ................................................................... I
    g (measured from 4th current transformer)
    Polarizing Voltage Threshold:.............................................. 0 to 300 Vac in steps of 1 V
    Polarizing Current Threshold:.............................................. 0.005 A
    Characteristic Angle:............................................................... -90º to +90º in steps of 1º
    Block Logic: ................................................................................. permission or block selectable by setting
    Angle Accuracy: ........................................................................ ±3º for I > 0.1 A and V > 5 Vac
    Operate T ime: ............................................................................ < 30 ms, typically
    NEUTRAL DIRECTIONAL (67N)
    Directionality: .............................................................................forward and reverse selectable by setting
    Polarizing:..................................................................................... voltage, current , dual
    Polarizing Voltage:.................................................................... V
    N (measured or calculated, selected by setting)
    Polarizing Current:.................................................................... I
    sg (measured from 5th current transformer)
    Operating Current: ................................................................... I
    NPolarizing Voltage Threshold:..............................................0 to 300 Vac in steps of 1 V
    Polarizing Current Threshold:.............................................. 0.005 A
    Characteristic Angle:............................................................... -90º to +90º in steps of 1º
    Block Logic: ................................................................................. permission or block selectable by setting
    Angle Accuracy: ........................................................................ ±3º for I > 0.1 A and V > 5 Vac
    Operate T ime: ............................................................................ < 30 ms, typically
    SENSITIVE GROUND DIRECTIONAL (67SG)
    Directionality: .............................................................................forward and reverse selectable by setting
    Polarizing:..................................................................................... voltage
    Polarizing Voltage:.................................................................... V
    N (measured or calculated, selected by setting)
    Operating Current: ................................................................... I
    sg (measured from 5th current transformer)
    Polarizing Voltage Threshold:.............................................. 0 to 300 Vac in steps of 1 V
    Characteristic Angle:............................................................... -90º to +90º in steps of 1º
    Block Logic: ................................................................................. permission or block selectable by setting
    Angle Accuracy: ........................................................................ ±2º for I > 0.1 A and V > 5 Vac
    Operate T ime: ............................................................................ < 30 ms, typically 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-13
    THERMAL MODEL (49)
    Current Input:.............................................................................fundamental phasor (without harmonics)
    Rated Current: ........................................................................... for connection to 1 or 5 A CTs
    Pickup Level:............................................................................... 0.05 to 160.00 A in steps of 0.01 A
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Level Accuracy: ........................................................................ values at nominal frequency:
    ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A
    ±1.5% of the reading for higher values
    T iming Accuracy: ..................................................................... ±3.5% of operating time or 50 ms (whichever is greater)
    Heating Constant:.................................................................... 3.0 to 600.0 minutes in steps of 0.1 minutes
    Cooling Constant: .................................................................... 1.00 to 6.00 times the heating constant , in steps of 0.01
    Snapshot Events: ..................................................................... selectable by setting
    PHASE OVERVOLTAGE (59P)
    Voltage Input: ............................................................................fundamental phasor (without harmonics) of phase-to-phase voltages
    Pickup Level:............................................................................... 2 to 30 V in steps of 1 V
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Level Accuracy: ........................................................................ ±1% of the reading from 10 to 208 V at nominal frequency
    Trip Delay: ................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ............................................................................... 0.00 to 900.00 s in steps of 0.01 s
    T iming Accuracy: ..................................................................... ±3.5% of operating time or 50 ms (whichever is greater)
    Logic: ............................................................................................. Any/Two/All phases logic, selectable by setting
    Snapshot Events: ..................................................................... selectable by setting
    PHASE UNDERVOLTAGE (27P)
    Voltage Input: ............................................................................fundamental phasor of phase-to-ground or phase-to-phase voltages (selectable by 
    setti
    ng)
    Pickup Level:............................................................................... 3 to 300 V in steps of 1 V
    Dropout Level: ........................................................................... 102% to 103% of the pickup level
    Level Accuracy: ........................................................................ ±1% of the reading from 10 to 208 V at nominal frequency
    Trip Delay: ................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Curve Shapes: ........................................................................... f ixed time or inverse curves
    Reset Type: ................................................................................. instantaneous
    Curve Multiplier (T ime Dial): ................................................ 0.00 to 900.00 s in steps of 0.01 s
    T iming Accuracy: ..................................................................... ±3.5% of operating time or 50 ms (whichever is greater)
    Minimum Voltage Threshold:.............................................. 0 to 300 V in steps of 1 V
    Logic: ............................................................................................. Any/Two/All phases logic, selectable by setting
    Supervised by Breaker:......................................................... selectable by setting
    Snapshot Events: ..................................................................... selectable by setting
    NEUTRAL OVERVOLTAGE (59NH/59NL)
    Voltage Input: ............................................................................fundamental phasor of the neutral voltage
    Pickup Level:............................................................................... 3 to 300 V in steps of 1 V
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Level Accuracy: ........................................................................ ±1% of the reading from 10 to 208 V at nominal frequency
    Trip Delay: ................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ............................................................................... 0.00 to 900.00 s in steps of 0.01 s
    T iming Accuracy: ..................................................................... ±3.5% of operating time or 50 ms (whichever is greater)
    Snapshot Events: ..................................................................... selectable by setting 
    						
    							2-14F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    NEGATIVE SEQUENCE OVERVOLTAGE (47)
    Voltage Input: ............................................................................. fundamental phasor
    Pickup Level: ............................................................................... 3 to 300 V in steps of 1 V
    Dropout Level: ............................................................................ 97% to 98% of the pickup level
    Level Accuracy: ......................................................................... ±1% of the reading from 10 to 208 V
    Trip Delay: .................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ................................................................................ 0.00 to 900.00 s in steps of 0.01 s
    T iming Accuracy: ..................................................................... ±3.5% of operating time or 50 ms (whichever is greater)
    Snapshot Events: ...................................................................... selectable by setting
    AUXILIARY OVERVOLTAGE (59X)
    Voltage Input: .............................................................................fundamental phasor of the auxiliary voltage
    Pickup Level: ............................................................................... 3 to 300 V in steps of 1 V
    Dropout Level: ............................................................................ 97% to 98% of the pickup level
    Level Accuracy: ......................................................................... ±1% of the reading from 10 to 208 V at nominal frequency
    Trip Delay: .................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ................................................................................ 0.00 to 900.00 s in steps of 0.01 s
    T iming Accuracy: ..................................................................... ±3.5% of operating time or 50 ms (whichever is greater)
    Snapshot Events: ...................................................................... selectable by setting
    AUXILIARY UNDERVOLTAGE (27X)
    Voltage Input: .............................................................................fundamental phasor of the auxiliary voltage
    Pickup Level: ............................................................................... 3 to 300 V in steps of 1 V
    Dropout Level: ............................................................................ 102% to 103% of the pickup level
    Level Accuracy: ......................................................................... ±1% of the reading from 10 to 208 V at nominal frequency
    Curve Shapes: ............................................................................ fixed time or inverse curves
    Reset Type: .................................................................................. instantaneous
    Curve Multiplier (T ime Dial): ................................................. 0.00 to 900.00 s in steps of 0.01 s
    T iming Accuracy: ..................................................................... ±3.5% of operating time or 50 ms (whichever is greater)
    Snapshot Events: ...................................................................... selectable by setting
    UNDERFREQUENCY (81U)
    Pickup Level: ...............................................................................20.00 to 65.00 Hz in steps of 0.01 Hz
    Dropout Level: ............................................................................ pickup + 0.03 Hz
    Level Accuracy: ......................................................................... ±0.05 Hz of the reading from 30 to 80 Hz
    Trip Delay: .................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ................................................................................ 0.00 to 900.00 s in steps of 0.01 s
    Minimum Voltage Threshold: .............................................. 10 to 300 V in steps of 1 V
    T ime Delay Accuracy: ............................................................ 0 to 7 cycles
    Operate T ime: ............................................................................ typically 10 cycles at 0.1 Hz/s change
    Snapshot Events: ...................................................................... selectable by setting
    OVERFREQUENCY (81O)
    Pickup Level: ...............................................................................20.00 to 65.00 Hz in steps of 0.01 Hz
    Dropout Level: ............................................................................ pickup - 0.03 Hz
    Level Accuracy: ......................................................................... ±0.05 Hz of the reading from 30.00 to 80.00 Hz
    Trip Delay: .................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ................................................................................ 0.00 to 900.00 s in steps of 0.01 s
    Minimum Voltage Threshold: .............................................. 10 to 300 V in steps of 1 V
    T ime Delay Accuracy: ............................................................ 0 to 7 cycles
    Operate T ime: ............................................................................ typically 10 cycles at 0.1 Hz/s change
    Snapshot Events: ...................................................................... selectable by setting 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-15
    FORWARD POWER (32FP)
    Current , Voltage: ......................................................................fundamental phasor (primary values)
    Number of Stages:................................................................... 2
    Pickup Level:............................................................................... 0.00 to 10000.00 MW in steps of 0.01 MW
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Level Accuracy for Primary Magnitudes: ..................... ±3% of complete range
    Trip Delay (Two Stages): ........................................................ 0.00 to 900.00 s in steps of 0.01 s
    T iming Accuracy: ..................................................................... ±3.5% of operate time or 50 ms (whichever is greater)
    Block T ime After Close: ......................................................... 0.00 to 900.00 s in steps of 0.01 s
    Snapshot Events: ..................................................................... selectable by setting
    DIRECTIONAL POWER (32)
    Current , Voltage: ......................................................................fundamental phasor (primary values)
    Number of Stages:................................................................... 2
    Pickup Level:............................................................................... -10000.00 to 10000.00 MW (primary values) in steps of 0.01 MW
    Characteristic Angle (Two Stages): .................................. 0.00º to 359.99º in steps of 0.01º
    Accuracy for Primary Magnitudes: ................................. ±3% of complete range
    Trip Delay (Two Stages): ........................................................ 0.00 to 900.00 s in steps of 0.01 s
    T iming Accuracy: ..................................................................... ±3.5% of operate time or 50 ms (whichever is greater)
    Block T ime After Close: ......................................................... 0.00 to 900.00 s in steps of 0.01 s
    Snapshot Events: ..................................................................... selectable by setting
    Operate T ime:............................................................................ < 45 ms at 50 Hz, typically
    WATTMETRIC ZERO-SEQUENCE DIRECTIONAL (32N)
    Measured Power: .....................................................................zero sequence
    Number of Elements: ............................................................. 6 (3 high level, 3 low level)
    Voltage Pickup Level V
    N: ....................................................... 2.00 to 70.00 V in steps of 0.01 V
    voltage calculated from phases if auxiliary voltage is set to V
    xvoltage measured from the 4th voltage transformer if auxiliary voltage is set to VNLevel Accuracy for Voltage: ................................................ ±1% of reading from 10 to 208
    Current Selection: .................................................................... I
    N (calculated from phases)
    I
    G (measured from the 4th current transformer)
    OC Pickup Level: ....................................................................... 0.005 to 0.400 A in steps of 0.001
    Level Accuracy for Current: ................................................ ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A
    ±1.5% of the reading for higher values
    OC Pickup Delay:...................................................................... 0.00 to 600.00 s in steps of 0.01 s
    Power Pickup Level: ................................................................ 0.01 to 4.50 W in steps of 0.01 W
    Characteristic Angle (MTA):.................................................. 0º to 360º in steps of 1º
    Power Pickup Delay:............................................................... 0.00 to 600.00 s in steps of 0.01 s
    Level Accuracy for Power:................................................... ±2.5% of the reading at -0.8 ≤ PF  ≤ -1 and 0.8 < PF  ≤ 1
    Curve Shapes: ........................................................................... Inverse Curve
    Def inite T ime
    FlexCurve
    TM A/B/C/D user curves
    Curve Multiplier (T ime Dial): ................................................ 0.02 to 2.00 s in steps of 0.01 s
    Tripping T ime Accuracy: ...................................................... ±3.5% of operate time or 50 ms whichever is greater
    Snapshot Events: ..................................................................... selectable by setting
    Operate T ime:............................................................................ < 45 ms at 50 Hz, typically 
    						
    							2-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    2.5.2  Control
    AUTORECLOSE (79)
    Schemes: ...................................................................................... three-pole tripping schemes
    Number of Shots:...................................................................... up to 4 reclose attempts before lockout
    Dead T ime: .................................................................................. independent dead time setting before each shot
    adjustable between 0.00 and 900.00 s in steps of 0.01 s.
    Reclaim T ime:............................................................................. 0.00 and 900.00 s in steps of 0.01 s
    Condition Permisison:............................................................. selectable by setting
    Hold T ime:.................................................................................... 0.00 and 900.00 s in steps of 0.01 s
    Reset T ime: .................................................................................. 0.00 and 900.00 s in steps of 0.01 s
    Snapshot Events: ...................................................................... selectable by setting
    Protection settings can be modified after each shot through PLC programming (block  signals are available after each shot).
    SYNCHROCHECK (25)
    Dead/live Level for Line and Bus:......................................0.00 to 300.00 in steps of 0.01 V
    Maximum Voltage Difference: ............................................ 2.00 to 300.00 V in steps of 0.01 V
    Maximum Angle Difference: ................................................ 2.0º to 80.0º in steps of 0.1º
    Maximum Frequency Slip:.................................................... 10 to 5000 mHz in steps of 10 mHz
    Synchronism T ime:.................................................................. 0.01 to 1.00 s in steps of 0.01 s
    Angle Accuracy: ........................................................................ 3º
    Dead Source Function:........................................................... None
    (DL-DB) Dead Line - Dead Bus
    (LL-DB) Live Line-Dead Bus
    (DL-LB) Dead Line – Live Bus
    Snapshot Events: ...................................................................... selectable by setting
    FUSE FAILURE
    Algorithm based on positive sequence of voltage and current
    Activation by V
    2/V1 ratio
    BREAKER FAILURE (50BF)
    Current Input: .............................................................................phasor (without harmonics)
    Rated Current:............................................................................ for connection to 1 or 5 A CTs
    Pickup Level for Supervision: .............................................. 0.05 to 160.00 A in steps of 0.01 A
    Pickup Level for High Level: ................................................. 0.05 to 160.00 A in steps of 0.01 A
    Pickup Level for Low Level: .................................................. 0.05 to 160.00 A in steps of 0.01 A
    Pickup Level for Internal Arcing: ........................................ 0.05 to 160.00 A in steps of 0.01 A
    Dropout Level: ............................................................................ 97% to 98% of the pickup level
    Level Accuracy: ......................................................................... values at nominal frequency:
    ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A
    ±1.5% of the reading for higher values
    T iming Accuracy: ..................................................................... ±3.5% of operate time or 50 ms (whichever is greater)
    Snapshot Events: ...................................................................... selectable by setting 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-17
    CT SUPERVISION FAILURE (60CTS)
    Inputs:............................................................................................Neutral Current INNeutral Voltage VN (from three-phase VTs)
    Ground Current I
    gSensitive Ground Current IsgT ime Delay:................................................................................. 0.00 to 600.00 s in steps of 0.01 s
    3IO Level Accuracy: ................................................................ ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A (for ground)
    ±1.5% of the reading ± 1 mA from 0.005 to 5.000 A (for sensitive ground
    3VO Level Accuracy:............................................................... ±1% of reading from 10 to 208 V
    Ground Current Accuracy: .................................................. ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A 
    Sensitive Ground Current Accuracy: .............................. ±1.5% of the reading ± 1 mA from 0.005 to 5.000 A
    Operate T ime:............................................................................ < 20 ms at 60 Hz
    < 25 ms at 50 Hz
    Snapshot Events: ..................................................................... selectable by setting
    SECOND HARMONIC INHIBIT
    Operating Parameter: ...........................................................current 2nd harmonic per phase or average
    Pickup Level:............................................................................... 0.1 to 40.0% in steps of 0.1%
    Dropout Level: ........................................................................... 98% of the pickup level
    Level Accuracy: ........................................................................ 2% or 10 mA
    Minimum Current:.................................................................... 0.05 to 15.00 A in steps of 0.01 A
    T ime Delay:................................................................................. 0.00 to 600.00 s in steps of 0.01 s
    T ime Delay Accuracy: ........................................................... ±3% of expected time or 1.5 cycles (whichever is greater)
    T ime Accuracy:......................................................................... 3% or 1.5 cycles
    Snapshot Events: ..................................................................... selectable by setting
    BROKEN CONDUCTOR (I2/I1)
    Pickup Level:...............................................................................20.0-100.0% (I2/I1 ratio) in steps of 0.1%
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Trip Delay: ................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    T iming Accuracy: ..................................................................... ±3.5% of operate time or 50 ms (whichever is greater)
    Snapshot Events: ..................................................................... selectable by setting
    Operation Threshold: ............................................................. 0.000 to 1.000 A in steps of 0.001 A
    Current Inhibition Level:........................................................ selectable by setting from 0.000 to 1.000 A in steps of 0.001 A
    LOCKED ROTOR (48)
    Current Input:.............................................................................phasor (without harmonics) or RMS
    Rated Current: ........................................................................... for connection to 1 or 5 A CTs
    Full Load Current:..................................................................... 0.10 to 10.00 kA in steps of 0.01 kA
    Pickup Level:............................................................................... .1.01 to 109.00 in steps of 0.01 x FLC
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Level Accuracy for Primary Magnitudes: ..................... ±3% complete range
    Trip Delay: ................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ............................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Operate T ime:............................................................................ 20 ms at 3 x pickup at 50 Hz, typically
    T iming Accuracy: ..................................................................... ±3% of operate time or 50 ms (whichever is greater)
    Snapshot Events: ..................................................................... selectable by setting
    PULSE COUNTERS
    Number of Pulse Counters Available:.............................up to 8
    Multiplier Factor: ...................................................................... 0.000 to 65000.000 in steps of 0.001
    Overload Factor: ...................................................................... 0 to 10000000 in steps of 1
    Board Origin: .............................................................................. all available input/output boards in the device. See order code (F, G, H, J)
    Input Origin: ................................................................................ up to 32 (depending on board selection type) 
    						
    							2-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    ANALOG COMPARATORS
    Analog Input: .............................................................................. any analog value in the device
    Analog Maximum Threshold Value: ................................. -100000.000 to 100000.000 in steps of 0.001
    Analog Minimum Threshold Value: .................................. -100000.000 to 100000.000 in steps of 0.001
    Analog Delay: ............................................................................. 0.00 to 900.00 in steps of 0.01
    Analog Hysteresis: ................................................................... 0.0 to 50.0 in steps of 0.1
    Analog Direction (for activation inside or outside the  dea
     dband: ..............................................................................
    IN or OUT
    FREQUENCY RATE OF CHANGE 
    df/dt Trend: .................................................................................. increasing, decreasing, bidirectional
    df/dt Pickup Level: .................................................................... 0.10 to 10.00 Hz/s in steps of 0.01 Hz/s
    df/dt Level Accuracy:.............................................................. 80 mHz/s or 3.5% (whichever is greater)
    Overvoltage Supv. .................................................................... 0.00 to 110.00% in steps of 0.01%
    95% Settling T ime for df/dt: ................................................ < 24 cycles
    Operate T ime: ............................................................................ at 2 x pickup: 12 cycles
    at 3 x pickup: 8 cycles
    at 5 x pickup: 6 cycles
    Frequency Rate Min. ............................................................... 20.00 to 80.00 Hz in steps of 0.01 Hz
    Frequency Rate Max............................................................... 20.00 to 80.00 Hz in steps of 0.01 Hz
    Frequency Rate Delay: .......................................................... 0.00 to 60.00 s in steps of 0.01 s
    Snapshot Events: ...................................................................... selectable by setting
    LOAD ENCROACHMENT
    Responds to: ...............................................................................positive sequence quantities
    Minimum Voltage: .................................................................... 0.00 to 300.00 V in steps of 0.01 V
    Reach (sec.
    Ω): ........................................................................... 0.02 to 250.00 Ω in steps of 0.01 Ω
    Impedance Accuracy: ............................................................ ±3%
    Angle: ............................................................................................. 5 to 50º in steps of 1º
    Angle Accuracy: ........................................................................ ±3%
    Pickup Delay: .............................................................................. 0.000 to 65.535 s in steps of 0.001
    Reset Delay: ................................................................................ 0.000 to 65.535 s in steps of 0.001
    T ime Accuracy: ......................................................................... ±3.5% or ±60 ms, whichever is greater
    Operate T ime: ............................................................................ < 60 ms at 50 Hz, typically
    Snapshot Events: ...................................................................... selectable by setting
    BREAKER SETTINGS
    Number of Switchgear: .........................................................1 to 16 (selection of switchgear for breaker control)
    Maximum KI2t: ........................................................................... 0.00 to 9999.99 (kA)2s in steps of 0.01 (kA)2s
    KI2t Integration T ime: ............................................................. 0.03 to 0.25 s in steps of 0.01
    Maximum Openings: ............................................................... 0 to 9999 in steps of 1
    Maximum Openings in One Hour: .................................... 1 to 60 in steps of 1
    Snapshot Events: ...................................................................... selectable by setting
    BREAKER MAINTENANCE
    KI2t Breaker Counters for Phases A, B, C:......................0.00 to 9999.99 (kA)2s in steps of 0.01 (kA)2s
    Breaker Opening Counters: ................................................. 0 to 9999 in steps of 1
    Breaker Closing Counters: .................................................... 0 to 9999 in steps of 1
    SWITCHGEAR
    Switchgear: .................................................................................1 to 16 (configurable in Rela y Conf iguration)
    Snapshpt Events: ...................................................................... selectable by setting (for each switchgear, in Sy
     stem Setup)
    MAXIMUM NUMBER OF STARTS
    Metering Algorithm:................................................................. fundamental
    Tripping T ime Accuracy: ....................................................... ±250 ms or 5% (whichever is greater)
    Full Load Amps: ......................................................................... 0.5 to 10.0 A in steps of 0.1 A
    Breaker Supervision: ............................................................... selectable by setting
    Min. Stop T ime: .......................................................................... 0.0 to 900.0 s in steps of 0.1 s 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-19
    Number of Starts:.....................................................................0 to 10 in steps of 1
    T ime to Restart: ........................................................................ 0 to 100 minutes in steps of 1 minute
    Reset Counter:........................................................................... selectable by setting
    Snapshot Events: ..................................................................... selectable by setting
    Operate T ime:............................................................................ < 45 ms at 50 Hz, typically
    DIGITAL COUNTERS
    Function: ......................................................................................Disabled, Enabled
    Name: ............................................................................................ any 12 alphanumeric characters
    Preset: ........................................................................................... -2147483648, 0, +2147483647
    Compare: ..................................................................................... -2147483648, 0, +2147483647
    COLD LOAD PICKUP
    Cold Outage T ime:...................................................................1 to 1000 minutes in steps of 1 minute
    Cold Blocking T ime: ................................................................ 1 to 1000 s in steps of 1 s
    2.5.3  Monitoring
    OSCILLOGRAPHY
    Maximum Records: .................................................................up to 20 oscillography records
    Sampling Rate:.......................................................................... programmable to 4, 8, 16, 32, or 64 samples per power cycle
    Capacity per record:...............................................................
    (27592 samples)/(number of oscill os x number of samples/cycle)
    Maximum Records: ................................................................. up to 20 oscillography records
    Trigger Position: ........................................................................ 5% to 95% of total length
    Trigger:.......................................................................................... programmable via PLC
    Data:............................................................................................... 5 current channels and 4 voltage channels up to 16 digital channels programmable 
    thr
    
    ough PLC
    Data Storage:............................................................................. non-volatile (flash) memory without battery
    Format: ......................................................................................... International Standard COMTRADE ASCII - IEEE C37.111-1999
    Automatic Overwrite:............................................................. selectable by setting (oscillography records can be concatenated)
    Snapshot Events: ..................................................................... selectable by setting
    FAULT LOCATOR
    Method: ........................................................................................single-ended
    Positive Sequence Module: ................................................. 0.01 to 250.00 Ohm in steps of 0.01 Ohms
    Positive Sequence Angle: ..................................................... 25 to 90º in steps of 1º
    Zero Sequence Module: ........................................................ 0.01 to 750.00 Ω in st
     eps of 0.01 Ω
    Zero Sequence Angle: ............................................................ 25 to 90º in steps of 1º
    Line Length: ................................................................................ 0.0 to 2000.0 in steps of 0.1 miles or km (as per line length setting)
    Accuracy:..................................................................................... 5% (typically)
    Show Fault on HMI: ................................................................. selectable by setting
    Snapshot Events: ..................................................................... selectable by setting
    Maximum Records: ................................................................. up to 10 fault report records
    Data:............................................................................................... Fault date and time, pre-fault currents and voltages, fault currents and voltages, fault 
    type, d
    
    istance to the fault (fault location), line parameters, recloser and breaker status 
    information.
    Data Storage:............................................................................. In non-volatile (flash) memory without battery available through communications In 
    v
    
    olatile (RAM) memory available through HMI (if selectable by setting)
    Format: ......................................................................................... text in ASCII format 
    						
    							2-20F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    SNAPSHOT EVENTS
    Capacity*: .................................................................................... 1023 scrolling events
    T ime-tag: ...................................................................................... 1 ms using an internal clock of 100 μs
    T iming Accuracy: ..................................................................... 1 ms (using IRIG-B synchronization)
    Triggers: ........................................................................................ any element pickup, dropout , or operation
    digital input/output change of state
    virtual inputs and control events
    Data Storage: ............................................................................. non-volatile (flash) memory without battery
    *Note: For firmware 7.20, up to 511 snapshot events are availabl e. For firmware below 7.20, up to 479 snapshot events are available.
    CONTROL EVENTS
    Capacity: ......................................................................................128 events programmable through PLC
    T ime-tag: ...................................................................................... 1 ms plus one PLC cycle using an internal clock of 100  μs. For
      digital inputs, 
    the debounce time of these digital inputs must be added.
    T iming Accuracy: ..................................................................... 1 ms (with IRIG-B synchronization input)
    Trigger: .......................................................................................... Any digital signal programmable through the PLC
    Alarm:............................................................................................. Control events can be displayed as an alarm on the alarms panel. Information is 
    alw
    
    ays available through  Communications for all models and in the HMI for models 
    with a graphical display (M in order code).
    Data Storage: ............................................................................. non-volatile (flash) memory without battery
    Control events are also displayed in the snapshot events recording
    DEMAND
    Channels:...................................................................................... 9
    Parameters:................................................................................. Ia (kA RMS), Ib (kA RMS), Ic (kA RMS), Ig (kA RMS), Isg (kA RMS), I2 (kA), P (MW), Q (MVAr) 
    and S (MV
    
    A)
    Current and Power Method: ................................................ Thermal Exponential, Block Interval, Rolling Demand
    Measurements: .......................................................................... Each channel shows the present and maximum measured value, with date and time 
    f
    
    or the maximum recorded value.
    Samples: ....................................................................................... 5, 10, 15, 20, 30, 60 minutes
    Accuracy: ..................................................................................... ±2%
    Trigger Input: .............................................................................. selectable by setting (operation mode selection for the block interval calculation 
    method
    
    )
    Snapshot Events: ...................................................................... selectable by setting
    DATA LOGGER
    Number of Channels:..............................................................1 to 16
    Parameters:................................................................................. any available analog actual value
    Samples: ....................................................................................... 1 second, 1, 5, 10, 15, 20, 30, 60 minutes
    Storage Capacity:..................................................................... f ixed, 32768 measurements 
    						