CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-3 5.1.1 Communication parameters 1.Ethernet Connection/Type - Both boot code and f irmware upgrade processes require Ethernet communications. It is strongly recommended to use a direct connection between the PC and the relay using a Cross-Over RJ45 Ethernet cable, instead a direct connection through a hub or switch. Upgrading through Local Area Network (LAN) must be avoided. Serial RS232 Communication - Serial communication is necessary only to perform the bootware upgrade for versions previous to 7.00. 2.Relay IP Address - An IP address must be assigned to the relay in the Ethernet parameters via HMI at Product Setup > Communication > Ethernet > Ethernet1 menu, or via Enervista 650 Setup software at Setpoint > Product Setup > Communication Settings > Network (Ethernet) 1 a s shown in the table below: Table 5-1: Ethernet parameters 3. PC IP Address - In case the boot code has been previously updated to the relay (section 9.2), the IP address and other parameters already assigned in the process are: IP Address:192.168.37.177 Netmask:255.255.255.0 Gateway:192.168.37.10 Then the PC settings should be the same pattern as follows: IP Address:192.168.37.xxx Netmask:255.255.255.0 Gateway:192.168.37.10 (if desired) Where XXX is a number between 0 and 255 that is not assigned to any other device to avoid collisions. 4.Other Network, Communications and Data Flow checks • According to the model number of the relay, to enable th e 10 /100 BASE TX-CABLE option in the relay communication board, a specif ic jumper in this board must be changed. See detailed instructions in paragraph 3.4.3 of Instruction Manual GEK-106310AE. • IP address, netmask, gateway are correct and match the para met ers used in the computer to perform the procedure. See table 9.1 (on this chapter) of Manual GEK-106310AE COMMUNICATION PARAMETERS. Product Setup > Communication Settings > Network (Ethernet) 1 NameValueUnitsRange IP Address Oct1 192 [0 : 255] IP Address Oct2 168 [0 : 255] IP Address Oct3 37 [0 : 255] IP Address Oct4 177 [0 : 255] Netmask Oct1 255 [0 : 255] Netmask Oct2 255 [0 : 255] Netmask Oct3 255 [0 : 255] Netmask Oct4 0 [0 : 255] Ga t e w a y I P O c t 1 192 [0 : 255] Ga t e w a y I P O c t 2 168 [0 : 255] Ga t e w a y I P O c t 3 37 [0 : 255] Ga t e w a y I P O c t 4 10 [0 : 255]
5-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE 5.1.2 Bootware version upgrade Boot code upgrade is performed using En erVista 650 Setup, and the most recent version of Enervista 650 setup software should be used. It is required that no active communication is currently established between the program and the relay, and that no configuration files are open. During the boot code upgrading process, all the data stored in the relay is lost. Save all calibration, settings, oscillography, etc. from the relay before starting the upgrade. 5.1.2.1 Bootware upgrade 1. Windows XP, Windows 7 and Windows 8 Operating Systems must be used for installation and the reliable operation of Enervista 650 Setup program and bootware/firmware relay upgrade. 2. To upgrade the boot code, it is required to connect an RS232 cable to the front of the relay, and an Ethernet cable to the rear port (ETH_1/ETH_2 or ETH_E/ETH_A/ETH_B). 3. If it is being used a USB-to-Serial RS232 Cable Converter, it must be a RS-232C standard compliant , powered by the User computers USB bus and with DB9 male connector. To ensure the correct state of communication between the computer and the relay along the whole upgrading process, all other USB devices must be unplugged. Due to the extended variety of USB-to-Serial Cable Converters existing nowadays in the market , with different characteristics, even different charge imposed to the USB bus of the PC, it is strongly recommended to use the GE USB-to-Serial RS232 Cable Converter, part number GE0100-0001. 4. When using USB-to-Serial RS232 cable it is necessar y f irst to determine the COM Port number the Laptop uses through the USB device. Depending in the actual F650 upgr ade task under operation, the procedure is as follows: 4.1 Firmware upgrade: It is not necessary to use a serial cable 4.2 Bootware and firmware upgrade being the relay fully operative with the actual F/W version: The COM port number must be determined by using the 650 Setup program. With USB device disconnected from the Laptop and from the relay, start the 650 Setup program. At the top menu bar choose Communication > Computer > Communication Port menu and check the allowable serial ports displayed.Retu rn to the main 650 Setup screen and connect the USB device to PC and select Communication > Computer > Communication Port to display the allowed serial ports. The new one port number shown is the USB port number to be used for the upgrade process. 4.3 Bootware and firmware upgrade being the relay blocked at startup (no preliminary communication PC-Relay allowable): Repeat the process described above in 4.2 to determine the COM PORT number and continue with upgrade process. 5. Once the COM PORT number is determined, set it in Communication > Computer together with and the Baud Rate and Parity parameters. Click Store. 6. Start the Enervista F650 Setup program and select Communication > Upgrade R elay. Figure 5-1: Upgrade device
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-5 7. Select Device Boot Upgrade. FW version
5-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE Figure 5-4: Warning message to save setting and conf iguration f iles 10. Parameters already set in step 5 are operative during seri al comm unications. If they have not been previously set a pop up window prompts for the serial COM port to be used during upgrading. 11. During the upgrade, the system shows the following message indicating the procedure to be followed. If you click Yes, the next window allows you to choose the Network adapter for your Ethernet connection to the relay.
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-7 12. After selecting the Network adapter, a window to choose a temporary IP address is shown. It is advisable to set the same IP address that is going to be used later in the relay for Ethernet connection. Figure 5-5: setting address 13. After entering the temporary IP Address, the next new window r equires the bootware f ile retrieved from http://www.gegridsolutions.com/index.htm and previously stored someplace in the PC.
5-8F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE Figure 5-6: Boot code f ile selection 14. Choose the bootware f ile and click Open butt on. Figure 5-7: Loading boot code f ile 15. Then the program shows a message requiring switch OFF and ON the relay while the progress bar is in course, to start t he upgrading process. Figure 5-8: Relay switch off-on message
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-9 16. It is important to switch the Relay OFF and ON again during the time shown by the progress bar; in case this time expires, the program offers the option to continue wi th the process or to postpone, verify the correct RS232 connections and try again later. Notice that the serial COM PORT used in the boot upgrade procedure is the one selected in step 4 above. Figure 5-9: loading update f ile error message If the relay gets stuck during the upgrading process after swit ching OFF and ON the relay, giving error message shown, it is due to no serial communication via the front RS232 port. Check the serial cable and serial settings connection. At this point the relay will not be upgraded. After switching it OFF and ON it will continue working with the former firmware and bootware versions. 17. After switching the relay OFF and ON, if the serial communication between EnerVista 650 Setup and the relay is correct the program shows the following message: Then it requires the confirmation to proceed to upgrade:
5-10F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE 18. Click Yes to start the process, beginning with the relay flash memory deletion. At this point all the information stored in the relay is lost. Until now, no important change has been made to the relay, the boot memory upgrading process has just been prepared. This process can take several minutes, du ring which a progress bar is displayed. 19. If the process is successful, continue to step 20. If the process is unsuccessful and the relay gets stuck at “Sending file imagen_kernel…” (see figure below) This error may be due to no communication via the Ethernet port. At this point serial communications work properly, the relay flash memory has been erased, and the upgrade procedure must be completed to start working with the unit. If the procedure is not completed, the HMI shows the message OS Loading... and the relay does not start up. In this case refer to step 4 above If all points from step 4 are correct but the problem persists: Disable and Enable the Ethernet connection while the files are bein g sent (during the “Sending file...” message - previous figure). To do this, in Windows OS go to Startup > Control Panel > Network Connection > Local Network, right-click and select Disable. Now the Local Network status Icon is shown as Disabled. In the same screen right-click Local Network, select Enable, and wait until Enabled status is shown. 20. Once the memory has been erased and the f iles upgraded in the relay, the parameters for the Ethernet communications must be set . The requested values are the IP address and the gateway.
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-11 Figure 5-10: IP address setpoint window These values should match the LAN structure where the relay will be connected. The relay IP address should have the first three octets corresponding with the gateway and the last octet must be a free IP address reserved to the relay to avoid possible collisions with other devices. The gateway must be the one used in the LAN structure connecting the relay 21. After assigning the Ethernet parameters, the upgrade of the boot code is complete and successful. 22. A window is displayed with the message: Settin g Default IP address, followed by: Figure 5-11: BOOTware upgrade successful process After boot code upgrade, the equipment firmware must also be upgraded.
5-12F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE 5.1.3 Firmware version upgrade 5.1.3.1 Introduction 1. Save relay settings and conf iguration to a f ile before proceeding, as they will be lost during upgrade. 2. Save calibration settings to a f ile for f irmware revisions lower than 1.50, before upgrading the F650 to a new f irmware version. 3. For f irmware revision higher than 1.50 when only upgrading the f irmware (no bootware upgrade), the calibration f iles ar e not modif ied and do not need to be saved. 4. Special care should be taken when the boot code has been previously upgraded: all data (including calibration set tings) is lost . 5. In case of errors during the f irmware upgrade process, repeat the entire process as many times as necessary. This is possib le thanks to an independent boot memory (bootcode). 6. A pure firmware upgrade process should use the EnerVist a 650 Setup software and Ethernet connection (Port ETH_1 or ETH2) via a Cross-Over RJ45 Ethernet cable. Note: Downgrading firmware versions can cause errors in measurements. 5.1.3.2 Firmware upgrade 1. Once communication with the relay through the Ethernet connection has been verif ied, enter the EnerVista 650 Setup program and select Communication > Upgrade Relay . Figure 5-1: Upgrade device 2. Select Device FW Upgrade FW v ersion