Trane Intellipak 2 Service Manual
Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Installation RT-SVX24K-EN81 Power Wire Sizing and Protection Devices To correctly size electrical service wiring for a unit, find the appropriate calculations listed below. Each type of unit has its own set of calculations for MCA (Minimum Circuit Ampacity), MOP (Maximum Overcurrent Protection), and RDE (Recommended Dual Element fuse size). Read the load definitions that follow and then find the appropriate set of calculations based on unit type. Note: Set 1 is for cooling only and cooling with gas heat units, and set 2 is for cooling with electric heat units. Load Definitions: (To determine load values, see the Electrical Service Sizing Data Tables on the following page.) LOAD1 = CURRENT OF THE LARGEST MOTOR (COMPRESSOR OR FAN MOTOR) LOAD2 = SUM OF THE CURRENTS OF ALL REMAINING MOTORS LOAD3 = CURRENT OF ELECTRIC HEATERS LOAD4 = ANY OTHER LOAD RATED AT 1 AMP OR MORE Set 1. Cooling Only Rooftop Units and Cooling with Gas Heat Rooftop Units MCA = (1.25 x LOAD1) + LOAD2 + LOAD4 MOP = (2.25 x LOAD1) + LOAD2 + LOAD4 Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size as listed in NEC 240-6, select the next lower standard fuse rating. Note: If selected MOP is less than the MCA, then select the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the selected fuse size does not exceed 800 amps. RDE=(1.5xLOAD1)+LOAD2+LOAD4 Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240-6, select the next higher standard fuse rating. Note: If the selected RDE is greater than the selected MOP value, then select the RDE value to equal the MOP value. Set 2. Rooftop units with Electric Heat To arrive at the correct MCA, MOP, and RDE values for these units, two sets of calculations must be performed. First calculate the MCA, MOP, and RDE values as if the unit was in cooling mode (use the equations given in Set 1). Then calculate the MCA, MOP, and RDE values as if the unit were in the heating mode as follows. (Keep in mind when determining LOADS that the compressors dont run while the unit is in the heating mode). MCA = 1.25 x (LOAD1 + LOAD2 + LOAD4) + LOAD3 The nameplate MCA value will be the larger of the cooling mode MCA value or the heating mode MCA value calculated above. MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4 The selection MOP value will be the larger of the cooling mode MOP value or the heating mode MOP value calculated above. Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size as listed in NEC 240-6, select the next lower standard fuse rating. Note: If selected MOP is less than the MCA, then select the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the selected fuse size does not exceed 800 amps. RDE=(1.5xLOAD1)+LOAD2+LOAD3+LOAD4 The selection RDE value will be the larger of the cooling mode RDE value or the heating mode RDE value calculated above. Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240-6, select the next higher standard fuse rating. Notes: If the selected RDE is greater than the selected MOP value, then select the RDE value to equal the MOP value. On 90 to 162 ton rooftops, the selected MOP value is stamped in the MOP field on the nameplate. Table 22. Electrical service sizing data Nom Tons Compressor Nominal Voltage 460 V 575 V 380 V Size Number per Unit Capacity kW (ea.) RLA (ea.) LRA (ea.) RLA (ea.) LRA (ea.) RLA (ea.) LRA (ea.) 60 Hz 50 Hz Std. Coil High Cap Std. CoilHigh Cap 90/100 240 4 21.3 21.6 17.6 17.9 34.1 215 27.3 175 34.0 215 105/118 240 2 24.2 24.5 20.2 20.3 34.1 215 27.3 175 34.0 215 300 2 25.0 25.3 20.9 21.0 44.7 260 35.8 210 44.6 260 120/128 300 4 26.9 27.8 22.4 23.0 44.7 260 35.8 210 44.6 260 130/140 300 2 28.5 28.8 23.8 23.8 44.7 260 35.8 210 44.6 260 380 2 33.7 34.2 28.2 28.2 52.1 320 41.1 235 52.0 320 150/162 380 4 34.7 -- 28.7 -- 52.1 320 41.1 235 52.0 320
Installation 82RT-SVX24K-EN Table 23. Electrical service sizing data—motors Condenser Fan Motors Nominal Tons No. of Fans 460 V 575 V 380 V FLA FLA FLA 90, 105 6 16.2 13.2 15 120, 130, 150 8 21.6 17.6 20 100 2 11.8 N/A N/A 118, 128, 140, 162 2 11.8 N/A N/A Supply Fan Motors Motor Horsepow er 460 V 575 V 380 V FLA FLA FLA 15 18.5 15.1 24 20 24.7 19.6 29 25 3124.5 38 30 36.6 29.2 47 40 49.0 3954 50 60.5 4868 60 71.5 57.2 81 75 9072103 100 115 92N/A Exhaust/Return Fan Motors Motor Horsepow er 460 V 575 V 380 V FLA FLA FLA 7.5 9.47.8 13.6 10 12.6 10.1 16 15 18.5 15.1 24 20 24.7 19.6 29 25 3124.5 38 30 36.6 29.2 47 40 49.0 3954 50 60.5 4868 60 71.5 57.2 81 Table 24. Electrical service sizing data—electric heat module (electric heat units only) Voltage 460 575 380 Module kW FLA FLA FLA 90 / 56 108.386.685.1 140 / 88 168.4134.7133.7 265 / 166 318.8255252.2 300 / 188 360.8288.7285.6 Table 25. Electrical service sizing data—control power transformer (heating mode only) Nominal Tons Digit 2 Unit Function Voltages 460 575 380 FLA FLA FLA 90-150/100-162 E, L, S, X 3 3 4 90, 105/100, 118 F (850 MBH) 4 4 5 90, 105/100, 118 F (1100 MBH) 4 4 5 90, 105/100, 118 F (1800 MBH) 4 4 5 120-150/128-162 F (1100 MBH) 4 4 5 120-150/128-162 F (1800 MBH) 4 4 5 120-150/128-162 F (2500 MBH) 4 4 5 Table 26. Electrical service sizing data—crankcase heater Nominal Tons Voltage 460 575 380 FLA (add) FLA (add) FLA (add) 90-162 11 1 Table 27. Voltage utilization range Unit Voltage 460/60/3 414-506 575/60/3 (a) (a) Units with air-cooled condensers only. 517-633 380/50/3 (i)342-418 Table 28. Electrical service sizing data—evaporative condenser Unit Part kwHPVoltage 460FLA Pump 1.5 2.7 Sump Heater3 3.8 Table 29. Electrical service sizing data—energy recovery wheel motor Nominal Tons Unit Function Voltages 460 575 FLA FLA 90-128 1 (Low CFM ERW) 1.2 0.95 130-162 1 (Low CFM ERW) 1.7 1.4 90-162 2 (Std. CFM ERW) 1.7 1.4
Installation RT-SVX24K-EN83 Field Installed Control Wiring The Rooftop Module (RTM) must have a mode input in order to operate the rooftop unit. The flexibility of having several system modes depends upon the type of sensor and/or remote panel selected to interface with the RTM. An overall layout of the various control options available, with the required number of conductors for each device, is illustrated beginning with Figure 57, p. 89. Note: All field wiring must conform to NEC guidelines as well as state and local codes. The various field installed control panels, sensors, switches, and contacts discussed in this section require both AC and DC consideration. These diagrams are representative of standard applications and are provided for general reference only. Always refer to the wiring diagram that shipped with the unit for specific electrical schematic and connection information. Controls using 24 VAC Before installing any connecting wiring, refer to Figure 10, p. 23 for the electrical access locations provided on the unit and Table 32, p. 83 for AC conductor sizing guidelines, and; a. Use copper conductors unless otherwise specified. b. Ensure that the AC control wiring between thecontrols and the units termination point does not exceed three (3) ohms/conductor for the length of the run. Note: Resistance in excess of 3 ohms per conductor may cause component failure due to insufficient AC voltage supply. c. Be sure to check all loads and conductors for grounds, shorts, and miswiring. d. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring. Controls using DC Analog Input/Outputs Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to the appropriate illustration in Figure 10, p. 23for the electrical access locations provided on the unit and Table 33, p. 83 for conductor sizing guidelines and; e. Use standard copper conductor thermostat wire unless otherwise specified. f. Ensure that the wiring between the controls and the unit termination point does not exceed two and a half (2.5) ohms/conductor for the length of the run. Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the controls. g. Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires. Units equipped with a Trane BACnet® Communication Interface (BCI) or LonTalk® communication Interface (LCI) option which utilizes a serial communication link; a. Must be 18 AWG shielded twisted pair cable(Belden 8760 or equivalent). b. Must not exceed 5,000 feet maximum for each link. Table 30. Electrical service sizing data—convenience outlet transformer Nominal Tons Voltage 460 575 FLA (add) FLA (add) 90-162 3.32.6 Table 31. Compressor data Unit Size Number of Compress ors Compress or Size Compress or Designat or Compress or Type 90/100 Ton Std & Hi-Capacity 2 CSHN250 1A, 2A Scroll 2 CSHN250 1B, 2B Scroll 105/118 Ton Std & Hi-Capacity 2 CSHN250 1A, 2A Scroll 2 CSHN315 1B, 2B Scroll 120/128 Ton Std & Hi-Capacity 2 CSHN315 1A, 2A Scroll 2 CSHN315 1B, 2B Scroll 130/140 Ton Std & Hi-Capacity 2 CSHN315 1A, 2A Scroll 2 CSHN374 1B, 2B Scroll 150/162 Ton Std 2 CSHN374 1A, 2A Scroll 2 CSHN374 1B, 2B Scroll WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. Table 32. AC conductors Distance from Unit to Control Recommended Wire Size 000-460 feet 18 gauge 461-732 feet 16 gauge 733-1000 feet 14 gauge Table 33. DC conductors Distance from Unit to Control Recommended Wire Size 000-150 feet22 gauge 151- 240 feet 20 gauge 241- 385 feet 18 gauge 386- 610 feet 16 gauge 611- 970 feet 14 gauge
Installation 84RT-SVX24K-EN c. Must not pass between buildings. Constant Volume System Controls Remote Panel w/o NSB—BAYSENS110* This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto) with four system status LEDs. It is a manual or automatic changeover control with dual setpoint capability. It can be used with a remote zone sensor BAYSENS077*. Refer to Table 34, p. 87for the Temperature vs. Resistance coefficient. Constant Volume Zone Panel -BAYSENS108* This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or automatic changeover control with dual setpoint capability. Variable Air Volume System Controls VAV Changeover Contacts The changeover input is used with modulating gas heat, electric heat, or hydronic heat. When the contacts are closed, the unit will control to the discharge heating setpoint. Refer to the unit wiring diagram for the field connection terminals in the unit control panel. The switch must be rated at 12 ma @ 24 VDC minimum. Constant Volume or Variable Air Volume System Controls Remote Human Interface Module The remote Human Interface module enables the operatorto set or modify the operating parameters of the unit using a 16 key keypad and to view the operating status of the unit on the 2 line, 40 character LCD screen without leaving the building. However, the Remote Human Interface module can not be used to perform any service functions. One remote panel is designed to monitor and control up to four units providing each of the units are equipped with an IPCB module. Use the installation instructions that shipped with the module to install it, and the appropriate illustrations beginning with Figure 57, p. 89to connect it to the unit. Remote Panel w/ NSB -BAYSENS119* This 7 day programmable sensor features four periods for Occupied\Unoccupied programming per day. Either one or all four periods can be programmed. If the power is interrupted, the program is retained in permanent memory. If power is off longer than 2 hours, only the clock and day may have to be reset. The front panel allows selection of Occupied/Unoccupied periods with two temperature inputs (Cooling Supply Air Temperature and Heating Warm-up temperature) per occupied period. The occupied cooling setpoint ranges between 40 and 80°F. The warm-up setpoint ranges between 50 and 90°F with a 2 degree deadband. The Unoccupied cooling setpoint ranges between 45 and 98°F.The heating setpoint ranges between 43 and 96°F. The liquid crystal display (LCD) displays zone temperature, temperature setpoints, week day, time, and operational mode symbols.The DIP switches on the subbase are used to enable or disable applicable functions, i.e.; Morning warm-up, economizer minimum position override during unoccupied status, heat installed, remote zone temperature sensor, 12/24 hour time display, and daytime warm-up. Refer to Table 34, p. 87for the Temperature vs. Resistance coefficient. During an occupied period, an auxiliary relay rated for 1.25 amps @ 30 volts AC with one set of single pole double throw contacts is activated. Remote Zone Sensor (BAYSENS073*) This electronic analog sensor features remote zone sensing and timed override with override cancellation. It is used when the RTM has been programmed as the source for zone temperature control. Refer to Table 34, p. 87for the Temperature vs. Resistance coefficient. Remote Zone Sensor (BAYSENS074*) This electronic analog sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated Comfort TMsystem. Refer to Table 34, p. 87 for the Temperature vs. Resistance coefficient. Remote Zone Sensor (BAYSENS016*) This bullet type analog Temperature sensor can be used for; outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, remote temperature sensing (uncovered), morning warm-up temperature sensing, and for VAV zone reset. Wiring procedures vary according to the particular application and equipment involved. When this sensor is wired to a BAYSENS119* Remote Panel, wiring must be 18 AWG ShieldedTwisted Pair (Belden 8760 or equivalent). Refer to Table 34, p. 87 for the Temperature vs. Resistance coefficient. Remote Zone Sensor (BAYSENS077*) This electronic analog sensor can be used with BAYSENS119* or 021* Remote Panels. When this sensor is wired to a BAYSENS119* Remote Panel, wiring must be 18 AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details. CO2Sensing—Space or Duct The CO2sensor shall have the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2in the air. As the CO2levels increase, the outside air damper modulates to meet the CO 2space ventilation requirements.
Installation RT-SVX24K-EN85 Remote Minimum Position Potentiometer (BAYSTAT023*) The remote minimum position potentiometer is used on units with an economizer. It allows the operator to remotely set the economizer minimum position (which controls the amount of outside air entering the unit). Use the installation instructions that shipped with the potentiometer to install it, and the appropriate illustrations beginning with Figure 57, p. 89to connect it to the unit. Single Zone Variable Air Volume & Rapid Restart System Control Remote Zone Sensor (BAYSENS016*) This bullet-type, analog temperature sensor can be used for supply air and return air temperature sensing. Wiring procedures vary according to application and equipment. When this sensor is wired to a BAYSENS119* Remote Panel, wiring must be 18 AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to Table 34, p. 87for the Temperature vs. Resistance coefficient. External Auto/Stop Switch A field supplied single pole single throw switch may be used to shut down the unit operation. This switch is a binary input wired to the RTM. When opened, the unit shuts down immediately and can be cancelled by closing the switch. Refer to the appropriate illustrations beginning with Figure 57, p. 89 for the proper connection terminals in the unit control panel. The switch must be rated for 12 ma @ 24 VDC minimum. Emergency Override When a Lontalk®/BACnet® communication module is installed, the user can initiate from the Trane Tracer Summit or 3rd party BAS one of five (5) predefined, not available to configure, Emergency Override sequences. All compressors, condenser fans and the Humidification output are deenergized for any Emergency Override sequence. Each Emergency Override sequence commands the unit operation as follows: 1. PRESSURIZE_EMERG: – Supply Fan - On – Supply Fan VFD Open/Max (if so equipped) – Exhaust Fan - Off; Exhaust Dampers Closed (if soequipped) – OA Dampers - Open; Return Damper - Closed – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Energized – VOM Relay - Energized (if so equipped) – Preheat Output - Off – Return Fan - Off; Exhaust Dampers - Closed (if so equipped) – Return VFD - Min (if so equipped) 2. EMERG_DEPRESSURIZE: – Supply Fan - Off – Supply Fan VFD - Closed/Min (if so equipped) – Exhaust Fan - On; Exhaust Dampers Open/Max (if so equipped) – OA Dampers - Closed; Return Damper - Open – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Energized – VOM Relay - Energized (if so equipped) – Preheat Output - Off – Return Fan - On; Exhaust Dampers - Open (if so equipped) – Return VFD - Max (if so equipped) 3. EMERG_PURGE: – Supply Fan - On – Supply Fan VFD - Open/Max (if so equipped) – Exhaust Fan - On; Exhaust Dampers Open (if so equipped) – OA Dampers - Open; Return Damper - Closed – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Energized – VOM Relay - Energized (if so equipped) – Preheat Output - Off – Return Fan - On; Exhaust Dampers - Open (if so equipped) – Return VFD - Max (if so equipped) 4. EMERG_SHUTDOWN: – Supply Fan - Off – Supply Fan VFD - Closed/Min (if so equipped) – Exhaust Fan - Off; Exhaust Dampers Closed (if so equipped) – OA Dampers - Closed; Return Damper - Open – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Energized – VOM Relay - Energized (if so equipped) – Preheat Output - Off – Return Fan - Off; Exhaust Dampers - Closed (if so equipped) – Return VFD - Min (if so equipped) 5. EMERG_FIRE - Input from fire pull box/system: – Supply Fan - Off – Supply Fan VFD - Closed/Min (if so equipped) – Exhaust Fan - Off; Exhaust Dampers Closed (if so equipped)
Installation 86RT-SVX24K-EN – OA Dampers - Closed; Return Damper - Open – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Energized – VOM Relay - Energized (if so equipped) – Preheat Output - Off – Return Fan - Off; Exhaust Dampers - Closed (if so equipped) – Return VFD - Min (if so equipped) Ventilation Override Module (VOM) Important: The ventilation override system should not be used to signal the presence of smoke caused by a fire, as it is not intended nor designed to do so. The user can customize up to five (5) different override sequences for purposes of ventilation override control. If more than one VOM sequence is being requested, the sequence with the highest priority is initiated first. Sequence hierarchy is the sequence “A” (UNIT OFF) is first, with sequence “E” (PURGE with Duct Pressure Control) last. A ventilation override mode can be initiated by closing any of the five (5) corresponding binary inputs on the VOM module. A binary output is provided on the VOM module to provide remote indication of an active VOM mode. All compressors, condenser fans and the Humidification output are deenergized for any VOM sequence. The factory default definitions for each mode are as follows: 1. UNIT OFF sequence “A” When complete system shutdown is required the following sequence can be used. – Supply Fan - Off – Supply Fan VFD - Closed/Min (if so equipped) – Exhaust Fan - Off; Exhaust Dampers Closed (if soequipped) – OA Dampers - Closed; Return Damper - Open – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Deenergized – VOM Relay - Energized – Preheat Output - Off – Return Fan - Off; Exhaust Dampers - Closed (if so equipped) – Return VFD - Min (if so equipped) – OA Bypass Dampers - Open (if so equipped) – Exhaust Bypass Dampers - Open (if so equipped) 2. PRESSURIZE sequence “B” Perhaps a positively pressurized space is desired instead of a negatively pressurized space. In this case, the supply fan should be turned on with VFD at 100% speed and exhaust fan should be turned off. – Supply Fan - On – Supply Fan VFD - Max (if so equipped) – Exhaust Fan - Off; Exhaust Dampers Closed (if soequipped) – OA Dampers - Open; Return Damper - Closed – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Energized – VOM Relay - Energized – Preheat Output - Off – Return Fan - Off; Exhaust Dampers - Closed (if so equipped) – Return VFD - Min (if so equipped) – OA Bypass Dampers - Open (if so equipped) – Exhaust Bypass Dampers - Open (if so equipped) 3. EXHAUST sequence “C” With only the exhaust fans running (supply fan off), the space that is conditioned by the rooftop would become negatively pressurized. This is desirable for clearing the area of smoke from the now-extinguished fire, possibly keeping smoke out of areas that were not damaged. – Supply Fan - Off – Supply Fan VFD - Closed/Min (if so equipped) – Exhaust Fan - On; Exhaust Dampers - Open (if soequipped) – OA Dampers - Closed; Return Damper - Open – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Deenergized – VOM Relay - Energized – Preheat Output - Off – Return Fan - On; Exhaust Dampers - Open (if so equipped) – Return VFD - Max (if so equipped) – OA Bypass Dampers - Open (if so equipped) – Exhaust Bypass Dampers - Open (if so equipped) 4. PURGE sequence “D” Possibly this sequence could be used for purging the air out of a building before coming out of Unoccupied mode of operation on VAV units or for the purging of smoke or stale air if required after a fire. – Supply Fan - On – Supply Fan VFD - Max (if so equipped) – Exhaust Fan - On; Exhaust Dampers - Open (if soequipped) – OA Dampers - Open; Return Damper - Closed
Installation RT-SVX24K-EN87 – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Energized – VOM Relay - Energized – Preheat Output - Off – Return Fan - On; Exhaust Dampers - Open (if so equipped) – Return VFD - Max (if so equipped) – OA Bypass Dampers - Open (if so equipped) – Exhaust Bypass Dampers - Open (if so equipped) 5. PURGE with duct pressure control sequence “E” This sequence can be used when supply air control is required for smoke control. – Supply Fan - On – Supply Fan VFD - (If so equipped) Controlled by Supply Air Pressure Control function; Supply Air Pressure High Limit disabled – Exhaust Fan - On; Exhaust Dampers Open (if so equipped) – OA Dampers - Open; Return Damper - Closed – Heat - All heat stages off; Mod Heat output at 0 VDC – Occupied/Unoccupied/VAV box output - Energized – VOM Relay - Energized – Preheat Output - Off – Return Fan - On; Exhaust Dampers - Open (if so equipped) – Return VFD - Max (if so equipped) – OA Bypass Dampers - Open (if so equipped) Exhaust Bypass Dampers - Open (if so equipped) Temperature vs. Resistance Coefficient The UCM network relies on various sensors located throughout the system to provide temperature information in the form of an analog input. All of the sensors used have the same temperature vs. resistance co-efficient and are made from Keystone Carbon D97 material with a 1 degree Centigrade tolerance. Emergency Stop Input A normally closed (N.C.) switch wired to the RTM may beused during emergency situations to shut down all unit operations. When opened, an immediate shutdown occurs. An emergency stop diagnostic is entered into the Human Interface and the unit must be manually reset. Refer to the appropriate illustrations in Figure 57, p. 89 Figure 59, p. 91 for the proper connection terminals in the unit control panel. The switch must be rated for 12 ma @ 24 VDC minimum. External Stop Input A normally closed (N.C.) switch wired to the RTM may be used during emergency situations to shut down all unit operations. When opened, an immediate shutdown occurs. When the contacts are closed, the unit will resume normal operation after minimum delays have occurred. Refer to the appropriate illustrations in Figure 57, p. 89for the proper connection terminals in the unit control panel. Occupied/Unoccupied Contacts To provide Night Setback control if a remote panel with NSB was not ordered, a field supplied contact must be installed. This binary input provides the Occupied/ Unoccupied status information of the building to the RTM. It can be initiated by a time clock, or a Building Automation System control output. The relay’s contacts must be rated for 12 ma @ 24 VDC minimum. Refer to the appropriate illustrations in Figure 58, p. 90 Figure 59, p. 91 for the proper connection terminals in the unit control panel. Demand Limit Relay If the unit is equipped with a Generic BAS Module, a normally open (N.O.) switch may be used to limit the electrical power usage during peak periods. When demand limit is initiated, the mechanical cooling and Table 34. Temp vs. resistance Temp (F) Resistance (in. 1000 Ohms) Temp (F) Resistance (in. 1000 Ohms) -40 346.10 7111.60 -30 241.70 7211.31 -20 170.10 7311.03 -10 121.40 7410.76 -5 103.00 7510.50 0 87.56 7610.25 5 74.65 7710.00 10 63.80 789.76 15 54.66 799.53 2046.94 809.30 25 40.40 858.25 30 34.85 907.33 35 30.18 1005.82 40 26.22 1055.21 45 22.85 1104.66 50 19.96 1203.76 55 17.47 1303.05 60 15.33 1402.50 65 13.49 1502.05 66 13.15 1601.69 67 12.82 1701.40 68 12.5 1801.17 69 12.19 1900.98 70 11.89 2000.83 Table 34. Temp vs. resistance (continued) Temp (F)Resistance (in. 1000 Ohms) Temp (F) Resistance (in. 1000 Ohms)
Installation 88RT-SVX24K-EN heating operation is limited to either 50% or 100%. Demand limit can be initiated by a toggle switch closure, a time clock, or an ICS TMcontrol output. These contacts must be rated for 12 ma @ 24 VDC minimum. Outside Air Sensor—BAYSENS016* This device senses the outdoor air temperature and sends this information in the form of an analog input to the RTM. Its factory installed on units with an economizer, but can be field provided/installed and used for informational purposes on units without an economizer. Refer to the appropriate illustrations in Figure 58, p. 90 Figure 59, p. 91 for the proper connection terminals in the unit control panel. Refer to Table 34, p. 87for Temperature vs. Resistance coefficient. Generic Building Automation System The Generic Building Automation System (GBAS) module allows a non-Trane building control system to communicate with the rooftop unit and accepts external setpoints in form of analog inputs for cooling, heating, demand limiting, and supply air pressure parameters. Refer to Figure 61, p. 93 &Table 35, p. 94 for the input wiring to the GBAS module and the various desired setpoints with the corresponding DC voltage inputs for VAV, SZVAV and CV applications.
Installation RT-SVX24K-EN89 Figure 57. Typical field wiring diagram for 90 to 162 ton CV control options
Installation 90RT-SVX24K-EN Figure 58. Typical ventilation override binary output for 90 to 162 ton CV control options