    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-21
    2.5.4  User-programmable
    PLC LOGIC
    Programming language: ......................................................The logical configuration is performed using graphical functions based on the IEC 
    61131-3 st
    andard.
    Lines of code*:........................................................................... 640 lines of code or 15360 bytes, whichever is greater (for versions < 7.00)
    1000 total equations or 15360 bytes, whichever is greater (for versions >= 7.00)
    (*) Note: Reserved Modbus memory space of PLC equations in text format is up to 15360 bytes. This space is shared with informat ion 
    conf
     igured in Enervista at  Setpoint > Relay Conf iguration . According to this, the number of PLC equations can be limited by values 
    conf igured on that section.
    Supported operations: .......................................................... NOT, XOR, OR (2 to 8 inputs), AND (2 to 8 inputs), NOR (2 to 8 inputs), 
    NAND (2 to 8 inputs), Latch (Reset Dominant), Edge Detectors, T imers.
    2 inputs default gates, from 3 to 8 inputs provided in library format . 
    Starting in version 7.20, analog operators are also available.
    Libraries:....................................................................................... Logical gates fully programmable by user. Used to create user-programmable logic to 
    be d
    
    istributed as a single object .
    Inputs:............................................................................................ any logical variable, contact or virtual input
    Number of T imers: .................................................................. 8 maximum in each logic scheme (provided in library format)
    FLEXCURVES
    Number: .......................................................................................4 (A through D)
    Reset Points: ............................................................................... 40 (0 through 1 of pickup)
    Operate Point: ........................................................................... 80 (0 through 20 of pickup)
    T ime Delay:................................................................................. 0 to 65535 ms in steps of 1 ms
    Saturation Level: ...................................................................... 20 x the pickup level
    USER-PROGRAMMABLE LEDS
    Number: .......................................................................................15 conf igurable LEDs plus the Ready non-conf igurable LED
    Programmability: ..................................................................... any logical variable, contact , or virtual input
    Reset Mode: ................................................................................ self-reset or latched. 
    The f irst 5 LEDs (red) are latched by hardware, usually configured for trip signals.
    The following 10 LEDs (yellow and green) are self-reset but can be latched through PLC 
    conf
    
    iguration.
    Reset Signal: ............................................................................... The LEDs can be reset by hardware, pressing the front “esc” key for more than 3 
    second
    
    s or using the LED reset signal through PLC conf iguration.
    USER-DEFINABLE DISPLAYS
    Number of Conf igurable Displays: .................................. 1: one line diagram fully conf igurable. In graphical displays only
    Number of Fixed Displays: .................................................. 6: Metering (selectable between Primary and Secondary values), Snapshot Events (all 
    and new
    
    ), Alarms, Inputs and Outputs screen with test functionality for inputs and 
    outputs. (In graphical displays only.)
    Number of Selectable Displays: ........................................ 2: Logotype, Metering, or both in scrolling mode can be selected as the default screen 
    in t
    
    ext display for all models (basic and mimic). The metering screen contains current 
    and voltages for phases and ground in primary or secondary values.
    USER-PROGRAMMABLE FRONT KEYS
    Number of Conf igurable Keys:.......................................... 5
    Operation: ................................................................................... Drive PLC operands 
    						
    							2-22F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    2.5.5  Metering
    CURRENT
    Accuracy (at nominal frequency): .................................... ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A (for phases and ground)
    ±1.5% of the reading ± 1 mA from 0.005 to 5 A (for sensitive ground)
    ±1.5% of the reading for higher values
    % of Load-to-trip Accuracy: ................................................ ±0.5% of full-scale
    VOLTAGE
    Accuracy: .....................................................................................±1% of reading from 10 to 208 V
    REAL POWER (WATTS)
    Accuracy: .....................................................................................±2.0% of the reading at -0.8 ≤ PF  ≤ -1.0 and 0.8 < PF  ≤ 1.0
    REACTIVE POWER (VARS)
    Accuracy: ..................................................................................... ±2.0% of the reading at -0.2 ≤ PF  ≤ 0.2
    APPARENT POWER (VA)
    Accuracy: ..................................................................................... ±2.0% of the reading
    WATT-HOURS (POSITIVE AND NEGATIVE)
    Accuracy: .....................................................................................±2.0% of the reading
    Range: ............................................................................................ -2147483 to +2147483 MWh
    Parameters:................................................................................. 3-phase only
    Update Rate:............................................................................... 100 ms
    WAR-HOURS (POSITIVE AND NEGATIVE)
    Accuracy: .....................................................................................±2.0% of the reading
    Range: ............................................................................................ -2147483 to +2147483 MVArh
    Parameters:................................................................................. 3-phase only
    Update Rate:............................................................................... 100 ms
    FREQUENCY
    Accuracy: .....................................................................................+/- 0.03Hz
     From 30 to 80 Hz
    Note: Voltage input must be above 10 V to start measuring frequency
    ANGLE
    Accuracy: .....................................................................................±3º
    2.5.6  Inputs
    AC CURRENT INPUTS
    CT Ratio: ........................................................................................1.0 to 6000.0 in steps of 0.1
    Rated Currents:.......................................................................... Appropriate for 1 or 5 A. F650 has universal range for CT (valid for 1 or 5 A to only one 
    te
    
    rminal).
    Relay Burden: ............................................................................. < 8 mVA at 1 A 
    < 200 mVA at 5 A VA
    Input Impedance: ..................................................................... < 8 mOhm 
    Current Withstand: .................................................................. Continuous at 20 A
    1 s at 500 A for phases and ground
    1 s at 50 A for sensitive ground 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-23
    AC VOLTAGE INPUTS
    VT Ratio: .......................................................................................1.0 to 6000.0 in steps of 0.1
    Rated Voltage: ........................................................................... 275 Vac
    Metering Range: ....................................................................... From 2 to 275 Vac
    Relay Burden: ............................................................................ 0.05 VA at 120 Vac (50 or 60 Hz)
    Voltage Withstand:.................................................................. Continuous at 275 V to neutral
    1 min/hr at 420 to neutral
    VAC inputs do not need varistors, as the impulse  test is applied to 100% of the transformers
    CONTACT INPUTS
    Input Activation Threshold: .................................................10 to 230 Vdc in steps of 1 V (selectable by setting)
    Impedance:................................................................................. > 100 kΩ
    Maximum Error: ........................................................................ ±10% setti
    ng or ±  5 V
    Load for Voltage Supervision Inputs:.............................. 2 mA + V/100 kΩ
    Voltage Threshold for Voltage Supervision Inputs: .. < 10 V (fixed)
    Debounce T ime: ....................................................................... 1 to 50 ms in steps of 1 ms
    Recognition T ime: .................................................................... 2 ms (typical)
    T iming Resolution:................................................................... 1 ms
    For Activation Voltage Threshold and Debounce T ime there is a single setting for all inputs in the same group (all inputs shari ng the sa
     me 
    common).
    Input Type and Delay Input Time are not grouped; there is a different setting for each input.
    Input Type: .................................................................................. positive-edge/negative-edge/positive/negative
    Delay Input T ime: .................................................................... 0 to 60000 ms in steps of 1 ms (input signal time delay)
    REMOTE INPUTS (IEC61850 GSSE/GOOSE)
    Number of Input Devices: ....................................................32, conf igured from 64 incoming bit pairs
    Number f Remote Devices: ................................................. 16 (24 for relay version 7.00 and above)
    Default States on Loss of Comms: ................................... On, Off, Latest/on, Latest/off
    ANALOG INPUTS
    Input Impedance: ....................................................................116Ω
    Current Input (mADC): ............................................................ 0 to -1; 0 to +1; -1 to +1; 0 to 5; 0 to 10; 0 to 20; 4 to 20 (programmable)
    Conversion Range: .................................................................. -1 to +20 mA
    Accuracy:..................................................................................... ±0.2% of full scale
    Type: .............................................................................................. passive
    IRIG-B INPUT
    Amplitude Modulation: ..........................................................DC SHIFT = demodulated input (no carrier)
    Input Voltage: ............................................................................ TTL
    Input Burden: ............................................................................. 1.5 mA
    Input Impedance: .................................................................... 3.3 kΩ
    Minimum Input Voltage: ....................................................... 2.4 V
    Maximum Input Voltage: ...................................................... ± 24 V
    Formats: ....................................................................................... B000 (*) B001, B002 and B003 (*
    (*) Signal combinations recognized in accordance with IRIG Standard 200-95
    Isolation:....................................................................................... 2 kV 
    						
    							2-24F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    2.5.7  Real time clock
    Accuracy: ..................................................................................... typical ±20 ppm
    Backup Energy: ......................................................................... more than 1 week
    Note : For r
    elay versions before 7.00, when the relay date and time is changed using any documented methods (Modbus, IRIG-B, SNTP, 
    Front Panel...) the relay acknowledges and updates the time instantly but it takes nearly 3 minutes for the new time to be perm anently 
    stored in the Real T ime Clock’s NVRAM.
    2.5.8  Outputs
    OUTPUTS
    Single Contact Carry continuous: ..................................... 16 A 
    Make and Carry for 1 s: ......................................................... 60 A
    Break at L/R of 40 ms: ............................................................ 0.3 A DC max. at 125 Vdc
    0.25 A DC max. at 250 Vdc
    Operate T ime: ............................................................................ < 8 ms
    Contact Material: ...................................................................... silver alloy
    Output Logic Type, Output Type and Pulse Output Time are selectable by setting for each output
    Output Logic Type:...................................................................positive/negative
    Output Type: ............................................................................... normal/pulse/latch (selectable by setting for each output)
    Pulse Output T ime: .................................................................. 0 to 60000 ms in steps of 1 ms (applicable only to signals sent as pulse type)
    Separate operate and reset signals can be configured by any digital signal programmable through the PLC
    Contact Outputs (F31-F33, F34-F36) for board type 
    2 (supervision) in slot F: .................................................... The current seal-in circuit is used for verifying the current condition in a circuit during 
    the tim
    
    e that the tripping contact remains closed. If the current in the tripping circuit is 
    maintained over 500 mA, the function is sealed independently of the status of the 
    function that caused the trip.
    REMOTE OUTPUTS (IEC61850 GSSE/GOOSE)
    Standard Output Points: ........................................................ 32
    User Output Points:.................................................................. 32
    2.5.9  Control power supply
    LOW RANGE (LO) ALL RANGES
    Nominal DC Voltage:24 to 48 VPower Consumption:Typical =25 VA, Maximum =45 VA
    Min/Max DC Voltage 19.2 / 57.6 VDisplay backlight auto power-off mode after 15 minutes without touching 
    any key
     , in order to ensure long life and 
    minimum consumption
    Note:
    Low range is DC only
    Voltage Loss hold-up time:(*) 24 Vdc 30 ms
    48 Vdc 100 ms
    (*) These figures have been calculated for  models wit
     h the following characteristic:
    - IEC Symbols Graphic display
    - Rear Ethernet Communication Board 2: PRP, 1588, 10/100 Base TX+ Redundant 100 Base FX 
    - F and G I/O Board:
            Slot F: 8 Digital Inputs + 8 Output
     s + 2 Trip / Close circuit supervision circuits 
            Slot G: 16 Digital Inputs + 8 Outputs 
    HIGH RANGE (HI) INTERNAL FUSE
    Nominal DC Voltage:110 to 250 VV:250 VAC
    Min/Max DC Voltage 88 / 300 VI:2.5A
    Nominal AC Voltage: 120 to 230 VSize:5 x 20 mm
    Min/Max AC Voltage: 102 / 250 VTy p e :Quick acting (F)
    Voltage Loss Hold-up Time: 200 ms typical
    100 ms worst case UL listed miniature Fuse 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-25
    2.5.10  Communications
    FRONT PORT: 
    Front port:COM2
    Type: RS232/USB
    Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200 baud
    Default Baud Rate: 19200 baud
    Protocols: ModBus
    ® RTU/DNP 3.0
    Typical Distance: 3 m
    Isolation: 2 kV
    ASYNCHRONOUS REAR PORTS:
    None or two rear ports (depending on model):COM1, COM2 (rear COM2 multiplexed with front port)
    Type (depending on model):
    Model F None
    Model A Redundant RS485
    Model X Redundant RS485 + fiber CAN for inputs/outputs module 
    Model P Redundant 1mm-plastic F.O.
    Model Y Redundant 1mm-plastic F.O. + fiber CAN for inputs/outputs module 
    Model G Redundant multimode glass F.O. 
    Model Z Redundant multimode glass F.O. + fiber CAN for inputs/outputs module 
    Model C Cable CAN port for I/O module 
    Model M Cable CAN port for I/O module (cable) + RS485 (ModBus RTU)
    Optic Features for ST Connector Devices: Wave length: 1300nm
    Fiber type: multimode 62.5/125 μm or 50
     /125 μm
    Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200 baud
    Default Baud Rate: 19200 baud
    Protocols: ModBus
    ® RTU/DNP 3.0/IEC103
    Typical Distance:  1200 m for cooper cable, 1000 m for glass fiber 
     and 50 m for plastic fiber
    Isolation: 2 kV
    CAN PORT: 
    Rear Port:CAN port in models C, M, X, Y, Z for asynchronous rear ports
    Type: Multimode glass F.O. port with ST connectors
    Fiber Wavelength: 820 nm
    Fiber Type: multimode 62.5/125 μm or
      50/125 μm
    Maximum Recommended Length: 300 m for cooper cable and glass fiber
    Isolation: 2 kV
    ETHERNET PORT:
    Rear port: 
    For models B, C, D, E:ETH_1/ ETH_2
    For models G, H, J, K, L, M: ETH_E/ ETH_A/ ETH_B
    Type (depending on model):
    Model B:  10/100BaseTX self-negotiable
    Model C:  10/100BaseTX + 100Base FX
    Model D:  10/100BaseTX + redundant 100BaseFX (Physical media redundancy)
    Model E:  Redundant 10/100BaseTX self-negotiable ports
    Model G:  1588, 10/100 Base TX* + 100 Base TX
    Model H:  1588, 10/100 Base TX* + 100 Base FX
    Model J:  PRP, 1588, 10/100 Base TX* + Redundant 100 Base FX
    Model K:  PRP, HSR, RSTP, 1588, 10/100 Base TX* + Redundant 100 Base FX
    Model L:  PRP, 1588, 10/100 Base TX* + Redundant 100 Base TX
    Model M:  PRP, HSR, RSTP, 1588, 10/100 Base TX* + Redundant 100 Base TX 
    (*) Note: This Ethernet port (ETH_E) is intended o
     nly for maintenance purposes. 
    						
    							2-26F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    10/100BaseTX: RJ45 connector
    100BaseFX: ST connectors
    Wavelength:  1300 nm
    Fiber Type:  multimode 62.5/125 μm or
      50/125 μm
    Protocols:  ModBus® TCP/IP
    DNP over TCP/IP and UDP/IP
    IEC 61850
    http, ftp, tftp (allow the use of a standard Internet browser)
    Typical Distance: 1000 m for glass fiber and 150 m for RJ45 cable
    Response Time to ModBus Commands: 10 ms typical
    Isolation: 2 kV
    In Models C and D, the 10/100BaseTX port is selected by an internal switch (see 3.3.3)
    Two witness LEDs for transmiss ion an
     d reception are included
    SIMPLE NETWORK TIME PROTOCOL (SNTP)
    Clock Synchronization error:  
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-27
    2.5.11  Optical
    Wave length: 1300 nm
    Connector types:  ST p
     ackage style 
    Fiber type:  multimo
     de 62.5/125 μm or 50/125 μ m
    Notes:
    1. These optical power values are measured with the following conditions:
    The Beginning of Live (BOL) to the End of Life (EOL) op tical power degradation is typically 1.5 dB per industry 
    convention for long wavelength LEDs. The actual degradatio n observed in Agilent’s 1300nm LED products is 
    						
    							2-28F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.5 TECHNICAL SPECIFICATIONS CHAPTER 2:  PRODUCT DESCRIPTION
    2.5.12  Environmental
    Operating Temperature:........................................................ - 10°C to + 60° C
    Storage Temperature: ............................................................ - 40°C t
    o + 85° C
    Humidity (non-condensing):................................................ 95%
    Altitude: ......................................................................................... up to 2000 m
    Class of Equipment:................................................................. I
    Equipment Mobility: ................................................................ fixed
    Overvoltage Category:........................................................... III
    Pollution Degree:....................................................................... 2
    2.5.13  Packaging and weight
    Net Weight:..................................................................................5 kg
    Packaged Weight: .................................................................... 6 kg
    Package Dimensions: ............................................................. 30 x 40 x 40 cm (D x W x H)
    2.5.14  Type tests
    Type test report available upon request.
    F650 has been designed to comply with the highest existing  requirements. More specifically, UNIPEDE recommendations 
    for high voltage substations are followed, even if for most applications such high classes are not required.
    The relay complies with ANSI C37.90 standards, and has be en designed to comply with international standards.
    CATEGORYSTANDARDCLASSTEST
    SAFETY
    Dielectric voltage withstandIEC60255-272 KV / 2.3 KV
    Impulse voltage withstand IEC60255-275 KV
    Insulation resistance IEC60255-27500 V (test level)
    EMC Electrostatic Discharge Immunity
    IEC60255-26/IEC61000-4-2Level 4
    Radiated RF Electromagnetic Field Immunity IEC60255-26/IEC61000-4-3Level 3
    Electrical Fast Transient Immunity IEC60255-26/IEC61000-4-4Zone A
    Surge Immunity IEC60255-26/IEC61000-4-5Zone A
    Conducted RF Immunity IEC60255-26/IEC61000-4-6Level 3
    Power magnetic Immunity IEC60255-26/IEC61000-4-8Level 5
    Power Frequency Immunity IEC60255-26/IEC61000-4-16Zone A
    Damped Oscillatory Wave Immunity IEC60255-26/IEC61000-4-18
    2.5 KV Common Mode 1 KV Diff. Mode
    Voltage Dips & InterruptionsIEC60255-26/IEC61000-4-11/
    IEC
    61000-4-29 Levels based on IEC61000-4-11 & 
    IEC61000-4
    -29
    Ripple on DC IEC60255-26/IEC61000-4-1715% Rated DC value
    Radiated & Conducted Emissions IEC60255-26/CISPR11/
    CI
    
    SPR22 Class A
    MECHANICAL Sinusoidal Vibration
    IEC60255-21-1Class 1
    Shock & Bump IEC60255-21-2Class 1
    Seismic IEC60255-21-3Class 2
    Enclosure Protection IEC60255-27/IEC60529IP52
    CLIMATIC Cold test (storage)
    IEC60068-2-1-40˚C 16 hrs
    Cold test (operational) IEC60068-2-1-20˚C 16 hrs
    Dry heat test (storage) IEC60068-2-285˚C 16 hrs
    Dry heat test (operational) IEC60068-2-260˚C 16 hrs
    Change of Temperature IEC60068-2-145 cycles (3+3) -20˚C/6
     0˚C
    Damp Heat Humidity Cyclic IEC60068-2-306 cycles (12+12) 55˚C @ 93% R.H.
    Damp Heat steady state IEC60068-2-7840˚C 
    @ 93% R.H. 
    						
    							CHAPTER 2:  PRODUCT DESCRIPTION2.5 TECHNICAL SPECIFICATIONS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER 2-29
    2.5.15  Approvals
    EAC
    The EAC Technical Regulations (TR) for Machines and Equipment apply to the Customs Union (CU) of the Russian 
    Federation, Belarus, and Kazakhstan
    APPLICABLE COUNCIL DIRECTIVEACCORDING TO
    CE COMPLIANCE
    Low voltage directive IEC60255-27
    DirectiveIEC60255-26
    NORTH AMERICAULUL508
    EACMachines and EquipmentTR CU 010/2011
    ISOManufactured under a registered quality programISO9001
    Item Description
    Country of origin Spain
    Date of manufacture See label on the F650 unit
    Declaration of Conformity and/or Certif icate of Conformity Available on request 
    						
    							2-30F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    2.6 EXTERNAL CONNECTIONS CHAPTER 2:  PRODUCT DESCRIPTION
    2.6  External connections
    Figure 2-2: F650 wiring diagram (189C4216H2) 
    						