APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-25 Digital Counter 6 nameDigCnt 6 Name NA Digital counter 6 PresetDigCnt 6 Preset0 1 [-2147483648 : 2147483647] Digital counter 6 CompareDigCnt 6 Compare0 1[-2147483648 : 2147483647] Function permissionDigCnt 7 FunctionDISABLED NA Digital Counter 7 nameDigCnt 7 Name NA Digital counter 7 PresetDigCnt 7 Preset0 1 [-2147483648 : 2147483647] Digital counter 7 CompareDigCnt 7 Compare0 1 [-2147483648 : 2147483647] Function permissionDigCnt 8 FunctionDISABLED NA Digital Counter 8 nameDigCnt 8 Name NA Digital counter 8 PresetDigCnt 8 Preset0 1[-2147483648 : 2147483647] Digital counter 8 CompareDigCnt 8 Compare0 1 [-2147483648 : 2147483647] Snapshot Event GenerationSnapshot EventsENABLED NA [ENABLED; DISABLED] SETPOINT > CONTROL ELEMENTS > COLD LOAD PICK UP SETTING DESCRIPTIONNAMEDEFAULT VALUESTEP RANGEUSER VALUE Function permsisionCold Load FunctionDISABLED NA[ENABLED; DISABLED] Cold Load Pickup Outage TimeCold Outage Time20 mi n[1 : 1000] Cold Load Pickup Blocking TimeCold Blocking Time5s[1 : 1000] Snapshot Event GenerationCold Load EventsENABLED NA[ENABLED; DISABLED] Setpoint > Inputs/Outputs > Contact I/O > Board F > Board G >board h>board j Setting DescriptionNameDefault ValueStepRangeUser Value I/O board type (available only for CIO mo dules) I/O Board Type_ XNONE N/A[NONE, 16 INP + 8OUT, 8 INP + 8OUT + SUPV 32 INP 16 INP + 8 ANA] Input activation voltage threshold Group A Voltage Threshold A_X80 1 V[10 : 230] Input activation voltage threshold Group BVoltage Threshold B _X801 V[10 : 230] Input activation voltage threshold Group C Voltage Threshold C_X80 1 V[10 : 230] Input activation voltage threshold Group D Voltage Threshold D_X80 1 V[10 : 230] Debounce time for Group A Debounce T ime A_X151 ms[1 : 50] Debounce time for Group B Debounce T ime B_X15 1 ms[1 : 50] Debounce time for Group C Debounce T ime C_X15 1 ms[1 : 50] Debounce time for Group D Debounce T ime D_X15 1 ms[1 : 50] Input type Input Type_X_C CY (CCY ) POSITIVE N/A[POSITIVE-EDGE, NEGATIVE-EDGE, POSITIVE, NEGATIVE] Input signal time delay Delay Input Ti me_ X_CC Y (CC Y) 0 1 ms[0 : 60000] Output logic type Output Logic_X_0 Z POSITIVE N/A[POSITIVE, NEGATIVE]
D-26F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.1 FACTORY DEFAULT SETTINGS APPENDIX D: Output typeOutput Type_X_0 Z NORMAL N/A[NORMAL, PULSE, LATCH] Output pulse length Pulse Output Ti me_ X_0 Z 10000 1 ms[0 : 60000] Analog Inputs Range Range_X_0 Z NONE N/A[NONE, -1 to 0mA, 0 to 1 mA, -1 to 1 mA, 0 to 5 mA, 0 to 10 mA] Minimum Value Min_Value_X_0 Z 0.00 0.01[ -9999.99 : 9999.99] Maximum Value Max_Value_X_0 Z 0.00 0.01[ -9999.99 : 9999.99] Snapshot event generation Snapshot EventsENABLEDN/A[DISABLED – ENABLED] Note 2: Description of X, Y and Z in input/output boards X F, G, H or J, the I/O board name, depending on the Relay model. F and G are internal Relay boards, and H and J are additional boards available in CIO m odules (remote Bus CAN I/O module) For the I/O board selection in the relay mo del: I/O BOARD TYPE ASSOCIATED DIGITENERVISTA 650 SETUP BOARD SETTINGSBOARD TYPE 0 NONENone 1 16 INP+ 8 OUT Mixed 28 INP +8 OUT +SUPVSupervision 4 32 INP32 digital inputs 5 16 INP + 8 ANA16 digital inputs + 8 analog inputs CC Y Is the name used for inputs in I/O boards Mixed, 16 d igital inputs: CC1….CC16 Supervision: 8 d igital inputs: CC1,..., CC8 32 INP: 32 digital inputs; CC1,...,CC32 0 Z Is the name used for the different outputs in I/O boards, 8 outputs available for any of the two t ypes of board (01,…., 08) Setpoint > inputs/outputs > remote comms Setting DescriptionNameDefault ValueStepRangeUser Value Remote comms selection Remote CommsNONEN/A[NONE – GSSE – GOOSE] SETTING DESCRIPTION FOR GSSE Remote comms selection Remote CommsGSSEN/A[NONE – GSSE – GOOSE] Device Identif ication 650 IDF650N/A Hold time signal send by the transmiting device Hold T ime 100001 ms[1000 : 60000] Snapshot Events Generation Snapshot Events Rem ote Out DISABLED N/A[DISABLED – ENABLED] Remote Device DescriptionRemote Device XRemote Device XN/A Bit Pair Selection Bit Pair XNoneN/A[DNA-1 to DNA-32 – UserS t-1 to UserSt-64] Default Value Selection Default Value XOFFN/A[OFF – ON – LATEST OFF – LA TEST ON] SETTING DESCRIPTION FOR GoOSE Remote comms selection Remote CommsGOOSEN/A[NONE – GSSE – GOOSE]
APPENDIX D: D.1 FACTORY DEFAULT SETTINGS GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-27 Default Value SelectionDefault Value XOFFN/A[OFF – ON – LATEST OFF – LA TEST ON] Note: X is the Remote Device index, up to 32 LIST OF TIME OVERCURRENT CURVES AVAILABLE IN F650 IEEE extremely/very/moderately inverse IEC Curve A/B/C/Long-T ime Inverse/ Short-T ime Inverse IAC extremely/very/normally/moderately inverse ANSI extremely/very/normally/moderately inverse I2t Def inite time Rectif ier curve User Curve - FlexCurve™ A/B/C/D
D-28F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.2 FACTORY DEFAULT CONFIGURATION APPENDIX D: D.2 Factory default conf iguration NOTE: SOURCE COLUMN: This columns allow selecting the simple or complex (OR signal or Virtual output) operand that actives the selected elements on relay configuration If more than one operands are selected, the relay performs an OR gate with them to activate the selected element. SIGNAL LOGIC COLUMN: Refers to each individual signal selected on its left. NOT legend means that the refered signal is inverted SOURCE LOGIC COLUMN: Refers to the whole SOURCE signal selected on its left. NOT legend means that SOURCE signal is inverted If more than one operand were selected, the OR gate output is inverted SETPOINT > RELAY CONFIGURATION > OUTPUTS OUTPUTSOURCESOURCE LOGICLOGIC CONT OP OPER_F_01 VO_000_PROTECTION_ALARM - CONT OP OPER_F_02 VO_046_59P_PKP - VO_045_27P_PKP - CONT OP OPER_F_03 VO_048_50G_PKP - CONT OP OPER_F_04 VO_049_51G_PKP - CONT OP OPER_F_05 VO_051_50PH_PKP - VO_050_50PL_PKP - CONT OP OPER_F_06 VO_053_51P_PKP - CONT OP OPER_F_07 OPERATION BIT 1 - AR CLOSE BREAKER - CONT OP OPER_F_08 OPERATION BIT 2 - VO_083_GENERAL_TRIP - SETPOINT > RELAY CONFIGURATION > LEDS LED SOURCESOURCE LOGICLOGICLED NAME LED01VO_000_PROTECTION ALARM-PROT ALARM LED02VO_083_GENERAL_TRIP-TRIP LED03VO_019_PHASE_OVERCURRENT_TRIP-50/51P TRIP LED04VO_069_GROUND_OVERCURRENT_TRIP-50/51G TRIP LED05VO_074_59P_TRIP--27/59 TRIPVO_073_27P_TRIP LED06VO_085_GENERAL_PKP-PICKUP LED07VO_007_PHASE_OVERCURRENT_PKP-50/51P PICKUP LED08VO_009_GROUND_OVERCURRENT_PKP-50/51G PICKUP LED09VO_045_27P_PKP-27 PICKUP LED10VO_046_59P_PKP-59 PICKUP LED11AR READY-79 READY LED12AR RCL IN PROGRESS-79 IN-PROG LED13AR BLOCK-79 BLOCK LED14AR CONDS INPUTNOT79 INHIBIT LED15AR LOCKOUT-79 LOCKOUT
APPENDIX D: D.2 FACTORY DEFAULT CONFIGURATION GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-29 SETPOINT > RELAY CONFIGURATION > PROTECTION ELEMENTS PROTECTION ELeMENTSOURCESIGNAL LOGICSOURCE LOGIC LED RESET INPUTOPERATION BIT 3 CHANGE LOCAL-REMOTENot Conf igured CHANGE OP BLOCKED Not Conf igured HMI BACKLIGHT ON Not Conf igured HMI BACKLIGHT OFF Not Conf igured PH IOC1 HIGH A BLK GROUP 1 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR1 A OP NOT LATCHED VIRT IP 1 PH IOC1 HIGH B BLK GROUP 1 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR1 B OP NOT LATCHED VIRT IP 1 PH IOC1 HIGH C BLK GROUP 1 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR1 C OP NOT LATCHED VIRT IP 1 PH IOC2 HIGH A BLK GROUP 2 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR2 A OP NOT LATCHED VIRT IP 1 PH IOC2 HIGH B BLK GROUP 2 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR2 B OP NOT LATCHED VIRT IP 1 PH IOC2 HIGH C BLK GROUP 2 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR2 C OP NOT LATCHED VIRT IP 1 PH IOC3 HIGH A BLK GROUP 3 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR3 A OP NOT LATCHED VIRT IP 1 PH IOC3 HIGH B BLK GROUP 3 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR3 B OP NOT LATCHED VIRT IP 1 PH IOC3 HIGH C BLK GROUP 3 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR3 C OP NOT LATCHED VIRT IP 1 PH IOC1 LOW A BLK GROUP 1 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR1 A OP NOT LATCHED VIRT IP 2
D-30F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.2 FACTORY DEFAULT CONFIGURATION APPENDIX D: PH IOC1 LOW B BLKGROUP 1 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR1 B OP NOT LATCHED VIRT IP 2 PH IOC1 LOW C BLK GROUP 1 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR1 C OP NOT LATCHED VIRT IP 2 PH IOC2 LOW A BLK GROUP 2 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR2 A OP NOT LATCHED VIRT IP 2 PH IOC2 LOW B BLK GROUP 2 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR2 B OP NOT LATCHED VIRT IP 2 PH IOC2 LOW C BLK GROUP 2 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR2 C OP NOT LATCHED VIRT IP 2 PH IOC3 LOW A BLK GROUP 3 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR3 A OP NOT LATCHED VIRT IP 2 PH IOC3 LOW B BLK GROUP 3 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR3 B OP NOT LATCHED VIRT IP 2 PH IOC3 LOW C BLK GROUP 3 BLOCKED CONT IP_F_CC2 (50P BLOCK)(CC2) PHASE DIR3 C OP NOT LATCHED VIRT IP 2 NEUTRAL IOC1 BLOCK GROUP 1 BLOCKED NEUTRAL DIR1 OP NOT NEUTRAL IOC2 BLOCK GROUP 2 BLOCKED NEUTRAL DIR2 OP NOT NEUTRAL IOC3 BLOCK GROUP 3 BLOCKED NEUTRAL DIR3 OPNOT GROUND IOC1 BLOCKGROUP 1 BLOCKED CONT IP_F_CC5 (50G BLOCK)(CC5) GROUND DIR1 OP NOT LATCHED VIRT IP 3 GROUND IOC2 BLOCK GROUP 2 BLOCKED CONT IP_F_CC5 (50G BLOCK)(CC5) GROUND DIR2 OP NOT LATCHED VIRT IP 3 SETPOINT > RELAY CONFIGURATION > PROTECTION ELEMENTS PROTECTION ELeMENTSOURCESIGNAL LOGICSOURCE LOGIC
APPENDIX D: D.2 FACTORY DEFAULT CONFIGURATION GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-31 GROUND IOC3 BLOCKGROUP 3 BLOCKED CONT IP_F_CC5 (50G BLOCK)(CC5) GROUND DIR3 OP NOT LATCHED VIRT IP 3 SENS GND IOC1 BLK GROUP 1 BLOCKED SENS GND DIR1 OP NOT LATCHED VIRT IP 4 SENS GND IOC2 BLK GROUP 2 BLOCKED SENS GND DIR2 OP NOT LATCHED VIRT IP 4 SENS GND IOC3 BLK GROUP 3 BLOCKED SENS GND DIR3 OP NOT LATCHED VIRT IP 4 PH TOC1 HIGH A BLK GROUP 1 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR1 A OP NOT LATCHED VIRT IP 5 PH TOC1 HIGH B BLK GROUP 1 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR1 B OP NOT LATCHED VIRT IP 5 PH TOC1 HIGH C BLK GROUP 1 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR1 C OP NOT LATCHED VIRT IP 5 PH TOC2 HIGH A BLK GROUP 2 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR2 A OP NOT LATCHED VIRT IP 5 PH TOC2 HIGH B BLK GROUP 2 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR2 B OP NOT LATCHED VIRT IP 5 PH TOC2 HIGH C BLKGROUP 2 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR2 C OP NOT LATCHED VIRT IP 5 PH TOC3 HIGH A BLK GROUP 3 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR3 A OP NOT LATCHED VIRT IP 5 PH TOC3 HIGH B BLK GROUP 3 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR3 B OP NOT LATCHED VIRT IP 5 SETPOINT > RELAY CONFIGURATION > PROTECTION ELEMENTS PROTECTION ELeMENTSOURCESIGNAL LOGICSOURCE LOGIC
D-32F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.2 FACTORY DEFAULT CONFIGURATION APPENDIX D: PH TOC3 HIGH C BLKGROUP 3 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR3 C OP NOT LATCHED VIRT IP 5 NEUTRAL TOC1 BLOCK GROUP 1 BLOCKED NEUTRAL DIR1 OP NOT NEUTRAL TOC2 BLOCK GROUP 2 BLOCKED NEUTRAL DIR2 OP NOT NEUTRAL TOC3 BLOCK GROUP 3 BLOCKED NEUTRAL DIR3 OP NOT GROUND TOC1 BLOCK GROUP 1 BLOCKED CONT IP_F_CC6 (51G BLOCK)(CC6) GROUND DIR1 OP NOT LATCHED VIRT IP 7 GROUND TOC2 BLOCK GROUP 2 BLOCKED CONT IP_F_CC6 (51G BLOCK)(CC6) GROUND DIR2 OP NOT LATCHED VIRT IP 7 GROUND TOC3 BLOCK GROUP 3 BLOCKED CONT IP_F_CC6 (51G BLOCK)(CC6) GROUND DIR3 OP NOT LATCHED VIRT IP 7 SENS GND TOC1 BLOCK GROUP 1 BLOCKED SENS GND DIR1 OP NOT LATCHED VIRT IP 8 SENS GND TOC2 BLOCK GROUP 2 BLOCKED SENS GND DIR2 OP NOT LATCHED VIRT IP 8 SENS GND TOC3 BLOCK GROUP 3 BLOCKED SENS GND DIR3 OPNOT LATCHED VIRT IP 8 PHASE UV1 BLOCK GROUP 1 BLOCKED PHASE UV2 BLOCK GROUP 2 BLOCKED PHASE UV3 BLOCK GROUP 3 BLOCKED NEG SEQ OV1 BLOCK GROUP 1 BLOCKED NEG SEQ OV2 BLOCK GROUP 2 BLOCKED NEG SEQ OV3 BLOCK GROUP 3 BLOCKED THERMAL1 BLOCK GROUP 1 BLOCKED THERMAL2 BLOCK GROUP 2 BLOCKED THERMAL3 BLOCK GROUP 3 BLOCKED PHASE DIR1 BLK INP GROUP 1 BLOCKED CONT IP_F_CC4 (67P BLOCK)(CC4) LATCHED VIRT IP 9 PHASE DIR2 BLK INP GROUP 2 BLOCKED CONT IP_F_CC4 (67P BLOCK)(CC4) LATCHED VIRT IP 9 SETPOINT > RELAY CONFIGURATION > PROTECTION ELEMENTS PROTECTION ELeMENTSOURCESIGNAL LOGICSOURCE LOGIC
APPENDIX D: D.2 FACTORY DEFAULT CONFIGURATION GEK-113000-AFF650 DIGITAL BAY CONTROLLER d-33 PHASE DIR3 BLK INPGROUP 3 BLOCKED CONT IP_F_CC4 (67P BLOCK)(CC4) LATCHED VIRT IP 9 NEUTRAL DIR1 BLK INP GROUP 1 BLOCKED NEUTRAL DIR2 BLK INP GROUP 2 BLOCKED NEUTRAL DIR3 BLK INP GROUP 3 BLOCKED GROUND DIR1 BLK INP GROUP 1 BLOCKED LATCHED VIRT IP 10 GROUND DIR2 BLK INP GROUP 2 BLOCKED LATCHED VIRT IP 10 GROUND DIR3 BLK INP GROUP 3 BLOCKED LATCHED VIRT IP 10 NEUTRAL OV1 HIGH BLK GROUP 1 BLOCKED LATCHED VIRT IP 12 NEUTRAL OV2 HIGH BLK GROUP 2 BLOCKED LATCHED VIRT IP 12 NEUTRAL OV3 HIGH BLK GROUP 3 BLOCKED LATCHED VIRT IP 12 NEUTRAL OV1 LOW BLK GROUP 1 BLOCKED NEUTRAL OV2 LOW BLK GROUP 2 BLOCKED NEUTRAL OV3 LOW BLK GROUP 3 BLOCKED AUXILIARY UV1 BLOCK GROUP 1 BLOCKED AUXILIARY UV2 BLOCK GROUP 2 BLOCKED AUXILIARY UV3 BLOCKGROUP 3 BLOCKED PHASE OV1 BLOCKGROUP 1 BLOCKEDLATCHED VIRT IP 11 PHASE OV2 BLOCK GROUP 2 BLOCKED LATCHED VIRT IP 11 PHASE OV3 BLOCK GROUP 3 BLOCKED LATCHED VIRT IP 11 AUXILIARY OV1 BLOCK GROUP 1 BLOCKED AUXILIARY OV2 BLOCK GROUP 2 BLOCKED AUXILIARY OV3 BLOCK GROUP 3 BLOCKED NEG SEQ TOC1 BLOCK GROUP 1 BLOCKED NEG SEQ TOC2 BLOCK GROUP 2 BLOCKED NEG SEQ TOC3 BLOCK GROUP 3 BLOCKED OVERFREQ1 BLOCK GROUP 1 BLOCKED OVERFREQ2 BLOCK GROUP 2 BLOCKED OVERFREQ3 BLOCK GROUP 3 BLOCKED UNDERFREQ1 BLOCK GROUP 1 BLOCKED UNDERFREQ2 BLOCK GROUP 2 BLOCKED UNDERFREQ3 BLOCK GROUP 3 BLOCKED SETT GROUPS BLOCK Not Conf igured BROKEN CONDUCT1 BLK GROUP 1 BLOCKED BROKEN CONDUCT2 BLK GROUP 2 BLOCKED BROKEN CONDUCT3 BLK GROUP 3 BLOCKED ISOLATED GND1 BLK GROUP 1 BLOCKED SENS GND DIR1 OP NOT SETPOINT > RELAY CONFIGURATION > PROTECTION ELEMENTS PROTECTION ELeMENTSOURCESIGNAL LOGICSOURCE LOGIC
D-34F650 DIGITAL BAY CONTROLLER GEK-113000-AF D.2 FACTORY DEFAULT CONFIGURATION APPENDIX D: ISOLATED GND2 BLKGROUP 2 BLOCKED SENS GND DIR2 OP NOT ISOLATED GND3 BLK GROUP 3 BLOCKED SENS GND DIR3 OP NOT SENS GND DIR1 BLK IP GROUP 1 BLOCKED SENS GND DIR2 BLK IP GROUP 2 BLOCKED SENS GND DIR3 BLK IP GROUP 3 BLOCKED FWD PWR1 BLOCK GROUP 1 BLOCKED FWD PWR2 BLOCK GROUP 2 BLOCKED FWD PWR3 BLOCK GROUP 3 BLOCKED PH TOC1 LOW A BLK GROUP 1 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR1 A OP NOT LATCHED VIRT IP 6 PH TOC1 LOW B BLK GROUP 1 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR1 B OPNOT LATCHED VIRT IP 6 PH TOC1 LOW C BLK GROUP 1 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR1 C OP NOT LATCHED VIRT IP 6 PH TOC2 LOW A BLK GROUP 2 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR2 A OP NOT LATCHED VIRT IP 6 PH TOC2 LOW B BLK GROUP 2 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR2 B OP NOT LATCHED VIRT IP 6 PH TOC2 LOW C BLK GROUP 2 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR2 C OP NOT LATCHED VIRT IP 6 PH TOC3 LOW A BLK GROUP 3 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR3 A OP NOT LATCHED VIRT IP 6 PH TOC3 LOW B BLK GROUP 3 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR3 B OP NOT LATCHED VIRT IP 6 PH TOC3 LOW C BLK GROUP 3 BLOCKED CONT IP_F_CC3 (51P BLOCK)(CC3) PHASE DIR3 C OP NOT LATCHED VIRT IP 6 DIR PWR1 BLOCK GROUP 1 BLOCKED DIR PWR2 BLOCK GROUP 2 BLOCKED SETPOINT > RELAY CONFIGURATION > PROTECTION ELEMENTS PROTECTION ELeMENTSOURCESIGNAL LOGICSOURCE LOGIC