Home > Trane > Air Conditioner > Trane Intellipak 2 Service Manual

Trane Intellipak 2 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Installation
    RT-SVX24K-EN81
    Power Wire Sizing and Protection Devices
    To correctly size electrical service wiring for a unit, find the
    appropriate calculations listed below. Each type of unit has
    its own set of calculations for MCA (Minimum Circuit
    Ampacity), MOP (Maximum Overcurrent Protection), and RDE (Recommended Dual Element fuse size). Read the
    load definitions that follow and then find the appropriate
    set of calculations based on unit type.
    Note: Set 1 is for cooling only and cooling with gas heat
    units, and set 2 is for cooling with electric heat
    units.
    Load Definitions: (To determine load values, see the
    Electrical Service Sizing Data Tables on the following
    page.)
    LOAD1 = CURRENT OF THE LARGEST MOTOR
    (COMPRESSOR OR FAN MOTOR)
    LOAD2 = SUM OF THE CURRENTS OF ALL REMAINING
    MOTORS
    LOAD3 = CURRENT OF ELECTRIC HEATERS
    LOAD4 = ANY OTHER LOAD RATED AT 1 AMP OR MORE
    Set 1. Cooling Only Rooftop Units and Cooling
    with Gas Heat Rooftop Units
    MCA = (1.25 x LOAD1) + LOAD2 + LOAD4
    MOP = (2.25 x LOAD1) + LOAD2 + LOAD4
    Select a fuse rating equal to the MOP value. If the MOP
    value does not equal a standard fuse size as listed in NEC
    240-6, select the next lower standard fuse rating.
    Note: If selected MOP is less than the MCA, then select
    the lowest standard maximum fuse size which is
    equal to or larger than the MCA, provided the
    selected fuse size does not exceed 800 amps.
    RDE=(1.5xLOAD1)+LOAD2+LOAD4
    Select a fuse rating equal to the RDE value. If the RDE value
    does not equal a standard fuse size as listed in NEC 240-6,
    select the next higher standard fuse rating.
    Note: If the selected RDE is greater than the selected MOP
    value, then select the RDE value to equal the MOP
    value.
    Set 2. Rooftop units with Electric Heat
    To arrive at the correct MCA, MOP, and RDE values for
    these units, two sets of calculations must be performed.
    First calculate the MCA, MOP, and RDE values as if the unit
    was in cooling mode (use the equations given in Set 1).
    Then calculate the MCA, MOP, and RDE values as if the unit were in the heating mode as follows.
    (Keep in mind when determining LOADS that the
    compressors dont run while the unit is in the heating
    mode).
    MCA = 1.25 x (LOAD1 + LOAD2 + LOAD4) + LOAD3
    The nameplate MCA value will be the larger of the cooling mode MCA value or the heating mode MCA value
    calculated above.
    MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4
    The selection MOP value will be the larger of the cooling mode MOP value or the heating mode MOP value
    calculated above.
    Select a fuse rating equal to the MOP value. If the MOP
    value does not equal a standard fuse size as listed in NEC
    240-6, select the next lower standard fuse rating.
    Note: If selected MOP is less than the MCA, then select
    the lowest standard maximum fuse size which is
    equal to or larger than the MCA, provided the
    selected fuse size does not exceed 800 amps.
    RDE=(1.5xLOAD1)+LOAD2+LOAD3+LOAD4
    The selection RDE value will be the larger of the cooling mode RDE value or the heating mode RDE value calculated
    above.
    Select a fuse rating equal to the RDE value. If the RDE value
    does not equal a standard fuse size as listed in NEC 240-6,
    select the next higher standard fuse rating.
    Notes:
     If the selected RDE is greater than the selected MOP
    value, then select the RDE value to equal the MOP
    value.
     On 90 to 162 ton rooftops, the selected MOP value is
    stamped in the MOP field on the nameplate.
    Table 22. Electrical service sizing data
    Nom Tons Compressor
    Nominal Voltage
    460 V 575 V 380 V
    Size Number 
    per Unit Capacity kW (ea.)
    RLA 
    (ea.) LRA 
    (ea.) RLA 
    (ea.) LRA 
    (ea.) RLA 
    (ea.) LRA 
    (ea.)
    60 Hz 50 Hz
    Std. Coil High Cap 
    Std. CoilHigh Cap 
    90/100 240 4 21.3 21.6 17.6 17.9 34.1 215 27.3 175 34.0 215
    105/118 240 2 24.2 24.5 20.2 20.3 34.1 215 27.3 175 34.0 215
    300 2 25.0 25.3 20.9 21.0 44.7 260 35.8 210 44.6 260
    120/128 300 4 26.9 27.8 22.4 23.0 44.7 260 35.8 210 44.6 260
    130/140 300 2 28.5 28.8 23.8 23.8 44.7 260 35.8 210 44.6 260
    380 2 33.7 34.2 28.2 28.2 52.1 320 41.1 235 52.0 320
    150/162 380 4 34.7 -- 28.7 -- 52.1 320 41.1 235 52.0 320 
    						
    							Installation
    82RT-SVX24K-EN
    Table 23. Electrical service sizing data—motors
    Condenser Fan Motors
    Nominal  Tons  No. of Fans 460 V 575 V 380 V
    FLA FLA FLA
    90, 105 6 16.2 13.2 15
    120, 130,  150 8 21.6 17.6 20
    100 2 11.8 N/A N/A
    118, 128,  140, 162 2 11.8 N/A N/A
    Supply Fan Motors
    Motor 
    Horsepow er 460 V 575 V 380 V
    FLA FLA FLA
    15 18.5 15.1 24
    20 24.7 19.6 29
    25 3124.5 38
    30 36.6 29.2 47
    40 49.0 3954
    50 60.5 4868
    60 71.5 57.2 81
    75 9072103
    100 115 92N/A
    Exhaust/Return Fan Motors
    Motor 
    Horsepow er 460 V 575 V 380 V
    FLA FLA FLA
    7.5 9.47.8 13.6
    10 12.6 10.1 16
    15 18.5 15.1 24
    20 24.7 19.6 29
    25 3124.5 38
    30 36.6 29.2 47
    40 49.0 3954
    50 60.5 4868
    60 71.5 57.2 81
    Table 24. Electrical service sizing data—electric heat
    module (electric heat units only)
    Voltage
    460 575 380
    Module kW FLA FLA FLA
    90 / 56 108.386.685.1
    140 / 88 168.4134.7133.7
    265 / 166 318.8255252.2
    300 / 188 360.8288.7285.6
    Table 25. Electrical service sizing data—control power
    transformer (heating mode only)
    Nominal Tons  Digit 2 Unit 
    Function Voltages
    460 575 380 FLA FLA FLA
    90-150/100-162 E, L, S, X 3 3 4
    90, 105/100, 118 F (850 MBH) 4 4 5
    90, 105/100, 118 F (1100 MBH) 4 4 5
    90, 105/100, 118 F (1800 MBH) 4 4 5
    120-150/128-162 F (1100 MBH) 4 4 5
    120-150/128-162 F (1800 MBH) 4 4 5
    120-150/128-162 F (2500 MBH) 4 4 5
    Table 26. Electrical service sizing data—crankcase heater
    Nominal Tons Voltage
    460 575 380
    FLA (add) FLA
    (add) FLA
    (add)
    90-162 11 1
    Table 27. Voltage utilization range
    Unit Voltage
    460/60/3 414-506
    575/60/3
    (a)
    (a) Units with air-cooled condensers only. 
    517-633
    380/50/3
    (i)342-418
    Table 28. Electrical service sizing data—evaporative condenser
    Unit Part kwHPVoltage 
    460FLA
    Pump 
    1.5 2.7
    Sump Heater3 3.8
    Table 29. Electrical service sizing data—energy recovery
    wheel motor
    Nominal Tons Unit Function Voltages
    460 575 FLA FLA
    90-128 1 (Low CFM ERW) 1.2 0.95
    130-162 1 (Low CFM ERW) 1.7 1.4 90-162 2 (Std. CFM ERW) 1.7 1.4 
    						
    							Installation
    RT-SVX24K-EN83
    Field Installed Control Wiring
    The Rooftop Module (RTM) must have a mode input in
    order to operate the rooftop unit. The flexibility of having
    several system modes depends upon the type of sensor
    and/or remote panel selected to interface with the RTM. An
    overall layout of the various control options available, with
    the required number of conductors for each device, is
    illustrated beginning with Figure 57, p. 89.
    Note: All field wiring must conform to NEC guidelines as
    well as state and local codes.
    The various field installed control panels, sensors, switches, and contacts discussed in this section require
    both AC and DC consideration. These diagrams are
    representative of standard applications and are provided
    for general reference only. Always refer to the wiring
    diagram that shipped with the unit for specific electrical
    schematic and connection information.
    Controls using 24 VAC
    Before installing any connecting wiring, refer to Figure 10,
    p. 23 for the electrical access locations provided on the unit and
    Table 32, p. 83 for AC conductor sizing guidelines,
    and;
    a. Use copper conductors unless otherwise specified.
    b. Ensure that the AC control wiring between thecontrols and the units termination point does not
    exceed three (3) ohms/conductor for the length of
    the run.
    Note: Resistance in excess of 3 ohms per conductor may
    cause component failure due to insufficient AC
    voltage supply.
    c. Be sure to check all loads and conductors for grounds, shorts, and miswiring.
    d. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring.
    Controls using DC Analog Input/Outputs
    Before installing any connecting wiring between the unit
    and components utilizing a DC analog input\output signal,
    refer to the appropriate illustration in Figure 10, p. 23for
    the electrical access locations provided on the unit and
    Table 33, p. 83 for conductor sizing guidelines and;
    e. Use standard copper conductor thermostat wire unless otherwise specified.
    f. Ensure that the wiring between the controls and the unit termination point does not exceed two and a
    half (2.5) ohms/conductor for the length of the run.
    Note: Resistance in excess of 2.5 ohms per conductor can
    cause deviations in the accuracy of the controls.
    g. Do not run the electrical wires transporting DC signals in or around conduit housing high voltage
    wires.
    Units equipped with a Trane BACnet® Communication
    Interface (BCI) or LonTalk® communication Interface (LCI)
    option which utilizes a serial communication link; a. Must be 18 AWG shielded twisted pair cable(Belden 8760 or equivalent).
    b. Must not exceed 5,000 feet maximum for each link.
    Table 30. Electrical service sizing data—convenience
    outlet transformer
    Nominal Tons Voltage
    460 575
    FLA (add) FLA (add)
    90-162 3.32.6
    Table 31. Compressor data
    Unit Size Number 
    of 
    Compress ors Compress
    or Size Compress
    or 
    Designat or Compress
    or Type
    90/100 Ton Std &  Hi-Capacity 2 CSHN250 1A, 2A Scroll
    2 CSHN250 1B, 2B Scroll
    105/118 Ton Std &  Hi-Capacity 2 CSHN250 1A, 2A Scroll
    2 CSHN315 1B, 2B Scroll
    120/128 Ton Std &  Hi-Capacity 2 CSHN315 1A, 2A Scroll
    2 CSHN315 1B, 2B Scroll
    130/140 Ton Std &  Hi-Capacity 2 CSHN315 1A, 2A Scroll
    2 CSHN374 1B, 2B Scroll
    150/162 Ton Std  2 CSHN374 1A, 2A Scroll
    2 CSHN374 1B, 2B Scroll
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury.
    Table 32. AC conductors
    Distance from Unit to Control Recommended Wire Size
    000-460 feet 18 gauge
    461-732 feet 16 gauge
    733-1000 feet 14 gauge
    Table 33. DC conductors
    Distance from Unit to Control Recommended Wire Size
    000-150 feet22 gauge
    151- 240 feet 20 gauge
    241- 385 feet 18 gauge
    386- 610 feet 16 gauge
    611- 970 feet 14 gauge 
    						
    							Installation
    84RT-SVX24K-EN
    c. Must not pass between buildings.
    Constant Volume System Controls
    Remote Panel w/o NSB—BAYSENS110*
    This electronic sensor features four system switch settings
    (Heat, Cool, Auto, and Off) and two fan settings (On and
    Auto) with four system status LEDs. It is a manual or automatic changeover control with dual setpoint
    capability. It can be used with a remote zone sensor
    BAYSENS077*. Refer to Table 34, p. 87for the
    Temperature vs. Resistance coefficient.
    Constant Volume Zone Panel -BAYSENS108*
    This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and
    Auto). It is a manual or automatic changeover control with dual setpoint capability.
    Variable Air Volume System Controls
    VAV Changeover Contacts
    The changeover input is used with modulating gas heat, electric heat, or hydronic heat. When the contacts are
    closed, the unit will control to the discharge heating
    setpoint. Refer to the unit wiring diagram for the field
    connection terminals in the unit control panel. The switch
    must be rated at 12 ma @ 24 VDC minimum.
    Constant Volume or Variable Air Volume
    System Controls
    Remote Human Interface Module
    The remote Human Interface module enables the operatorto set or modify the operating parameters of the unit using
    a 16 key keypad and to view the operating status of the unit
    on the 2 line, 40 character LCD screen without leaving the
    building. However, the Remote Human Interface module
    can not be used to perform any service functions.
    One remote panel is designed to monitor and control up to
    four units providing each of the units are equipped with an
    IPCB module. Use the installation instructions that
    shipped with the module to install it, and the appropriate
    illustrations beginning with Figure 57, p. 89to connect it to
    the unit.
    Remote Panel w/ NSB -BAYSENS119*
    This 7 day programmable sensor features four periods for Occupied\Unoccupied programming per day. Either one
    or all four periods can be programmed. If the power is
    interrupted, the program is retained in permanent
    memory. If power is off longer than 2 hours, only the clock
    and day may have to be reset.
    The front panel allows selection of Occupied/Unoccupied periods with two temperature inputs (Cooling Supply Air
    Temperature and Heating Warm-up temperature) per occupied period.
    The occupied cooling setpoint ranges between 40 and 80°F. The warm-up setpoint ranges between 50 and 90°F
    with a 2 degree deadband. The Unoccupied cooling
    setpoint ranges between 45 and 98°F.The heating setpoint
    ranges between 43 and 96°F.
    The liquid crystal display (LCD) displays zone temperature, temperature setpoints, week day, time, and operational
    mode symbols.The DIP switches on the subbase are used
    to enable or disable applicable functions, i.e.; Morning
    warm-up, economizer minimum position override during
    unoccupied status, heat installed, remote zone
    temperature sensor, 12/24 hour time display, and daytime
    warm-up. Refer to Table 34, p. 87for the Temperature vs.
    Resistance coefficient. During an occupied period, an
    auxiliary relay rated for 1.25 amps @ 30 volts AC with one
    set of single pole double throw contacts is activated.
    Remote Zone Sensor (BAYSENS073*)
    This electronic analog sensor features remote zone sensing and timed override with override cancellation. It is
    used when the RTM has been programmed as the source
    for zone temperature control. Refer to Table 34, p. 87for
    the Temperature vs. Resistance coefficient.
    Remote Zone Sensor (BAYSENS074*)
    This electronic analog sensor features single setpoint capability and timed override with override cancellation. It
    is used with a Trane Integrated Comfort
    TMsystem. Refer to
    Table 34, p. 87 for the Temperature vs. Resistance
    coefficient.
    Remote Zone Sensor (BAYSENS016*)
    This bullet type analog Temperature sensor can be used for; outside air (ambient) sensing, return air temperature
    sensing, supply air temperature sensing, remote
    temperature sensing (uncovered), morning warm-up
    temperature sensing, and for VAV zone reset. Wiring
    procedures vary according to the particular application
    and equipment involved. When this sensor is wired to a
    BAYSENS119* Remote Panel, wiring must be 18 AWG
    ShieldedTwisted Pair (Belden 8760 or equivalent). Refer to
    Table 34, p. 87 for the Temperature vs. Resistance
    coefficient.
    Remote Zone Sensor (BAYSENS077*)
    This electronic analog sensor can be used with BAYSENS119* or 021* Remote Panels. When this sensor is
    wired to a BAYSENS119* Remote Panel, wiring must be 18
    AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details.
    CO2Sensing—Space or Duct
    The CO2sensor shall have the ability to monitor space
    occupancy levels within the building by measuring the
    parts per million of CO
    2in the air. As the CO2levels
    increase, the outside air damper modulates to meet the
    CO
    2space ventilation requirements. 
    						
    							Installation
    RT-SVX24K-EN85
    Remote Minimum Position Potentiometer
    (BAYSTAT023*)
    The remote minimum position potentiometer is used on
    units with an economizer. It allows the operator to
    remotely set the economizer minimum position (which
    controls the amount of outside air entering the unit). Use
    the installation instructions that shipped with the
    potentiometer to install it, and the appropriate illustrations
    beginning with Figure 57, p. 89to connect it to the unit.
    Single Zone Variable Air Volume & Rapid
    Restart System Control
    Remote Zone Sensor (BAYSENS016*)
    This bullet-type, analog temperature sensor can be used
    for supply air and return air temperature sensing. Wiring
    procedures vary according to application and equipment.
    When this sensor is wired to a BAYSENS119* Remote Panel, wiring must be 18 AWG Shielded Twisted Pair
    (Belden 8760 or equivalent). Refer to Table 34, p. 87for the
    Temperature vs. Resistance coefficient.
    External Auto/Stop Switch
    A field supplied single pole single throw switch may be used to shut down the unit operation. This switch is a
    binary input wired to the RTM. When opened, the unit
    shuts down immediately and can be cancelled by closing
    the switch. Refer to the appropriate illustrations beginning
    with Figure 57, p. 89 for the proper connection terminals in
    the unit control panel. The switch must be rated for 12 ma
    @ 24 VDC minimum.
    Emergency Override
    When a Lontalk®/BACnet® communication module is installed, the user can initiate from the Trane Tracer
    Summit or 3rd party BAS one of five (5) predefined, not
    available to configure, Emergency Override sequences. All
    compressors, condenser fans and the Humidification
    output are deenergized for any Emergency Override
    sequence. Each Emergency Override sequence
    commands the unit operation as follows:
    1. PRESSURIZE_EMERG:
    – Supply Fan - On
    – Supply Fan VFD Open/Max (if so equipped)
    – Exhaust Fan - Off; Exhaust Dampers Closed (if soequipped)
    – OA Dampers - Open; Return Damper - Closed
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Energized
    – VOM Relay - Energized (if so equipped)
    – Preheat Output - Off
    – Return Fan - Off; Exhaust Dampers - Closed (if so equipped) – Return VFD - Min (if so equipped)
    2. EMERG_DEPRESSURIZE:
    – Supply Fan - Off
    –
    Supply Fan VFD - Closed/Min (if so equipped)
    – Exhaust Fan - On; Exhaust Dampers Open/Max (if so equipped)
    – OA Dampers - Closed; Return Damper - Open
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Energized
    – VOM Relay - Energized (if so equipped)
    – Preheat Output - Off
    – Return Fan - On; Exhaust Dampers - Open (if so equipped)
    – Return VFD - Max (if so equipped)
    3. EMERG_PURGE:
    – Supply Fan - On
    –
    Supply Fan VFD - Open/Max (if so equipped)
    – Exhaust Fan - On; Exhaust Dampers Open (if so equipped)
    – OA Dampers - Open; Return Damper - Closed
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Energized
    – VOM Relay - Energized (if so equipped)
    – Preheat Output - Off
    – Return Fan - On; Exhaust Dampers - Open (if so equipped)
    – Return VFD - Max (if so equipped)
    4. EMERG_SHUTDOWN:
    – Supply Fan - Off
    –
    Supply Fan VFD - Closed/Min (if so equipped)
    – Exhaust Fan - Off; Exhaust Dampers Closed (if so equipped)
    – OA Dampers - Closed; Return Damper - Open
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Energized
    – VOM Relay - Energized (if so equipped)
    – Preheat Output - Off
    – Return Fan - Off; Exhaust Dampers - Closed (if so equipped)
    – Return VFD - Min (if so equipped)
    5. EMERG_FIRE - Input from fire pull box/system:
    – Supply Fan - Off
    –
    Supply Fan VFD - Closed/Min (if so equipped)
    – Exhaust Fan - Off; Exhaust Dampers Closed (if so equipped) 
    						
    							Installation
    86RT-SVX24K-EN
    – OA Dampers - Closed; Return Damper - Open
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Energized
    – VOM Relay - Energized (if so equipped)
    – Preheat Output - Off
    – Return Fan - Off; Exhaust Dampers - Closed (if so
    equipped)
    – Return VFD - Min (if so equipped)
    Ventilation Override Module (VOM)
    Important: The ventilation override system should not
    be used to signal the presence of smoke
    caused by a fire, as it is not intended nor
    designed to do so.
    The user can customize up to five (5) different override sequences for purposes of ventilation override control. If
    more than one VOM sequence is being requested, the
    sequence with the highest priority is initiated first.
    Sequence hierarchy is the sequence “A” (UNIT OFF) is first,
    with sequence “E” (PURGE with Duct Pressure Control)
    last. A ventilation override mode can be initiated by
    closing any of the five (5) corresponding binary inputs on
    the VOM module. A binary output is provided on the VOM
    module to provide remote indication of an active VOM
    mode. All compressors, condenser fans and the
    Humidification output are deenergized for any VOM
    sequence. The factory default definitions for each mode
    are as follows:
    1. UNIT OFF sequence “A”
    When complete system shutdown is required the following sequence can be used.
    – Supply Fan - Off
    – Supply Fan VFD - Closed/Min (if so equipped)
    – Exhaust Fan - Off; Exhaust Dampers Closed (if soequipped)
    – OA Dampers - Closed; Return Damper - Open
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Deenergized
    – VOM Relay - Energized
    – Preheat Output - Off
    – Return Fan - Off; Exhaust Dampers - Closed (if so equipped)
    – Return VFD - Min (if so equipped)
    – OA Bypass Dampers - Open (if so equipped)
    – Exhaust Bypass Dampers - Open (if so equipped)
    2. PRESSURIZE sequence “B”
    Perhaps a positively pressurized space is desired instead
    of
     a negatively pressurized space. In this case, the supply fan should be turned on with VFD at 100% speed and
    exhaust fan should be turned off.
    – Supply Fan - On
    – Supply Fan VFD - Max (if so equipped)
    – Exhaust Fan - Off; Exhaust Dampers Closed (if soequipped)
    – OA Dampers - Open; Return Damper - Closed
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Energized
    – VOM Relay - Energized
    – Preheat Output - Off
    – Return Fan - Off; Exhaust Dampers - Closed (if so equipped)
    – Return VFD - Min (if so equipped)
    – OA Bypass Dampers - Open (if so equipped)
    – Exhaust Bypass Dampers - Open (if so equipped)
    3. EXHAUST sequence “C”
    With only the exhaust fans running (supply fan off), the space
     that is conditioned by the rooftop would become
    negatively pressurized. This is desirable for clearing the
    area of smoke from the now-extinguished fire, possibly
    keeping smoke out of areas that were not damaged.
    – Supply Fan - Off
    – Supply Fan VFD - Closed/Min (if so equipped)
    – Exhaust Fan - On; Exhaust Dampers - Open (if soequipped)
    – OA Dampers - Closed; Return Damper - Open
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Deenergized
    – VOM Relay - Energized
    – Preheat Output - Off
    – Return Fan - On; Exhaust Dampers - Open (if so equipped)
    – Return VFD - Max (if so equipped)
    – OA Bypass Dampers - Open (if so equipped)
    – Exhaust Bypass Dampers - Open (if so equipped)
    4. PURGE sequence “D”
    Possibly this sequence could be used for purging the air
    out
     of a building before coming out of Unoccupied mode
    of operation on VAV units or for the purging of smoke or
    stale air if required after a fire.
    – Supply Fan - On
    – Supply Fan VFD - Max (if so equipped)
    – Exhaust Fan - On; Exhaust Dampers - Open (if soequipped)
    – OA Dampers - Open; Return Damper - Closed 
    						
    							Installation
    RT-SVX24K-EN87
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Energized
    – VOM Relay - Energized
    – Preheat Output - Off
    – Return Fan - On; Exhaust Dampers - Open (if so
    equipped)
    – Return VFD - Max (if so equipped)
    – OA Bypass Dampers - Open (if so equipped)
    – Exhaust Bypass Dampers - Open (if so equipped)
    5. PURGE with duct pressure control sequence “E”
    This sequence can be used when supply air control is required
     for smoke control.
    – Supply Fan - On
    – Supply Fan VFD - (If so equipped) Controlled by Supply Air Pressure Control function; Supply Air
    Pressure High Limit disabled
    – Exhaust Fan - On; Exhaust Dampers Open (if so equipped)
    – OA Dampers - Open; Return Damper - Closed
    – Heat - All heat stages off; Mod Heat output at 0 VDC
    – Occupied/Unoccupied/VAV box output - Energized
    – VOM Relay - Energized
    – Preheat Output - Off
    – Return Fan - On; Exhaust Dampers - Open (if so equipped)
    – Return VFD - Max (if so equipped)
    – OA Bypass Dampers - Open (if so equipped)
    Exhaust Bypass Dampers - Open (if so equipped)
    Temperature vs. Resistance Coefficient
    The UCM network relies on various sensors located throughout the system to provide temperature
    information in the form of an analog input. All of the
    sensors used have the same temperature vs. resistance
    co-efficient and are made from Keystone Carbon D97
    material with a 1 degree Centigrade tolerance.
    Emergency Stop Input
    A normally closed (N.C.) switch wired to the RTM may beused during emergency situations to shut down all unit
    operations. When opened, an immediate shutdown
    occurs. An emergency stop diagnostic is entered into the
    Human Interface and the unit must be manually reset.
    Refer to the appropriate illustrations in Figure 57, p. 89
    Figure 59, p. 91 for the proper connection terminals in the
    unit control panel. The switch must be rated for 12 ma @
    24 VDC minimum.
    External Stop Input
    A normally closed (N.C.) switch wired to the RTM may be used during emergency situations to shut down all unit
    operations. When opened, an immediate shutdown
    occurs. When the contacts are closed, the unit will resume
    normal operation after minimum delays have occurred.
    Refer to the appropriate illustrations in Figure 57, p. 89for
    the proper connection terminals in the unit control panel.
    Occupied/Unoccupied Contacts
    To provide Night Setback control if a remote panel with
    NSB was not ordered, a field supplied contact must be
    installed. This binary input provides the Occupied/
    Unoccupied status information of the building to the RTM.
    It can be initiated by a time clock, or a Building Automation
    System control output. The relay’s contacts must be rated
    for 12 ma @ 24 VDC minimum. Refer to the appropriate
    illustrations in Figure 58, p. 90 Figure 59, p. 91 for the
    proper connection terminals in the unit control panel.
    Demand Limit Relay
    If the unit is equipped with a Generic BAS Module, a
    normally open (N.O.) switch may be used to limit the
    electrical power usage during peak periods. When
    demand limit is initiated, the mechanical cooling and
    Table 34. Temp vs. resistance
    Temp (F)
    Resistance (in. 
    1000 Ohms) Temp (F) Resistance (in. 
    1000 Ohms)
    -40 346.10 7111.60
    -30 241.70 7211.31
    -20 170.10 7311.03
    -10 121.40 7410.76
    -5 103.00 7510.50
    0 87.56 7610.25
    5 74.65 7710.00
    10 63.80 789.76
    15 54.66 799.53
    2046.94 809.30
    25 40.40 858.25
    30 34.85 907.33
    35 30.18 1005.82
    40 26.22 1055.21
    45 22.85 1104.66
    50 19.96 1203.76
    55 17.47 1303.05
    60 15.33 1402.50
    65 13.49 1502.05
    66 13.15 1601.69
    67 12.82 1701.40
    68 12.5 1801.17
    69 12.19 1900.98
    70 11.89 2000.83
    Table 34. Temp vs. resistance (continued)
    Temp (F)Resistance (in. 
    1000 Ohms) Temp (F) Resistance (in. 
    1000 Ohms) 
    						
    							Installation
    88RT-SVX24K-EN
    heating operation is limited to either 50% or 100%.
    Demand limit can be initiated by a toggle switch closure,
    a time clock, or an ICS
    TMcontrol output. These contacts
    must be rated for 12 ma @ 24 VDC minimum.
    Outside Air Sensor—BAYSENS016*
    This device senses the outdoor air temperature and sends this information in the form of an analog input to the RTM.
    Its factory installed on units with an economizer, but can
    be field provided/installed and used for informational
    purposes on units without an economizer. Refer to the
    appropriate illustrations in Figure 58, p. 90 Figure 59, p. 91
    for the proper connection terminals in the unit control
    panel. Refer to Table 34, p. 87for Temperature vs.
    Resistance coefficient.
    Generic Building Automation System
    The Generic Building Automation System (GBAS) module allows a non-Trane building control system to
    communicate with the rooftop unit and accepts external
    setpoints in form of analog inputs for cooling, heating,
    demand limiting, and supply air pressure parameters.
    Refer to Figure 61, p. 93 &Table 35, p. 94 for the input
    wiring to the GBAS module and the various desired
    setpoints with the corresponding DC voltage inputs for
    VAV, SZVAV and CV applications. 
    						
    							Installation
    RT-SVX24K-EN89
    Figure 57. Typical field wiring diagram for 90 to 162 ton CV control options 
    						
    							Installation
    90RT-SVX24K-EN
    Figure 58. Typical ventilation override binary output for 90 to 162 ton CV control options 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Intellipak 2 Service Manual