APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-15 Setpoint > Protection Elements > Neutral Current > Neutral IOC Neutral IOC 1 > Neutral IOC 2 > Neutral IOC 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Pickup level Pickup Level30.000.01 A[0.05 : 160.00] Trip time Trip Delay0.000.01 s[0.00 : 900.00] Reset time Reset Delay0.000.01 s [0.00 : 900.00] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Ne utral Current > Neutral Directional > Neutral Directional 1 > Neutral Directional 2 > Neutral Directional 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Maximum Torque Angle MTA-451 Deg[-90 : +90] Operation Direction DirectionFORWARDN/A[FORWARD – REVERSE] Polarization type PolarizationVON/A[V 0 – IP – V0+IP – V0*IP ] Block logic type Block LogicPERMISSIONN/A[BLOCK – PERMISSION] Polarization voltage threshold Pol V Threshold101 V[0 : 300] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Ground Current > Ground TOC Ground TOC 1 > Ground TOC 2 > Ground TOC 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Input type InputPHASOR(DFT)N/A[PHASOR – RMS] Pickup level Pickup Level1.000.01 A [0.05 : 160.00] Curve shape CurveIEEE Ext InvN/A[See list of curves] Time Dial TD Multiplier1.000.01 s[0.00 : 900.00] Reset type ResetINSTANTANEOUSN/A[INSTANTANEOUS – LINEAR] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Ground Current > Ground IOC Ground IOC 1 > Ground IOC 2 > Ground IOC 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Input type InputPHASOR(DFT)N/A[PHASOR – RMS] Pickup levelPickup Level30.000.01 A[0.05 : 160.00] Trip time Trip Delay0.000.01 s[0.00 : 900.00] Reset time Reset Delay0.000.01 s[0.00 : 900.00] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
D-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Setpoint > Protection Elements > Ground Current > Ground Directional > Ground Directional 1 > Ground Directional 2 > Ground Directional 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Maximum Torque Angle MTA-451 Deg[-90 : +90] Operation Direction DirectionFORWARDN/A[FORWARD – REVERSE] Polarization typePolarizationVON/A[V0 – IP – V0+IP – V0*IP ] Block logic typeBlock LogicPERMISSIONN/A[BLOCK – PERMISSION] Polarization voltage threshold Pol V Threshold101 V[0 : 300] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Sensitiv e Ground Current > Sensitive Ground TOC Sensitive Ground TOC 1 > Sensitive Ground TOC 2 > Sensitive Ground TOC 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Input type InputPHASOR(DFT)N/A[PHASOR – RMS] Pickup level Pickup Level0.0500.00 1 A[0.005 : 16.000] Curve shape CurveIEEE Ext InvN/A[See list of curves] Time Dial TD Multiplier1.000.01 s[0.00 : 900.00] Reset type ResetINSTANTANEOUSN/A[INSTANTANEOUS – LINEAR] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Sensitiv e Ground Current > Sensitive Ground IOC Sensitive Ground IOC 1 > Sensitive Ground IOC 2 > Sensitive Ground IOC 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Input type InputPHASOR(DFT)N/A[PHASOR – RMS] Pickup level Pickup Level0.1000.00 1 A[0.005 : 16.000] Trip time Trip Delay0.000.01 s[0.00 : 900.00] Reset time Reset Delay0.000.01 s[0.00 : 900.00] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Sensitiv e Ground Current > Isolated Ground IOC Isolated Ground IOC 1 > Isolated Ground IOC 2 > Isolated Ground IOC 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function Permission FunctionDISABLEDN/A[DISABLED – ENABLED] High Voltage level Vh Level201 V[2 : 70] Low Current levelIl LEVEL0.0050.00 1 A[0.005 : 0.400] Low Voltage level Vl LEVEL21 V[2 : 70] High Current level Ih LEVEL0.0250.00 1 A[0.005 : 0.400]
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-17 Operation timeDelay0.000.01 s[0.00 : 900.00] Deviation time to instantaneous Time to inst0.000.01 s[0.00 : 900.00] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Sensitive Gr ound Current > Sensitive Ground Directional > Sensitive Ground Directional 1 > Sensitive Ground Directional 2 > Sensitive Ground Directional 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permissionFunctionDISABLEDN/A[DISABLED – ENABLED] Maximum Torque AngleMTA-451 Deg[-90 : +90] Operation Direction DirectionFORWARDN/A[FORWARD – REVERSE] Block logic type Block LogicPERMISSIONN/A[BLOCK – PERMISSION] Polarization voltage threshold Pol V Threshold101 V[0 : 300] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Negative Sequence Current > Negative Sequence TOC > Negative Sequence TOC 1 > Negative Sequence TOC 2 > Negative Sequence TOC 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Pickup level Pickup Level1.000.01 A[0.05 : 160.00] Curve shape CurveIEEE Ext InvN/A[See list of curves] Time Dial TD Multiplier1.000.01 s [0.00 : 900.00] Reset type ResetINSTANTANEOUSN/A[INSTANTANEOUS – LINEAR] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Voltage Elements > Phase UV > Phase UV 1 > Phase UV 2 > Phase UV 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Input mode ModePHASE-PHASEN/A[PHASE-PHASE, PHASE- GR OUND] Pickup Level Pickup Level101 V[3 : 300] Curve shape CurveDEFINITE TIMEN/A[DEFINITE TIME – INVERSE TIME] Time Dial Delay10.000.01 s[0.00 : 900.00] Minimum Voltage Threshold Minimum Voltage51 V[0 : 300] Operation logic LogicANY PHASEN/A[ANY PHASE – TWO PHASES – ALL PHASES] Supervision by breaker status Supervised by 52DISABLEDN/A[DISABLED – ENABLED] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Voltage Elements > Phase OV > Phase OV 1 > Phase OV 2 > Phase OV 3 Setting DescriptionNameDefault ValueStepRangeUser Value
D-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Function permissionFunctionDISABLEDN/A[DISABLED – ENABLED] Pickup Level Pickup Level101 V[3 : 300] Trip time Trip Delay10.000.01 s[0.00 : 900.00] Reset time Reset Delay0.000.01 s[0.00 : 900.00] Operation logic LogicANY PHASEN/A[ANY PHASE – TWO PHASES – ALL PHASES] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elem ents > Voltage Elements > >Neutral OV High > Neutral OV High 1 > Neutral OV High 2 > Neutral OV High 3 >Neutral OV Low > Neutral OV Low 1 > Neutral OV Low 2 > Neutral OV Low 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Pickup Level Pickup Level101 V[3 : 300] Trip time Trip Delay10.000.01 s[0.00 : 900.00] Reset time Reset Delay0.000.01 s[0.00 : 900.00] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > voltage elements > Negative Sequence OV > Negative Sequence OV 1 > Negative Sequ ence OV 2 > Negative Sequence OV 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Pickup Level Pickup Level101 V[3 : 300] Trip time Trip Delay10.000.01 s[0.00 : 900.00] Reset time Reset Delay0.000.01 s[0.00 : 900.00] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements >voltage elements > Auxiliary oV Auxiliary oV 1 > Auxiliary oV 2 > Auxiliary oV 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Pickup Level Pickup Level101 V[3 : 300] Trip T ime Trip Delay10.000.01 s [0.00 : 900.00]] Reset T ime Reset Delay0.000.01 s[0.00 : 900.00] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements >voltage elements > Auxiliary UV Auxiliary UV 1 > Auxiliary UV 2 > Auxiliary UV 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Pickup LevelPickup Level101 V[3 : 300]
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-19 Curve shapeCurveDEFINITE TIMEN/A[DEFINITE TIME – INVERSE TIME] Time Dial Delay10.000.01 s[0.00 : 900.00] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Power > Forward Power Forward Power 1 > Forward Power 2 > Forward Power 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Block from offline Blk T ime After Close0.000.01 s [0.00 : 900.00] Pickup level for stage 1 Stage 1 Tap10.000.01 MW[0.00 : 10000.00] Trip time for stage 1 Stage 1 T ime60.000.01 s[0.00 : 900.00] Pickup level for stage 2 Stage 2 Tap20.000.01 MW[0.00 : 10000.00] Trip time for stage 2 Stage 2 T ime60.000.01 s[0.00 : 900.00] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Power > Directional Power> Directional Power 1 > Directional Power 2 > Directional Power 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Block from offline Blk T ime After Close0.000.01 s [0.00 : 900.00] Directional Angle for stage 1 Dir Power Angle 10.000.01 Deg[0.00 : 359.99] Pickup level for stage 1 Stage 1 Tap10.000.01 MW[-10000.00 : 10000.00] Trip time for stage 1 Stage 1 T ime60.000.01 s [0.00 : 900.00] Directional Angle for stage 2 Dir Power Angle 20.001 Deg[0.00 : 359.99] Pickup level for stage 2 Stage 2 Tap20.000.01 MW[-10000.00 : 10000.00] Trip time for stage 2 Stage 2 T ime60.000.01 s[0.00 : 900.00] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Protection Elements > Power WATT GND FLT HIGH 1 > WATT GND FLT HIGH 2 > WATT GND FLT HIGH 3WATT GND FLT LOW 1 > WATT GND FLT LOW 2 > WATT GND FLT LOW 3 SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER VALUE Function permission FunctionDISABLEDN/A[DISABLED-ENABLED] Supervision minimum voltageVoltage Pickup Level20.01 V[2.00 : 70.00] Source of operating current . Current selectionINN/A[IN-IG] Pickup Level for Overcurrent OC Pickup Level0,0050.00 1A[0.005 : 0.400]
D-20F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Pickup Delay for OvercurrentOC Pickup Delay0,20.01 s[0.00 : 600.00] Pickup Level for operating Power Power Pickup0,010.01 W[0.01 : 4.50] Max torque angle MTA01 Deg[0 : 360] Pickup Delay for Operating Power Power Pickup Delay0,20.01 s[0.00 : 600.00] Curve shape CurveDEFINITE TIMEN/A[DEFINITE TIME - INVERSE TIME - USER C URVE A - USER CURVE B - USER CURVE C - USER CURVE D] MultiplierMultiplier10.01 s[0.02 : 2.00] Snapshot event generation Snapshot EventDISABLEDN/A[DISABLED-ENABLED] Setpoint > Control Elements > Setting Group Setting DescriptionNameDefault ValueStepRangeUser Value Setting Grouping Permission FunctionDISABLEDN/A[DISABLED – ENABLED] Active Group Active GroupGROUP 1N/A[GROUP 1 – GROUP 2 – GR OUP 3] Snapshot Event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Control Elements > Underfrequency Underfrequency 1 > Underfrequency 2 > Underfrequency 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Pickup level Pickup Level49.500.01 Hz [20.00 : 65.00] Trip time Trip Delay0.000.01 s[0.00 : 900.00] Reset time Reset Delay0.000.01 s[0.00 : 900.00] Minimum voltage threshold Minimum Voltage301 V[10 : 300] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Control Elements > Overfrequency Overfrequency 1 > Overfreq uency 2 > Overfrequency 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permissionFunctionDISABLEDN/A[DISABLED – ENABLED] Pickup level Pickup Level50.500.01 Hz[20.00 : 65.00] Trip time Trip Delay0.000.01 s[0.00 : 900.00] Reset timeReset Delay0.000.01 s[0.00 : 900.00] Minimum voltage threshold Minimum Voltage301 V[10 : 300] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED]
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-21 Setpoint > Control Elements > Synchrocheck Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Dead bus voltage level Dead Bus Level10.000.01 V[0.00 : 300.00] Live bus voltage level Live Bus Level50.000.01 V[0.00 : 300.00] Dead line voltage level Dead Line Level10.000.01 V[0.00 : 300.00] Live line voltage level Live Line Level50.000.01 V[0.00 : 300.00] Voltage Difference Max Volt Difference10.000.01 V[2.00 : 300.00] Angle Difference Max Angle Difference10.00.1 Deg[2.0 : 80.0] Frequency Slip Max Freq Difference2010 mH z[10 : 5000] Breaker Closing timeTime0.500.01 s[0.01 : 600.00] Dead Line – Dead Bus Function permission DL-DB FunctionDISABLEDN/A[DISABLED – ENABLED] Live Line – Dead Bus Function permission LL-DB FunctionDISABLEDN/A[DISABLED – ENABLED] Dead Line – Live Bus Function permission DL-LB FunctionDISABLEDN/A[DISABLED – ENABLED] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Control Elements > Autoreclose Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Maximum Number of shots Max Number Shots1N/A[1 : 4] Dead time 1 Dead T ime 10.000.01 s[0.00 : 900.00] Dead time 2 Dead T ime 20.000.01 s[0.00 : 900.00] Dead time 3 Dead T ime 30.000.01 s [0.00 : 900.00] Dead time 4 Dead T ime 40.000.01 s[0.00 : 900.00] Reclaim time or reset lockout delay Reclaim T ime0.000.01 s[0.00 : 900.00] Reclose conditions permission Cond. PermissionDISABLEDN/A[DISABLED – ENABLED] Hold time Hold T ime0.000.01 s[0.00 : 900.00] Reset time Reset T ime0.000.01 s[0.00 : 900.00] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Control Elem ents > breaker failure Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Supervision (retrip) pickup level Supervision Pickup1.000.01 A [0.05 : 160.00] Hiset pickup level Hiset Pickup5.000.01 A[0.05 : 160.00]
D-22F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Lowset pickup levelLowset Pickup2.000.01 A[0.05 : 160.00] Internal arc pickup level Internal Arc Pickup0.100.01 A[0.05 : 160.00] Internal arc time delay Internal Arc Delay10.000.01 s[0.00 : 900.00] Retrip time delay Supervision Delay10.000.01 s[0.00 : 900.00] Hiset time delay HiSet Delay10.000.01 s[0.00 : 900.00] Lowset time delay LowSet Delay10.000.01 s[0.00 : 900.00] Second stage time delay 2nd Step Delay10.000.01 s[0.00 : 900.00] WITHOUT current element time delay No Current Delay10.000.01 s[0.00 : 900.00] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Control Elemen ts > VT Fuse Failure) Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLED N/A[DISABLED – ENABLED] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Setpoint > Control Elements > BROKEN CONDUCTOR Broken Conductor 1 > Broken Conductor 2 > Broken Conductor 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A[DISABLED – ENABLED] Tap Level in percentage of I2/I1 Tap200.10 %[20.0 : 100.0] Trip T ime Trip Delay600.01 s[0.00 : 900.00] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Current Inhibition Level setting Operation Threshold0.0050.00 1 A[0.000 : 1.000] Setpoint > Control Elements > Locked Rotor Locked Rotor 1 > Locked Rotor 2 > Locked Rotor 3 Setting DescriptionNameDefault ValueStepRangeUser Value Function permission FunctionDISABLEDN/A [DISABLED – ENABLED] Input type InputPHASOR(DFT) N/A[PHASOR – RMS] Full load current Full Load Current0.50KA[0.10 : 10.00] Pickup level Pickup Level1.01 N/A[1.01 : 109.00] Trip time Trip Delay0.00s[0.00 : 900.00] Reset time Reset Delay0.00s[0.00 : 900.00] Snapshot event generation Snapshot EventsENABLED N/A[DISABLED – ENABLED] SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER VALUE Pulse counter enabling setting CntPulses Enabled XDISABLEDN/A[DISABLED – ENABLED] Name of the pulse counter CntPulses Name XPulse Counter 1N/AN/A
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-23 Multiplier factor for the pulse counterCntPulses Factor X1.0000.00 1[0.000 : 65000.000] Overflow value for the pulse counter CntPulses Overflow X655351[0 : 1000000] Board selection for the pulse counter CntPulses Board Origin XF N/A[F,G,H,I] Input index inside the selected board CntPulses Input Origin X1 1[1 : 32] Note: X is the pulse counter index, up to 8. SETPOINT > CONTROL ELEMENTS > ANALOG COMPARATORS SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER VALUE Generic Analog Function Permission Analog FunctionDISABLEDN/A[DISABLED – ENABLED] Generic Snapshot Events Generation Analog Snapshot Ev ents DISABLED N/A[DISABLED – ENABLED] Analog Input Value Selection Analog Input XNoneN/A[All available analog values] Analog Maximum Threshold Value Analog Maximum X1.0000.00 1[-100000.000 : 100000.000] Analog Minimum Threshold Value Analog Minimum X1.0000.00 1[-100000.000 : 100000.000] Analog Delay for Activation Signal Analog Delay X0.000.01 s[0.00 : 900.00] Analog Hysteresis for the Deadband Analog Hysteresis X1.00.1[0.0 : 50.0] Analog Direction for Activation Inside or Ou tside the Deadband Analog Direction X OUTN/A[IN-OUT] Note: X is the analog comparator index, up to 20 SETPOINT > CONTROL ELEMENTS > FREQUENCY RATE OF CHANGE FREQUENCY RATE OF CHANGE 1 > FREQUENCY RATE OF CHANGE 2 > FREQUENCY RATE OF CHANGE 3 SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER VALUE Function Permission FunctionDISABLEDN/A[DISABLED – ENABLED] Direction of the frequency change Freq. Rate TrendINCREASINGN/A[INCREASING - DECRE ASING - BI- DIRECTIONAL] Operation Value in Hz/s Freq. Rate Pickup0.500.01 Hz /s [0.10 : 10.00] Minimum required voltage in % nominal vo ltage Freq. Rate OV Supv 40.000.01 %[0.00 : 110.00] Minimum Frequency Threshold Freq. Rate Min45.000.01 Hz[20.00 : 80.00] Maximum Frequency Threshold Freq. Rate Max65.000.01 Hz[20.00 : 80.00] Frequency rate Trip Delay Freq. Rate Delay0.000.01 s[0.00 : 60.00] Snapshot Events Generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] SETPOINT > CONTROL ELEMENTS > LOAD ENCROACHMENT LOAD ENCROACHMENT 1 > LOAD ENCROACHMENT 2 > LOAD ENCROACHMENT 3 SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER VALUE Function Permission FunctionDISABLEDN/A[DISABLED – ENABLED] Minimum positive-sequence voltage re quired Min. Voltage 25.000.01 V[0.00 : 300.00] Impedance reach of the element Reach1.000.01 Ohm[0.02 : 250.00]
D-24F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Angle (Size of the blocking region)Angle51 Deg[5 : 50] Trip T ime Pickup Delay0.0000.00 1 s[0.000 : 65.535] Reset T ime Reset Delay0.0000.00 1 s[0.000 : 65.535] Snapshot Events Generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] SETPOINT > CONTROL ELEMENTS > MAX. NUMBERS OF STARTS SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER VALUE Function PermissionFunctionDISABLEDN/A[DISABLED- ENABLED] Motor Full Load CurrentFull Load Amps5.00.1 A[0.5: 10.0] Stop condition supe rvised by breakerBreaker SupervisionDISABLEDN/A[DISABLED- ENABLED] Min. Stop Time0.00.1s[0.0: 900.0] Number of Starts per tourNumber of Starts51[0: 100] Reset counter setting Reset CounterDISABLEDN/A[DISABLED- ENABLED] Snapshot Event GenerationSnapshot EventsENABLEDN/A[DISABLED- ENABLED] SETPOINT > CONTROL ELEMENTS > DIGITAL COUNTERS SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER VALUE Function permissionDigCnt 1 FunctionDISABLED NA Digital Counter 1 nameDigCnt 1 Name NA Digital counter 1 PresetDigCnt 1 Preset0 1[-2147483648 : 2147483647] Digital counter 1 CompareDigCnt 1 Compare0 1 [-2147483648 : 2147483647] Function permissionDigCnt 2 FunctionDISABLED NA Digital Counter 2 nameDigCnt 2 Name NA Digital counter 2 PresetDigCnt 2 Preset0 1 [-2147483648 : 2147483647] Digital counter 2 CompareDigCnt 2 Compare0 1[-2147483648 : 2147483647] Function permissionDigCnt 3 FunctionDISABLED NA Digital Counter 3 nameDigCnt 3 Name NA Digital counter 3 PresetDigCnt 3 Preset0 1 [-2147483648 : 2147483647] Digital counter 3 CompareDigCnt 3 Compare0 1 [-2147483648 : 2147483647] Function permissionDigCnt 4 FunctionDISABLED NA Digital Counter 4 nameDigCnt 4 Name NA Digital counter 4 PresetDigCnt 4 Preset0 1[-2147483648 : 2147483647] Digital counter 4 CompareDigCnt 4 Compare0 1 [-2147483648 : 2147483647] Function permissionDigCnt 5 FunctionDISABLED NA Digital Counter 5 nameDigCnt 5 Name NA Digital counter 5 PresetDigCnt 5 Preset0 1 [-2147483648 : 2147483647] Digital counter 5 CompareDigCnt 5 Compare0 1[-2147483648 : 2147483647] Function permissionDigCnt 6 FunctionDISABLED NA