    							APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-15
    Setpoint > Protection Elements > Neutral Current > Neutral IOC
    Neutral IOC 1 > Neutral IOC 2 > Neutral IOC 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Pickup level Pickup Level30.000.01 
    A[0.05 : 160.00]
    Trip time Trip Delay0.000.01 
    s[0.00 : 900.00]
    Reset time Reset Delay0.000.01 
    s
    [0.00 : 900.00]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Ne utral Current > Neutral Directional >
    Neutral Directional 1 > Neutral Directional 2 > Neutral Directional 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Maximum Torque Angle MTA-451 
    Deg[-90 : +90]
    Operation Direction DirectionFORWARDN/A[FORWARD – REVERSE]
    Polarization type PolarizationVON/A[V
    0 – IP – V0+IP – V0*IP ]
    Block logic type Block LogicPERMISSIONN/A[BLOCK – PERMISSION]
    Polarization voltage threshold Pol V Threshold101 V[0 : 300]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Ground Current > Ground TOC
    Ground TOC 1 > Ground TOC 2 > Ground TOC 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Input type InputPHASOR(DFT)N/A[PHASOR – RMS]
    Pickup level Pickup Level1.000.01 
    A
    [0.05 : 160.00]
    Curve shape CurveIEEE Ext InvN/A[See list of curves]
    Time Dial TD Multiplier1.000.01 
    s[0.00 : 900.00]
    Reset type ResetINSTANTANEOUSN/A[INSTANTANEOUS – LINEAR]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements  > Ground Current > Ground IOC
    Ground IOC 1 > Ground IOC 2 > Ground IOC 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Input type InputPHASOR(DFT)N/A[PHASOR – RMS]
    Pickup levelPickup Level30.000.01 
    A[0.05 : 160.00]
    Trip time Trip Delay0.000.01 
    s[0.00 : 900.00]
    Reset time Reset Delay0.000.01 
    s[0.00 : 900.00]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] 
    						
    							D-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
    Setpoint > Protection Elements > Ground Current > Ground Directional >
    Ground Directional 1 > Ground Directional 2 > Ground Directional 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Maximum Torque Angle MTA-451 
    Deg[-90 : +90]
    Operation Direction DirectionFORWARDN/A[FORWARD – REVERSE]
    Polarization typePolarizationVON/A[V0 – IP – V0+IP – V0*IP ]
    Block logic typeBlock LogicPERMISSIONN/A[BLOCK – PERMISSION]
    Polarization voltage threshold Pol V Threshold101 V[0 : 300]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Sensitiv e Ground Current > Sensitive Ground TOC
    Sensitive Ground TOC 1 > Sensitive Ground TOC 2 > Sensitive Ground TOC 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Input type InputPHASOR(DFT)N/A[PHASOR – RMS]
    Pickup level Pickup Level0.0500.00
    1 A[0.005 : 16.000]
    Curve shape CurveIEEE Ext InvN/A[See list of curves]
    Time Dial TD Multiplier1.000.01 
    s[0.00 : 900.00]
    Reset type ResetINSTANTANEOUSN/A[INSTANTANEOUS – LINEAR]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Sensitiv e Ground Current > Sensitive Ground IOC
    Sensitive Ground IOC 1 > Sensitive Ground IOC 2 > Sensitive Ground IOC 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Input type InputPHASOR(DFT)N/A[PHASOR – RMS]
    Pickup level Pickup Level0.1000.00
    1 A[0.005 : 16.000]
    Trip time Trip Delay0.000.01 
    s[0.00 : 900.00]
    Reset time Reset Delay0.000.01 
    s[0.00 : 900.00]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Sensitiv e Ground Current > Isolated Ground IOC
    Isolated Ground IOC 1 > Isolated Ground IOC 2 > Isolated Ground IOC 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function Permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    High Voltage level Vh Level201 V[2 : 70]
    Low Current levelIl LEVEL0.0050.00
    1 A[0.005 : 0.400]
    Low Voltage level Vl LEVEL21 V[2 : 70]
    High Current level Ih LEVEL0.0250.00
    1 A[0.005 : 0.400] 
    						
    							APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-17
    Operation timeDelay0.000.01 
    s[0.00 : 900.00]
    Deviation time to instantaneous Time to inst0.000.01 
    s[0.00 : 900.00]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Sensitive Gr ound Current > Sensitive Ground Directional >
    Sensitive Ground Directional 1 > Sensitive Ground Directional 2 > Sensitive Ground Directional 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permissionFunctionDISABLEDN/A[DISABLED – ENABLED]
    Maximum Torque AngleMTA-451 
    Deg[-90 : +90]
    Operation Direction DirectionFORWARDN/A[FORWARD – REVERSE]
    Block logic type Block LogicPERMISSIONN/A[BLOCK – PERMISSION]
    Polarization voltage threshold Pol V Threshold101 V[0 : 300]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Negative  Sequence Current > Negative Sequence TOC >
    Negative Sequence TOC 1 > Negative Sequence TOC 2 > Negative Sequence TOC 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Pickup level Pickup Level1.000.01 
    A[0.05 : 160.00]
    Curve shape CurveIEEE Ext InvN/A[See list of curves]
    Time Dial TD Multiplier1.000.01 
    s
    [0.00 : 900.00]
    Reset type ResetINSTANTANEOUSN/A[INSTANTANEOUS – LINEAR]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements  > Voltage Elements > Phase UV >
    Phase UV 1 > Phase UV 2 > Phase UV 3 
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Input mode ModePHASE-PHASEN/A[PHASE-PHASE, PHASE-
    GR
    
    OUND]
    Pickup Level Pickup Level101 V[3 : 300]
    Curve shape CurveDEFINITE TIMEN/A[DEFINITE TIME – INVERSE 
    TIME]
    Time Dial Delay10.000.01 
    s[0.00 : 900.00]
    Minimum Voltage Threshold Minimum Voltage51 V[0 : 300]
    Operation logic LogicANY PHASEN/A[ANY PHASE – TWO PHASES 
    – ALL PHASES]
    Supervision by breaker status Supervised by 52DISABLEDN/A[DISABLED – ENABLED]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements  > Voltage Elements > Phase OV >
    Phase OV 1 > Phase OV 2 > Phase OV 3 
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value 
    						
    							D-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
    Function permissionFunctionDISABLEDN/A[DISABLED – ENABLED]
    Pickup Level Pickup Level101 V[3 : 300]
    Trip time Trip Delay10.000.01 
    s[0.00 : 900.00]
    Reset time Reset Delay0.000.01 
    s[0.00 : 900.00]
    Operation logic LogicANY PHASEN/A[ANY PHASE – TWO PHASES 
    – ALL PHASES]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elem ents > Voltage Elements >
    >Neutral OV High > Neutral OV High 1 >  Neutral OV High 2 > Neutral OV High 3
    >Neutral OV Low > Neutral OV Low 1 > Neutral OV Low 2 > Neutral OV Low 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Pickup Level Pickup Level101 V[3 : 300]
    Trip time Trip Delay10.000.01 
    s[0.00 : 900.00]
    Reset time Reset Delay0.000.01 
    s[0.00 : 900.00]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > voltage  elements > Negative Sequence OV >
    Negative Sequence OV 1 > Negative Sequ ence OV 2 > Negative Sequence OV 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Pickup Level Pickup Level101 V[3 : 300]
    Trip time Trip Delay10.000.01 
    s[0.00 : 900.00]
    Reset time Reset Delay0.000.01 
    s[0.00 : 900.00]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements  >voltage elements > Auxiliary oV
    Auxiliary oV 1 > Auxiliary oV 2 > Auxiliary oV 3 
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Pickup Level Pickup Level101 V[3 : 300]
    Trip T ime Trip Delay10.000.01 
    s
    [0.00 : 900.00]]
    Reset T ime Reset Delay0.000.01 
    s[0.00 : 900.00]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements  >voltage elements > Auxiliary UV
    Auxiliary UV 1 > Auxiliary UV 2 > Auxiliary UV 3 
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Pickup LevelPickup Level101 V[3 : 300] 
    						
    							APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-19
    Curve shapeCurveDEFINITE TIMEN/A[DEFINITE TIME – INVERSE 
    TIME]
    Time Dial Delay10.000.01 
    s[0.00 : 900.00]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Power > Forward Power
    Forward Power 1 > Forward Power 2 > Forward Power 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Block from offline Blk T ime After Close0.000.01 
    s
    [0.00 : 900.00]
    Pickup level for stage 1 Stage 1 Tap10.000.01
    MW[0.00 : 10000.00]
    Trip time for stage 1 Stage 1 T ime60.000.01 
    s[0.00 : 900.00]
    Pickup level for stage 2 Stage 2 Tap20.000.01
    MW[0.00 : 10000.00]
    Trip time for stage 2 Stage 2 T ime60.000.01 
    s[0.00 : 900.00]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Power > Directional Power>
    Directional Power 1 > Directional Power 2 > Directional Power 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Block from offline Blk T ime After Close0.000.01 
    s
    [0.00 : 900.00]
    Directional Angle for stage 1 Dir Power Angle 10.000.01 
    Deg[0.00 : 359.99]
    Pickup level for stage 1 Stage 1 Tap10.000.01
    MW[-10000.00 : 10000.00]
    Trip time for stage 1 Stage 1 T ime60.000.01 
    s
    [0.00 : 900.00]
    Directional Angle for stage 2 Dir Power Angle 20.001 
    Deg[0.00 : 359.99]
    Pickup level for stage 2 Stage 2 Tap20.000.01
    MW[-10000.00 : 10000.00]
    Trip time for stage 2 Stage 2 T ime60.000.01 
    s[0.00 : 900.00]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Protection Elements > Power 
    WATT GND FLT HIGH 1 > WATT GND FLT HIGH 2 > WATT GND FLT HIGH 3WATT GND FLT LOW 1 > WATT GND FLT LOW 2 > WATT GND FLT LOW 3
    SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER 
    VALUE
    Function permission FunctionDISABLEDN/A[DISABLED-ENABLED]
    Supervision minimum voltageVoltage Pickup Level20.01 
    V[2.00 : 70.00]
    Source of operating current . Current selectionINN/A[IN-IG]
    Pickup Level for Overcurrent OC Pickup Level0,0050.00
    1A[0.005 : 0.400] 
    						
    							D-20F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
    Pickup Delay for OvercurrentOC Pickup Delay0,20.01 
    s[0.00 : 600.00]
    Pickup Level for operating Power Power Pickup0,010.01 
    W[0.01 : 4.50]
    Max torque angle MTA01 
    Deg[0 : 360]
    Pickup Delay for Operating Power Power Pickup Delay0,20.01 
    s[0.00 : 600.00]
    Curve shape CurveDEFINITE TIMEN/A[DEFINITE TIME - INVERSE 
    TIME - USER C
    
    URVE A - 
    USER CURVE B - USER 
    CURVE C - USER CURVE D]
    MultiplierMultiplier10.01 
    s[0.02 : 2.00]
    Snapshot event generation Snapshot EventDISABLEDN/A[DISABLED-ENABLED]
    Setpoint > Control Elements > Setting Group
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Setting Grouping Permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Active Group Active GroupGROUP 1N/A[GROUP 1 – GROUP 2 – 
    GR
    
    OUP 3]
    Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Control Elements > Underfrequency
    Underfrequency 1 > Underfrequency 2 > Underfrequency 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Pickup level Pickup Level49.500.01 
    Hz
    [20.00 : 65.00]
    Trip time Trip Delay0.000.01 
    s[0.00 : 900.00]
    Reset time Reset Delay0.000.01 
    s[0.00 : 900.00]
    Minimum voltage threshold Minimum Voltage301 V[10 : 300]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Control Elements > Overfrequency
    Overfrequency 1 > Overfreq uency 2 > Overfrequency 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permissionFunctionDISABLEDN/A[DISABLED – ENABLED]
    Pickup level Pickup Level50.500.01 
    Hz[20.00 : 65.00]
    Trip time Trip Delay0.000.01 
    s[0.00 : 900.00]
    Reset timeReset Delay0.000.01 
    s[0.00 : 900.00]
    Minimum voltage threshold
    Minimum Voltage301 V[10 : 300]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] 
    						
    							APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-21
    Setpoint > Control Elements > Synchrocheck
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Dead bus voltage level Dead Bus Level10.000.01 
    V[0.00 : 300.00]
    Live bus voltage level Live Bus Level50.000.01 
    V[0.00 : 300.00]
    Dead line voltage level Dead Line Level10.000.01 
    V[0.00 : 300.00]
    Live line voltage level Live Line Level50.000.01 
    V[0.00 : 300.00]
    Voltage Difference Max Volt Difference10.000.01 
    V[2.00 : 300.00]
    Angle Difference Max Angle Difference10.00.1 
    Deg[2.0 : 80.0]
    Frequency Slip Max Freq Difference2010 
    mH
    
    z[10 : 5000]
    Breaker Closing timeTime0.500.01 
    s[0.01 : 600.00]
    Dead Line – Dead Bus Function permission
    DL-DB FunctionDISABLEDN/A[DISABLED – ENABLED]
    Live Line – Dead Bus Function permission LL-DB FunctionDISABLEDN/A[DISABLED – ENABLED]
    Dead Line – Live Bus Function permission DL-LB FunctionDISABLEDN/A[DISABLED – ENABLED]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Control Elements > Autoreclose
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Maximum Number of shots Max Number Shots1N/A[1 : 4]
    Dead time 1 Dead T ime 10.000.01 
    s[0.00 : 900.00]
    Dead time 2 Dead T ime 20.000.01 
    s[0.00 : 900.00]
    Dead time 3 Dead T ime 30.000.01 
    s
    [0.00 : 900.00]
    Dead time 4 Dead T ime 40.000.01 
    s[0.00 : 900.00]
    Reclaim time or reset lockout delay Reclaim T ime0.000.01 
    s[0.00 : 900.00]
    Reclose conditions permission Cond. PermissionDISABLEDN/A[DISABLED – ENABLED]
    Hold time Hold T ime0.000.01 
    s[0.00 : 900.00]
    Reset time Reset T ime0.000.01 
    s[0.00 : 900.00]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Control Elem ents > breaker failure
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Supervision (retrip) pickup level Supervision Pickup1.000.01 
    A
    [0.05 : 160.00]
    Hiset pickup level Hiset Pickup5.000.01 
    A[0.05 : 160.00] 
    						
    							D-22F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
    Lowset pickup levelLowset Pickup2.000.01 
    A[0.05 : 160.00]
    Internal arc pickup level Internal Arc Pickup0.100.01 
    A[0.05 : 160.00]
    Internal arc time delay Internal Arc Delay10.000.01 
    s[0.00 : 900.00]
    Retrip time delay Supervision Delay10.000.01 
    s[0.00 : 900.00]
    Hiset time delay HiSet Delay10.000.01 
    s[0.00 : 900.00]
    Lowset time delay LowSet Delay10.000.01 
    s[0.00 : 900.00]
    Second stage time delay 2nd Step Delay10.000.01 
    s[0.00 : 900.00]
    WITHOUT current element time delay No Current Delay10.000.01 
    s[0.00 : 900.00]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Control Elemen ts > VT Fuse Failure)
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLED
    N/A[DISABLED – ENABLED]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Setpoint > Control Elements > BROKEN CONDUCTOR
    Broken Conductor 1 > Broken Conductor 2 > Broken Conductor 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Tap Level in percentage of I2/I1 Tap200.10
    %[20.0 : 100.0]
    Trip T ime Trip Delay600.01 
    s[0.00 : 900.00]
    Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    Current Inhibition Level setting Operation Threshold0.0050.00
    1 A[0.000 : 1.000]
    Setpoint > Control Elements > Locked Rotor
    Locked Rotor 1 > Locked Rotor 2 > Locked Rotor 3
    Setting DescriptionNameDefault ValueStepRangeUser 
    Value
    Function permission FunctionDISABLEDN/A [DISABLED – ENABLED]
    Input type InputPHASOR(DFT) N/A[PHASOR – RMS]
    Full load current Full Load Current0.50KA[0.10 : 10.00]
    Pickup level Pickup Level1.01 N/A[1.01 : 109.00]
    Trip time Trip Delay0.00s[0.00 : 900.00]
    Reset time Reset Delay0.00s[0.00 : 900.00]
    Snapshot event generation Snapshot EventsENABLED N/A[DISABLED – ENABLED]
    SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS
    SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER 
    VALUE
    Pulse counter enabling setting CntPulses Enabled XDISABLEDN/A[DISABLED – ENABLED]
    Name of the pulse counter CntPulses Name XPulse Counter 1N/AN/A 
    						
    							APPENDIX D:  D.1 FACTORY DEFAULT SETTINGS
    GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-23
    Multiplier factor for the pulse counterCntPulses Factor X1.0000.00
    1[0.000 : 65000.000]
    Overflow value for the pulse counter CntPulses Overflow X655351[0 : 1000000]
    Board selection for the pulse counter CntPulses Board 
    Origin XF
    N/A[F,G,H,I]
    Input index inside the selected board CntPulses Input Origin 
    X1
    1[1 : 32]
    Note: X is the pulse counter index, up to 8. 
    SETPOINT > CONTROL ELEMENTS > ANALOG COMPARATORS
    SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER 
    VALUE
    Generic Analog Function Permission Analog FunctionDISABLEDN/A[DISABLED – ENABLED]
    Generic Snapshot Events Generation Analog Snapshot 
    Ev
    
    ents DISABLED
    N/A[DISABLED – ENABLED]
    Analog Input Value Selection Analog Input XNoneN/A[All available analog values]
    Analog Maximum Threshold Value Analog Maximum X1.0000.00
    1[-100000.000 : 100000.000]
    Analog Minimum Threshold Value Analog Minimum X1.0000.00
    1[-100000.000 : 100000.000]
    Analog Delay for Activation Signal Analog Delay X0.000.01 
    s[0.00 : 900.00]
    Analog Hysteresis for the Deadband Analog Hysteresis X1.00.1[0.0 : 50.0]
    Analog Direction for Activation Inside or 
    Ou
     tside the Deadband Analog Direction X
    OUTN/A[IN-OUT]
    Note: X is the analog comparator index, up to 20
    SETPOINT > CONTROL ELEMENTS > FREQUENCY RATE OF CHANGE
    FREQUENCY RATE OF CHANGE 1 > FREQUENCY RATE OF CHANGE 2 > FREQUENCY RATE OF CHANGE 3
    SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER 
    VALUE
    Function Permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Direction of the frequency change Freq. Rate TrendINCREASINGN/A[INCREASING - 
    DECRE
    
    ASING - BI-
    DIRECTIONAL]
    Operation Value in Hz/s Freq. Rate Pickup0.500.01 
    Hz
    
    /s [0.10 : 10.00]
    Minimum required voltage in % nominal 
    vo
     ltage Freq. Rate OV Supv
    40.000.01
    %[0.00 : 110.00]
    Minimum Frequency Threshold Freq. Rate Min45.000.01 
    Hz[20.00 : 80.00]
    Maximum Frequency Threshold Freq. Rate Max65.000.01 
    Hz[20.00 : 80.00]
    Frequency rate Trip Delay Freq. Rate Delay0.000.01 
    s[0.00 : 60.00]
    Snapshot Events Generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    SETPOINT > CONTROL ELEMENTS > LOAD ENCROACHMENT
    LOAD ENCROACHMENT 1 > LOAD ENCROACHMENT 2 > LOAD ENCROACHMENT 3
    SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER 
    VALUE
    Function Permission FunctionDISABLEDN/A[DISABLED – ENABLED]
    Minimum positive-sequence voltage 
    re
     quired Min. Voltage
    25.000.01 
    V[0.00 : 300.00]
    Impedance reach of the element Reach1.000.01 
    Ohm[0.02 : 250.00] 
    						
    							D-24F650 DIGITAL BAY CONTROLLER GEK-113000-AF
    D.1 FACTORY DEFAULT SETTINGS APPENDIX D:  
    Angle (Size of the blocking region)Angle51 
    Deg[5 : 50]
    Trip T ime Pickup Delay0.0000.00
    1 s[0.000 : 65.535]
    Reset T ime Reset Delay0.0000.00
    1 s[0.000 : 65.535]
    Snapshot Events Generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
    SETPOINT > CONTROL ELEMENTS > MAX. NUMBERS OF STARTS
    SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER 
    VALUE
    Function PermissionFunctionDISABLEDN/A[DISABLED- ENABLED]
    Motor Full Load CurrentFull Load Amps5.00.1 A[0.5: 10.0]
    Stop condition supe rvised by breakerBreaker SupervisionDISABLEDN/A[DISABLED- ENABLED]
    Min. Stop Time0.00.1s[0.0: 900.0]
    Number of Starts per tourNumber of Starts51[0: 100]
    Reset counter setting Reset CounterDISABLEDN/A[DISABLED- ENABLED]
    Snapshot Event GenerationSnapshot EventsENABLEDN/A[DISABLED- ENABLED]
    SETPOINT > CONTROL ELEMENTS > DIGITAL COUNTERS
    SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER 
    VALUE
    Function permissionDigCnt 1 FunctionDISABLED NA  
    Digital Counter 1 nameDigCnt 1 Name  NA  
    Digital counter 1 PresetDigCnt 1 Preset0 1[-2147483648 : 2147483647] 
    Digital counter 1 CompareDigCnt 1 Compare0 1
    [-2147483648 : 
    2147483647] 
    Function permissionDigCnt 2 FunctionDISABLED NA  
    Digital Counter 2 nameDigCnt 2 Name  NA  
    Digital counter 2 PresetDigCnt 2 Preset0 1
    [-2147483648 : 
    2147483647] 
    Digital counter 2 CompareDigCnt 2 Compare0 1[-2147483648 : 2147483647] 
    Function permissionDigCnt 3 FunctionDISABLED NA  
    Digital Counter 3 nameDigCnt 3 Name  NA  
    Digital counter 3 PresetDigCnt 3 Preset0 1
    [-2147483648 : 
    2147483647] 
    Digital counter 3 CompareDigCnt 3 Compare0 1
    [-2147483648 : 
    2147483647] 
    Function permissionDigCnt 4 FunctionDISABLED NA  
    Digital Counter 4 nameDigCnt 4 Name  NA  
    Digital counter 4 PresetDigCnt 4 Preset0 1[-2147483648 : 2147483647] 
    Digital counter 4 CompareDigCnt 4 Compare0 1
    [-2147483648 : 
    2147483647] 
    Function permissionDigCnt 5 FunctionDISABLED NA  
    Digital Counter 5 nameDigCnt 5 Name  NA  
    Digital counter 5 PresetDigCnt 5 Preset0 1
    [-2147483648 : 
    2147483647] 
    Digital counter 5 CompareDigCnt 5 Compare0 1[-2147483648 : 2147483647] 
    Function permissionDigCnt 6 FunctionDISABLED NA   
    						