Home > GE > Controller > GE F650 Manual

GE F650 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual GE F650 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 45 GE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-1
    F650 Digital Bay Controller
    Chapter 2:  Product Description
    GE
    Grid Solutions
    PRODUCT DESCRIPTION
    2.1  F650 Overview
    F650 is a protection, control, monitoring, metering and registering unit, suitable for many different applications, such as 
    main protection for distribution feeders and transmission lines, as well as backup protection for transformers, busbars, 
    capacitor banks, etc. 
    Overvoltage and undervoltage protection, overfrequency an d underfrequency protection, breaker failure protection, 
    directional current supervision fault diagnostics and programmable logic functions are provided. 
    This relay also provides phase, neutral, ground and sensitive ground, instantaneous and time overcurrent protection. The 
    time overcurrent function provides mult iple curve shapes or FlexCurves™ for optimum co-ordination. Automatic reclosing, 
    synchrocheck, and line fault locator features are also provided.
    Voltage, current, power, and energy me tering is built into the relay as a standard  feature. Current parameters are 
    available as true RMS magnitude, or as RMS magnitude of undamental frequency and angle (phasor).
    Diagnostic features include a sequence of records. The intern al clock used for time-tagging can be synchronized with an 
    IRIG-B signal or via SNTP, DNP or Modbus protocol over the Ethernet port. From firmware version 7.00 and above, IEEE 
    1588 time protocol is also available. Precise time stamping a llows the sequence of events to be determined throughout the 
    system. Oscillography data capture may be set to record the me asured parameters before and after the event for viewing 
    on a personal computer (PC). These tools significantly reduce troubleshooting time and simplify report generation in the 
    event of a system fault.
    A faceplate RS232 or USB port may be used to connect to a PC for programming settings and monitoring actual values.
    A variety of communications modules are available. Two re ar RS485 ports allow independent access by operating and 
    engineering personnel. All serial ports use the Modbus® RTU protocol. Optional communications modules include a 
    100BaseFX Ethernet interface which can be used to provide fast, reliable communications in noisy environments. 
    						
    							2-2F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.1 F650 OVERVIEW CHAPTER 2:  PRODUCT DESCRIPTION
    Another option provides two 100BaseFX fiber optic ports for redundancy. The Ethernet port supports IEC 61850, Modbus®/
    TCP, DNP 3.0 and TFTP protocols, and allows access to the relay via any standard web browser. The IEC 60870-5-104 
    protocol is supported on the Ethernet port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) and 
    High-availability Seamless Redundancy (HSR) of IEC 62439-3 (cla use 4 (PRP) and clause 5 (HSR)) for firmware version 7.00 
    and so on.
    Rear port COM1 can be set to support IEC60870-5-103 protocol
    The F650 IEDs use flash memory technology which allows field upgrading as new features are added:
    Figure 2-1:  FUNCTIONAL BLOCK DIAGRAM 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.2 ANSI DEVICE NUMBERS AND FUNCTIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-3
    2.2  ANSI device numbers and functions
    Main features available in the relay are gathered in tables below
    ** These functions are available for firmware version 7.50 or above
    DEVICE NUMBERPROTECTION & CONTROL FUNCTIONS
    25 Synchronism Check
    27/27X Bus/Line Undervoltage
    32 Sensitive Directional Power
    32FP Forward Power
    32N Wattmetric Zero-Sequence Directional
    46 Negative Sequence T ime Overcurrent
    47 Negative Sequence Voltage
    48 Locked Rotor
    49 Thermal Image - overload protection
    50 BF Breaker Failure
    50PH/PL Phase Instantaneous Overcurrent (High/Low)
    50N Neutral Instantaneous Overcurrent
    50G Ground Instantaneous Overcurrent
    50SG Ground Instantaneous Overcurrent for sensitive ground systems (measured from 5
    th current 
    transformer input)
    50IG Isolated Ground Instantaneous Overcurrent (measured from 5
    th current transformer input)
    51N Neutral T ime Overcurrent
    51G Ground T ime Overcurrent
    51SG Sensitive Ground T ime Overcurrent
    51PH/V Voltage Restraint Phase T ime Overcurrent
    51PL/V Voltage Restraint Phase T ime Overcurrent
    59/59X Bus/Line Overvoltage
    59NH/NL Neutral Overvoltage - High/Low
    67P Phase Directional Overcurrent
    67N Neutral Directional Overcurrent
    67SG Sensitive Ground Directional Overcurrent
    79 Autoreclose (Four shot recloser)
    81 U/O Under/Over Frequency Broken Conductor Detection
    N/A Load Encroachment
    N/A Broken Conductor
    81df/dt Frequency Rate of Change
    VTFF VT Fuse Failure Detection
    60CTS Failure Current Transformer Failure **
    2nd Harmonic 
    Inhibit Second Harminic Inhibit ** 
    						
    							2-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.3 OTHER DEVICE FUNCTIONS CHAPTER 2:  PRODUCT DESCRIPTION
    2.3  Other device functions
    *This functionality is availabl e from firmware version 7.00
    ** Maximum number of events can vary depend on fi rmware version. See details in section 2.5.3.3
    INPUTS/OUTPUTSMETERINGCOMMUNICATIONS
    9 Analog Inputs:
    5 current inputs (3 for phases, 1 for ground, 1 
    for sensitiv
     e ground),
    4 voltage inputs (3 for phases, 1 for busbar or 
    auxil
     iary voltage)  Metering Current for phases, ground and 
    s
    
    ensitive ground inputs Front RS232  port , USB port in HMI 
    opti
    on E, Two rear RS485/f ibre optic 
    ports, 10/100 TX and 100 FX Mbps 
    Ethernet port
    Digital Programmable Contact Inputs (up to 
    64) Voltages phase to phase and phase to 
    gr
    
    ound ModBus Communications RTU and 
    ov
    er TCP/IP
    Digital Programmable Contact Outputs (up to 
    16) Real, Reactive and Apparent Power and 
    Po
    
    wer Factor DNP Multimaster (3.0 Level 2)
    32 Latched Virtual Inputs
    32 Self-Reset Virtual Inputs Three Phase Energy
    IEC 870-5-104
    Virtual Outputs (up to 512) FrequencyModBus User Map
    Tripping and closing circuit supervision Sequence components of currents and 
    v
    
    oltages IEC 61850 protocol
    Remote Inputs/Outputs (GSSE and GOOSE 
    messag
     es) Pulse Counters
    IEC 870-5-103 protocol
    Analog Inputs (dCmA) Analog Comparators
    *Digital Counters
    USER INTERFACERECORDSOTHERS
    Alphanumerical display (4x20) Data Logger
    Breaking Arcing Current (I
    2t)
    Graphic display (16 x 40) DemandBreaker Control
    User Programmable LEDs (15) Event Recorder (up to 128 conf igurable 
    ev
    
    ents) IRIG-B synchronization/SNTP/
    IEEE 1588
    User Programmable Keys (up to 5) Fault Locator and Fault report     (up to 10 
    re
    
    cords) Logic Equations (PLC Editor)
    Easy menu management Oscillography (up to 20 records)Operations (up to 24)
    Conf igurable One-Line Diagram (Graphic 
    mod
     el only) Snapshot Events (up to 1023)**
    Web Server Application
    Phasor Diagram (available in EnerVista 650 
    Setup) 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.4 ORDER CODES
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-5
    2.4  Order codes
    F650 units are supplied as ½ 19” rack, 6 units high, containing the following modules: power supply, CPU, I/O modules, 
    communication modules. The required information to completely define an F650 model is shown on Table 2–1:
    Table 2-1: Order codes 
    F650---F-G-----DESCRIPTION
    B Basic Display (See Note 2)
    M Graphic Display  with Standard Symbols  (See Note 2)
    N Graphic Display with IEC symbols  (See Note 2)
    REAR SERIAL COMMUNICATIONS BOARD 1
    F None
    A Redundant RS485 
    P Redundant plastic f iber optic 
    G Redundant glass f iber optic
    X Redundant RS485 + f iber remote CAN bus I/O
    Y Redundant plastic f iber optic + f iber remote CAN bus I/O
    Z Redundant glass f iber optic + f iber remote CAN bus I/O
    C Cable Remote CAN bus I/O
    M RS485 + cable Remote CAN bus I/O
    REAR ETHERNET COMMUNICATIONS BOARD 2 
    B 10/100 Base TX
    C 10/100 Base TX + 100 Base FX
    D 10/100 Base TX + Redundant 100 Base FX
    E Redundant 10/100 Base TX
    G 1588, 10/100 Base TX* + 100 Base TX (See Note 3)
    H 1588, 10/100 Base TX* + 100 Base FX (See Note 3)
    J PRP, 1588, 10/100 Base TX* + Redundant 100 Base FX (See Note 4)
    K PRP, HSR, RSTP, 1588, 10/100 Base TX* + Redundant 100 Base FX 
    (See not
    
    e4)
    L PRP, 1588, 10/100 Base TX*+ Redundant 100 Base TX (See Note 4)
    M PRP, HSR, RSTP, 1588, 10/100 Base TX*+ Redundant 100 Base TX 
    (See Not
    
    e 4)
    I/O BOARD IN SLOT F
    1 16 Digital Inputs + 8 Outputs
    2 8 Digital Inputs + 8 Outputs + 2 trip/close circuit supervision circuits
    4 32 Digital Inputs
    5 16 Digital Inputs + 8 Analog Inputs
    I/O BOARD IN SLOT G
    0 None
    1 16 Digital Inputs + 8 Outputs
    4 32 Digital Inputs (see Note 1)
    5 16 Digital Inputs + 8 Analog Inputs (See Note 1)
    AUXILIARY VOLTAGE
    LO 24-48 Vdc (range 19.2 – 57.6)
    HI 110-250 Vdc (range 88 – 300). 
    120-230 Vac (range 96 – 250)
    LOR Redundant LO 
    HIR Redundant HI 
    LANGUAGE
    - English/English
    C Chinese/English (See Note 2and Note 7) 
    						
    							2-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.4 ORDER CODES CHAPTER 2:  PRODUCT DESCRIPTION
    SPECIAL MODELS MOD001 (Abbreviation +M1): have 6A output contacts instead of 16A.
    Notes:
    (*)   For firmware version 7.00 or above, Port
      E is intended for maintenance purposes.
    (1)   The digit selected for option G must be equal or higher than the d
     igit selected for option F for models including boards 4 and 5 
    only.
           F1G5 is a valid selection and F5G1 is an invalid selection. 
    (2)    Display options with language selection:
    Graphic display: available for English, Fren ch, Spanish and Chinese languages. For Chinese and Russian only IEC symbols option is available (N in order code).
    Basic display: available for all languages
    (3)    Advance functionalities Level I:
    G, H: IEEE1588 Precision Time Protocol (PTP), 61850 Edition 2.0. Digi tal counters. Max numbers of starts and Cold Load Pick-up 
    functionalities.
    (4)    Advance functionalities Level II:
    J, L: Parallel Redundancy Port (PRP,) IEEE1588 Pr ecision Time Protocol (PTP), 61850 Edition 2.0. Digital counters, DFT, 16 Switchgear  mapped in IEC61850, 16 nodes CILO, mapping of BlkOpn and BlkCls leafs of XSWI nodes, Max numbers of starts and Cold Load Pick-
    up functionalities.
    K, M: High-Availability Seamless Redundancy (HSR), Rapid Spanning Tree Protocol (RSTP), Parallel Redundancy Po rt (PRP,) IEEE1588 
    Precision Time Protocol (PTC), 61850 Edition 2.0. Digital counters, DFT, 16 Switchgear mapped in IEC61850, 16 nodes CILO, mappi ng of 
    BlkOpn and BlkCls leafs of XSWI nodes, Max numbers of starts and Cold Load Pick-up functionalities.
    (5)    For special models requested, relay order code shall be codified as a standard model (Table 2-1) following by Abbreviation + MX where X 
    indicates the number of special model selected.
    (6)    For non-last released firmware version models requested, relay order code shall be codified as standard model (Table 2-1),    following 
    by Abbreviation +VXXXXXBYYYYY where XXXXX is the firmware version requested and YYYYY is the corresponding bootcode version.
    (7)    Chinese Language: This language is not supported  for Rear Ethernet Communication Board options: G, H, J,K,L or M
    (8)    Display option with RS232 is not available for F650 Mode ls with Rear Ethernet Communication Board 2 options from G to M or with 
    Environmental Protection option M
    (9)    Marine Range option M in the Environmental Protection se ction is only available with REAR ETHERNET COMMUNICATIONS BOARD  2 
    options G,H,J,K,L or M
    (10)   For F650 whose order code has Communication Option 6, Rear Ethernet Communication Board 2 and that contains firmware v ersion 
    7.52, IEC 61850 Edition 1.0 is also available in relays with this option selected. Relay will wo rk with IEC 61850 Edition 1.0 or Edition 2.0 
    depend on which ICD have been sent to the device. See section
    FFrench/English
    P Russian/English (See Note 2)
    S Spanish/English
    T Turkish/English
    COMMUNICATION PROTOCOL
    - Modbus® RTU, TCP/IP, DNP 3.0 Level 2, IEC 60870-5-104
    3 IEC 60870-5-103, Modbus ® RTU,TCP/IP
    6 IEC 61850 (See Note 10), Modbus
    ® RTU and TCP/IP,DNP 3.0 Level 2, 
    IEC 60870-5-104
    ENVIRONMENTAL PROTECTION
    - Without Harsh (Chemical) Environment Conformal Coating
    H Harsh (Chemical) Environment Conformal Coating
    M Marine range: Lloyd’s Register (See Note 9)
    ENHANCED DISPLAY 
    - Display with RS232 (See Note 8)
    E Enhanced Display with USB 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.4 ORDER CODES
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-7
    2.4.1  CIO Modules
    For applications requiring a high number of inputs and outputs, F650 units can be connected to a CIO module
    (Remote CAN bus I/O module) for using up to 2 additional boards.
    F650 units allow monitoring and configuring these I/O boards as  if they were internal boards, located on slots F and G. In 
    this case, slots are labeled as H and J.
    The required information to completely define a CIO Module is shown on Table 2–2:.
    Table 2-2: Order code for CIO module
    (1) The digit selected for option J must be equal or higher than  the digit selected for option H for models including boards 4 and 5.
           CIOH1J5**: is a valid selection
           CIOH5J1**: is an invalid selection
    CIOH-J--DESCRIPTION
    I/O BOARD IN SLOT H
    1 16 Digital inputs + 8 outputs
    2 8 Digital Inputs + 8 Outputs + 2 trip/close circuit supervision circuits
    4 32 Digital Inputs
    5 16 Digital Inputs + 8 Analog Inputs
    I/O BOARD IN SLOT J
    0 None
    1 16 Digital inputs + 8 outputs
    4 32 Digital Inputs (See Note 1)
    5 16 Digital Inputs + 8 Analog Inputs (See Note 1)
    AUXILIARY VOLTAGE
    LO 24-48 Vdc (range 19.2 – 57.6)
    HI 110-250 Vdc (range 88 – 300)
    120-230 Vac (range 96 – 250)
    ENVIRONMENTAL PROTECTION
    H Harsh (Chemical) Environment Conformal Coating 
    						
    							2-8F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    2.5  Technical specif ications
      TECHNICAL SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
    2.5.1  Protection
    Phase and Ground protection functions use currents measured  through CT inputs for performing internal calculations, 
    while the Neutral protection functions use the current calculated from three phase currents.
    The sensitive ground protection functions are usually used for applications where the neutral is completely isolated. These 
    functions use current measured though the sensitive ground current input. This CT has a sensitivity 10 time higher than 
    standard CT inputs (Connected to 1A and 5A CT) and its current withstand is lower.
    PHASE TIME OVERCURRENT (51PH/51PL)
    Current Input: .............................................................................phasor (without harmonics) or RMS
    Rated Current:............................................................................ for connection to 1 or 5 A CTs
    Pickup Level: ............................................................................... 0.05 to 160.00 A in steps of 0.01 A
    Dropout Level: ............................................................................ 97% to 98% of the pickup level
    Level Accuracy: ......................................................................... values at nominal frequency:
    ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A
    ±1.5% of the reading for higher values
    Curve Shape: .............................................................................. IEEE extremely/very/moderately inverse 
    IEC A/B/C/long-time inverse/short time inverse curve
    IAC extremely/very/moderately inverse
    ANSI extremely/very/normally/moderately inverse
    I
    2t
    Def inite time
    Rectif ier curve
    FlexCurve
    TM A/B/C/D user curve
    Curve Multiplier (T ime Dial): ................................................. 0.00 to 900.00 s in steps of 0.01 s
    Reset Type: .................................................................................. instantaneous or time delayed, according to IEEE
    T iming Accuracy: ..................................................................... Operate at > 1.03 times the pickup ±3% of operate time or 50 ms
    (whichever is greater)
    Voltage Restraint: ..................................................................... selectable by setting
    Saturation Level: ....................................................................... 48 times the pickup level
    Snapshot Events: ...................................................................... selectable by setting 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-9
    GROUND TIME OVERCURRENT (51G)
    Current Input:.............................................................................phasor (without harmonics) or RMS
    Rated Current: ........................................................................... for connection to 1 or 5 A CTs
    Pickup Level:............................................................................... 0.05 to 160.00 A in steps of 0.01 A
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Level Accuracy: ........................................................................ values at nominal frequency:
    ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A
    ±1.5% of the reading for higher values
    Curve Shape:.............................................................................. IEEE extremely/very/moderately inverse 
    IEC A/B/C/long-time inverse/short time inverse curve
    IAC extremely/very/moderately inverse
    ANSI extremely/very/normally/moderately inverse
    I
    2t
    Def inite time
    Rectif ier curve
    FlexCurve
    TM A/B/C/D user curve
    Curve Multiplier (T ime Dial): ................................................ 0.00 to 900.00 s in steps of 0.01 s
    Reset Type: ................................................................................. instantaneous or time delayed, according to IEEE
    T iming Accuracy: ..................................................................... Operate at > 1.03 times the pickup ±3% of operate time or 50 ms
    (whichever is greater)
    Saturation Level: ...................................................................... 48 times the pickup level
    Snapshot Events: ..................................................................... selectable by setting
    NEUTRAL TIME OVERCURRENT (51N)
    Current Input:.............................................................................fundamental phasor (without harmonics) or RMS
    Pickup Level:............................................................................... 0.05 to 160.00 A in steps of 0.01 A
    Dropout Level: ........................................................................... 97% to 98% of the pickup level
    Level Accuracy: ........................................................................ values at nominal frequency:
    ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A
    ±1.5% of the reading for higher values
    Curve Shape:.............................................................................. IEEE extremely/very/moderately inverse 
    IEC A/B/C/long-time inverse/short time inverse curve
    IAC extremely/very/moderately inverse
    ANSI extremely/very/normally/moderately inverse
    I
    2t
    Def inite time
    Rectif ier curve
    FlexCurve
    TM A/B/C/D user curve
    Curve Multiplier (T ime Dial): ................................................ 0.00 to 900.00 s in steps of 0.01 s
    Reset Type: ................................................................................. instantaneous or time delayed, according to IEEE
    T iming Accuracy: ..................................................................... Operate at > 1.03 times the pickup ±3% of operate time or 50 ms
    (whichever is greater)
    Saturation Level: ...................................................................... 48 times the pickup level
    Snapshot Events: ..................................................................... selectable by setting 
    						
    							2-10F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    SENSITIVE GROUND TIME OVERCURRENT (51SG)
    Current Input: ............................................................................. phasor (without harmonics) or RMS
    Rated Current:............................................................................ for connection to 1 or 5 A CTs
    Pickup Level: ............................................................................... 0.005 to 16.000 A in steps of 0.001 A
    Dropout Level: ............................................................................ 97% to 98% of the pickup level
    Level Accuracy: ......................................................................... values at nominal frequency:
    ±1.5% of the reading ± 1 mA from 0.005 to 16.000 A
    Curve Shape: .............................................................................. IEEE extremely/very/moderately inverse 
    IEC A/B/C/long-time inverse/short time inverse curve
    IAC extremely/very/moderately inverse
    ANSI extremely/very/normally/moderately inverse
    I
    2t
    Def inite time
    Rectif ier curve
    FlexCurve
    TM A/B/C/D user curve
    Curve Multiplier (T ime Dial): ................................................. 0.00 to 900.00 s in steps of 0.01 s
    Reset Type: .................................................................................. instantaneous or time delayed, according to IEEE
    T iming Accuracy: ..................................................................... Operate at > 1.03 times the pickup ±3% of operate time or 50 ms
    (whichever is greater)
    Saturation Level: ....................................................................... 48 times the pickup level
    Snapshot Events: ...................................................................... selectable by setting
    PHASE AND GROUND INSTANTANEOUS OVERCURRENT (50PH/50PL/50G)
    Current Input: .............................................................................phasor (without harmonics) or RMS
    Rated Current:............................................................................ for connection to 1 or 5 A CTs
    Pickup Level: ............................................................................... 0.05 to 160.00 A in steps of 0.01 A
    Dropout Level: ............................................................................ 97% to 98% of the pickup level
    Level Accuracy: ......................................................................... values at nominal frequency:
    ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A
    ±1.5% of the reading for higher values
    Overreach: ................................................................................... < 2%
    Trip Delay: .................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ................................................................................ 0.00 to 900.00 s in steps of 0.01 s
    Operate T ime: ............................................................................ < 50 ms at 3 x pickup at 50 Hz, typically
    T iming Accuracy: ..................................................................... at 0 ms time delay (no intentional delay): 50 ms
    at non-zero time delay: ±3% of operate time or 50 ms
    (whichever is greater)
    Snapshot Events: ...................................................................... selectable by setting
    NEUTRAL INSTANTANEOUS OVERCURRENT (50N)
    Current Input: .............................................................................fundamental phasor (without harmonics)
    Pickup Level: ............................................................................... 0.05 to 160.00 A in steps of 0.01 A
    Dropout Level: ............................................................................ 97% to 98% of the pickup level
    Level Accuracy: ......................................................................... values at nominal frequency:
    ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A
    ±1.5% of the reading for higher values
    Overreach: ................................................................................... < 2%
    Trip Delay: .................................................................................... 0.00 to 900.00 s in steps of 0.01 s
    Reset Delay: ................................................................................ 0.00 to 900.00 s in steps of 0.01 s
    Operate T ime: ............................................................................ < 50 ms at 3 x pickup at 50 Hz, typically
    T iming Accuracy: ..................................................................... at 0 ms time delay (no intentional delay): 50 ms
    at non-zero time delay: ±3% of operate time or 50 ms
    (whichever is greater)
    Snapshot Events: ...................................................................... selectable by setting 
    						