Trane Intellipak 2 Service Manual
Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
General Information RT-SVX24K-EN11 modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for economizing, mechanical cooling, heating, and ventilation. Refer to the following discussion for an explanation of each module function. Rooftop Module (RTM - Standard on all units) The rooftop Module (RTM) responds to cooling, heating, and ventilation requests by energizing the proper unit components based on information received from other unit modules, sensors, remote panels, and customer supplied binary inputs. It initiates supply fan, exhaust fan, exhaust damper positioning or variable frequency drive output, and economizer operation based on that information. Compressor Module (MCM - standard on all units) The Compressor module, upon receiving a request formechanical cooling, energizes the appropriate compressors and condenser fans. It monitors the compressor operation through feedback information it receives from various protection devices. Human Interface Module (HI - standard on all units) The Human Interface module enables the operator toadjust the operating parameters for the unit using a 16 key keypad. The 2 line, 40 character LCD screen provides status information for the various unit functions as well as menus for the operator to set or modify the operating parameters. Heat Module (used on heating units) The Heat module, upon receiving a request for Heating,energizes the appropriate heating stages or strokes the Modulating Heating valve as required. Ventilation Override Module (VOM - Optional) The Ventilation Override module initiates specifiedfunctions such as; space pressurization, exhaust, purge, purge with duct pressure control, and unit off when any one of the five (5) binary inputs to the module are activated. The compressors and condenser fans are disabled during the ventilation operation. If more than one ventilation sequence is activated, the one with the highest priority is initiated. Interprocessor Communications Board (IPCB - Optional used with the Optional Remote Human Interface) The Interprocessor Communication Board expandscommunications from the rooftop unit UCM network to a Remote Human Interface Panel. DIP switch settings on the IPCB module for this application should be; Switches 1 and 2“Off” , Switch 3 “On”. Lontalk®/BACnet® Communication Interface Module (LCI/BCI - Optional - used on units with Trane ICS™ or 3rd party Building Automation Systems) The LonTalk/BACnet Communication Interface modules expand communications from the unit UCM network to a TraneTracer Summit™ or a 3rd party building automation system and allow external setpoint and configuration adjustment and monitoring of status and diagnostics. Exhaust/Comparative Enthalpy Module (ECEM - Optional used on units with Statitrac and/or comparative enthalpy options) The Exhaust/Comparative Enthalpy module receivesinformation from the return air humidity sensor, the Table 1. Resistance input vs. setpoint temperature RTM cooling or heating setpoint input used as the source for a ZONE temp setpoint (°F) RTM cooling setpoint input used as the source for SUPPLY AIR temp setpoint cooling (°F) Resistance (Ohms) Max. Tolerance 5% 40 401084 45 45992 50 50899 55 55796 60 60695 65 65597 70 70500 75 75403 80 80305 n/a 85208 n/a 90111 Table 2. RTM resistance value vs. system operating mode Resistance applied to RTM MODE input Terminals (Ohms) Max. Tolerance 5% Constant Volume Units Fan Mode System Mode 2320 AutoOff 4870 AutoCool 7680 AutoAuto 10770 OnOff 13320 OnCool 16130 OnAuto 19480 AutoHeat 27930 OnHeat
General Information 12RT-SVX24K-EN outside air humidity sensor, and the return air temperature sensor to utilize the lowest possible humidity level when considering economizer operation. In addition, it receives space pressure information which is used to maintain the space pressure to within the setpoint control band. Refer toFigure 1 for the Humidity vs. Voltage input values. Multi Purpose Module MPM (Optional - used with Return Fan Control, Energy Recovery, and Evaporative Condensers) The MPM supports three optional features. The first of which is return plenum pressure control by receiving analog voltage information for measuring return plenum pressure, calibrating that reading, and providing an output to control the return fan speed (if variable speed configured) in response to control algorithm requests. This module also provides inputs and outputs for control of all Energy Recovery feature devices including the energy wheel, exhaust and outdoor air bypass dampers, and recovery preheat. The liquid line pressure sensor inputs for both refrigeration circuits are received through the MPM in support of head pressure control on water- cooled condenser units. Variable Speed Module (VSM - Optional -Used with Fault Detection and Diagnostics FDD) The VSM is used with FDD. The VSM will accept a 0-10Vdc actuator feedback position signal which will then be used to determine the state of OutsideAir Damper system. Modulating Dehumidification Module MDM (Optional - used with Dehumidification Control) The MDM supports specific control inputs and outputs forModulating Dehumidification control including modulating Reheat and Cooling valve control as well as the Reheat Pumpout Coil Relay output. The Modulating Dehumidification control algorithm provides control requests to the MDM to accomplish proper Dehumidification control. Ventilation Control Module (VCM) The Ventilation Control Module (VCM) is located in thefilter section of the unit and is linked to the unit UCM network. Using a “velocity pressure” sensing ring located in the outside air section allows the VCM to monitor and control the quantity of outside air entering the unit to a minimum airflow setpoint. An optional temperature sensor can be connected to the VCM which enables it to control a field installed outside air preheater. An optional CO 2sensor can be connected to the VCM to control CO 2reset. The reset function adjusts the minimum CFM upward as the CO 2concentrations increase. The maximum effective (reset) setpoint value for outside air entering the unit is limited to the systems operating CFM. The following table lists the velocity pressure vs. Input Voltage (see also Figure 6, p. 18.). The velocity pressure transducer/solenoid assembly is illustrated below. Refer to the “Units withTRAQ™ Sensor,” p. 103 for VCM operation. Figure 1. Humidity vs. current Table 3. Minimum outside air setpoint w/VCM and TRAQ™ sensing Unit Input Volts CFM 90-162 Tons 0.5 - 4.5 VDC 0 - 46000
General Information RT-SVX24K-EN13 Generic Building Automation System Module (GBAS - Optional used with non-Trane building control systems) The Generic Building Automation System (GBAS) module allows a non-Trane building control system to communicate with the rooftop unit and accepts external setpoints in the form of analog inputs for cooling, heating, supply air pressure, and a binary Input for demand limit. Refer to the “Field Installed Control Wiring” section for the input wiring to the GBAS module and the various desired setpoints with the corresponding DC voltage inputs for both VAV, SZVAV, RR and CV applications. Input Devices and System Functions The descriptions of the following basic Input Devices used within the UCM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit electrical schematic for the specific module connections. Constant Volume (CV) and Variable Air Volume (VAV) Units Supply Air Temperature Sensor An analog input device used with CV and VAV applications that monitors the supply air temperature for: supply air temperature control (VAV), supply air temperature reset (VAV), supply air temperature low limiting (CV), supply air tempering (CV/VAV). It is mounted in the supply air discharge section of the unit and is connected to the RTM. Figure 2. Velocity pressure transducer/solenoid assembly Figure 3. Outside air tubing schematic Figure 4. Return air pressure tubing schematic
General Information 14RT-SVX24K-EN Return Air Temperature Sensor An analog input device used with a return humidity sensor on CV and VAV applications when the comparative enthalpy option is ordered. It monitors the return air temperature and compares it to the outdoor temperature to establish which temperature is best suited to maintain the cooling requirements. It is mounted in the return air section and is connected to the ECEM. Leaving Evaporator Temperature Sensor An analog input device used with CV and VAV applicationsthat monitors the refrigerant temperature inside the evaporator coil to prevent coil freezing. It is attached to the suction line near the evaporator coil and is connected to the MCM. It is factory set for 30°F and has an adjustable range of 25°F to 35°F.The compressors are staged “Off” as necessary to prevent icing. After the last compressor stage has been turned “Off”, the compressors will be allowed to restart once the evaporator temperature rises 10°F above the “coil frost cutout temperature” and the minimum three minute “Off” time has elapsed. Entering Evaporator Temperature Sensors Analog input devices used with CV and VAV applications. This device is used in conjunction with the Leaving Evaporator Temperature Sensor to prevent the unit from running compressors with insufficient charge. Filter Switch A binary input device used on CV and VAV applicationsthat measures the pressure differential across the unit filters. It is mounted in the filter section and is connected to the RTM. A diagnostic SERVICE signal is sent to the remote panel if the pressure differential across the filters is at least 0.5 w.c. The contacts will automatically open when the pressure differential across the filters decrease to 0.4 w.c. The switch differential can be field adjusted between 0.17 w.c. to 5.0 w.c. ± 0.05 w.c. Leaving Recovery Exhaust Temp Sensor Analog input device used on CV and VAV applications withEnergy Recovery option installed. It is used to monitor the temperature of the leaving air on the Exhaust Fan side of the energy recovery wheel. This temperature is used to determine if the temperature of the wheel is too cold as compared to the Recovery Frost Avoidance Setpoint. The result is used to determine when to enable energy wheel frost avoidance functions. Supply, Exhaust and Return Fan Airflow Proving Switches Supply Airflow Proving Switch is a binary input device used on CV and VAV applications to signal the RTM when the supply fan is operating. It is located in the supply fan section of the unit and is connected to the RTM. During a request for fan operation, if the differential switch is detected to be open for 40 consecutive seconds; compressor operation is turned “Off”, heat operation is turned “Off”, the request for supply fan operation is turned “Off” and locked out, exhaust dampers (if equipped) are “closed”, economizer dampers (if equipped) are “closed”, and a manual reset diagnostic is initiated. Exhaust/return Airflow Proving Switch is a binary input device used on all rooftop units equipped with an exhaust fan. It is located in the exhaust/return fan section of the unit and is connected to the RTM. During a request for fan operation, if the differential switch is detected to be open for 40 consecutive seconds, the economizer is closed to the minimum position setpoint, the request for exhaust fan operation is turned “Off” and locked out, and a manual reset diagnostic is initiated. The fan failure lockout can be reset at the Human Interface located in the unit control panel, by Tracer, or by cycling the control power to the RTM Off/On. Lead-Lag A selectable mode of operation through the HumanInterface. It alternates the starting between the first compressor of each refrigeration circuit. Only the compressor banks will switch, not the order of the compressors within a bank, providing the first compressor in each circuit had been activated during the same request for cooling. Charge Isolation During the OFF cycle, most of the charge is isolated between the compressor (internal) discharge check valves and liquid line solenoid valve. This reduces the OFF cycle charge migration, and liquid feedback during subsequent startup.The liquid line solenoid is energized (opened) with the start of the circuit compressor. Supply, Exhaust and Return Fan Circuit Breakers The supply fan and exhaust fan motors are protected by circuit breakers or fuses. They will trip and interrupt the power supply to the motors if the current exceeds the breakers “must trip” value. The rooftop module (RTM) will shut all system functions “Off” when an open fan proving switch is detected. Low Pressure Control Low Pressure Control is accomplished using a binary input device on CV and VAV applications. LP cutouts are located on the suction lines near the scroll compressors. The LPC contacts are designed to close when the suction pressure exceeds 41 ± 4 psig. If the LP control is open when a compressor is requested to start, none of the compressors on that circuit will be allowed to operate. They are locked out and a manual reset diagnostic is initiated. The LP cutouts are designed to open if the suction pressure approaches 22 ± 4 psig. If the LP cutout opens after a compressor has started, all compressors operating on that circuit will be turned off immediately and will
General Information RT-SVX24K-EN15 remain off for a minimum of three minutes. If the LP cutout trips four consecutive times during the first three minutes of operation, the compressors on that circuit will be locked out and a manual reset diagnostic is initiated. Saturated Condenser Temperature Sensors Analog input devices used on CV and VAV applications mounted inside a temperature well located on a condenser tube bend. They monitor the saturated refrigerant temperature inside the condenser coil and are connected to the MCM. As the saturated refrigerant temperature varies due to operating conditions, the condenser fans are cycled “On” or “Off” as required to maintain acceptable operating pressures. Head Pressure Control Accomplished using two saturated refrigeranttemperature sensors on CV and VAV applications. During a request for compressor operation, when the condensing temperature rises above the “lower limit” of the controlband, the Compressor Module (MCM) starts sequencing condenser fans “On”. If the operating fans can not bring the condensing temperature to within the controlband, more fans are turned on. As the saturated condensing temperature approaches the lower limit of the controlband, fans are sequenced “Off”. The minimum “On/Off” time for condenser fan staging is 5.2 seconds. If the system is operating at a given fan stage below 100% for 30 minutes and the saturated condensing temperature is above the “efficiency check point” setting, a fan stage will be added. If the saturated condensing temperature falls below the “efficiency check point” setting, the fan control will remain at the present operating stage. If a fan stage cycles four times within a 10 minute period, the control switches from controlling to the “lower limit” to a temperature equal to the “lower limit” minus the “temporary low limit suppression” setting. It will utilize this new “low limit” temperature for one hour to reduce condenser fan short cycling. For evaporative condensing units, head pressure is monitored with pressure transducers attached to the saturated condensing line and converted to a temperature by the MPM. This temperature is used to control the variable speed fan and sump pump. When the temperature rises above the upper limit (120°F) the sump pump is energized. If the condensing temperature drops below the lower limit (70°F) the sump pump is de- energized. High Pressure Limit Controls High Pressure controls are located on the discharge lines near the scroll compressors. They are designed to open when the discharge pressure approaches 650 ± 10 psig. The controls reset automatically when the discharge pressure decreases to approximately 550 ± 10 psig. However, the compressors on that circuit are locked out and a manual reset diagnostic is initiated after the fourth occurrence of a high pressure condition. Outdoor Air Humidity Sensor An analog input device used on CV and VAV applicationswith 100% economizer. It monitors the outdoor humidity levels for economizer operation. It is mounted in the outside air intake section and is connected to the RTM. Return Air Humidity Sensor An analog input device used on CV and VAV applicationswith the comparative enthalpy option. It monitors the return air humidity level and compares it to the outdoor humidity level to establish which conditions are best suited to maintain the cooling requirements. It is mounted in the return air section and is connected to the ECEM. Space Humidity Sensor Analog input device used on CV and VAV applications withmodulating dehumidification option and/or humidification field installed option. It is used to monitor the humidity level in the space and compared to dehumidification and humidification setpoints to maintain space humidity requirements. It is field mounted in the space and connected to the RTM. Status/Annunciator Output An internal function within the RTM module on CV and VAV applications that provides: c. diagnostic and mode status signals to the remotepanel (LEDs) and to the Human Interface d. control of the binary Alarm output on the RTM e. control of the binary outputs on the GBAS module to inform the customer of the operational status and/or diagnostic conditions Low Ambient Compressor Lockout Utilizes an analog input device for CV and VAV applications. When the system is configured for low ambient compressor lockout, the compressors are not allowed to operate if the temperature of the outside air falls below the lockout setpoint. When the temperature rises 5°F above the lockout setpoint, the compressors are allowed to operate. The factory preset is 50°F. These compressors come equipped with a protection module that monitors phase loss, phase sequencing and motor temperature. Space Pressure Transducer An analog input device used on CV and VAV applicationswith the Statitrac option. It modulates the exhaust dampers to keep the space pressure within the building to a customer designated controlband. It is mounted on the bottom support below the return damper blade assembly and is connected to the ECEM. Field supplied pneumatic tubing must be connected between the space being controlled and the transducer assembly.
General Information 16RT-SVX24K-EN Morning Warm-Up—Zone Heat When a system changes from an unoccupied to an occupied mode, or switches from STOPPED to AUTO, or power is applied to a unit with the MWU option, the heater in the unit or external heat will be brought on if the space temperature is below the MWU setpoint. The heat will remain on until the temperature reaches the MWU setpoint. If the unit is VAV, then the VAV box/unocc relay will continue to stay in the unoccupied position and the VFD output will stay at 100% during the MWU mode. When the MWU setpoint is reached and the heat mode is terminated, then the VAV box/unocc relay will switch to the occupied mode and the VFD output will be controlled by the duct static pressure. During Full Capacity MWU the economizer damper is held closed for as long as it takes to reach setpoint. During Cycling Capacity MWU the economizer damper is allowed to go to minimum position after one hour of operation if setpoint has not been reached. Compressor Motor Winding Thermostats A thermostat is embedded in the motor windings of eachScroll compressor. Each thermostat is designed to open if the motor windings exceed approximately 221°F. The thermostat will reset automatically when the winding temperature decreases to approximately 181°F. Rapid cycling, loss of charge, abnormally high suction temperatures, or the compressor running backwards could cause the thermostat to open. During a request for compressor operation, if the Compressor Module detects a problem outside of normal parameters, it turns any operating compressor(s) on that circuit “Off”, locks out all compressor operation for that circuit, and initiates a manual reset diagnostic (compressor trip). These compressors come equipped with a protection module that monitors phase loss, phase sequencing and motor temperature. Supply Air Temperature Low Limit Uses the supply air temperature sensor input to modulate the economizer damper to minimum position in the event the supply air temperature falls below the occupied heating setpoint temperature. Discharge Line Thermostat for Evaporative Condensers The first compressor on each circuit is equipped with aDischarge Line Thermostat. If the temperature of the line exceeds 210°F the thermostat interrupts the 115V circuit for the compressors and both of the compressors on that circuit will be de-energized. Once the temperature drops below 170°F the thermostat will close and allow the compressor to be energized. Freezestat A binary input device used on CV and VAV units with Hydronic Heat. It is mounted in the heat section and connected to the Heat Module. If the temperature of the air leaving the heating coil falls to 40°F, the normally open contacts on the freezestat closes signalling the Heat Module and the Rooftop Module (RTM) to: f. drive the Hydronic Heat Actuator to the full openposition Figure 5. Transducer voltage output vs. pressure input for supply, return and building pressure -0.75 to 9.0 Iwc Pressure Transducer Voltage Output vs. Pressure Input 0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 -0. 75 -0. 25 0.2 5 0. 7 5 1. 2 5 1. 7 5 2. 2 5 2. 7 5 3. 2 5 3. 7 5 4. 2 5 4. 7 5 5. 2 5 5. 7 5 6. 2 5 6. 7 5 7. 2 5 7. 7 5 8. 2 5 8. 7 5Pressure (inches w.c.) Volts
General Information RT-SVX24K-EN17 g. turn the supply fan “Off” h. closes the outside air damper i. turns “On” the SERVICE light at the Remote Panel j. initiates a “Low Temp Limit” diagnostic to the Human Interface Compressor Circuit Breakers The Scroll Compressors are protected by circuit breakerswhich interrupt the power supply to the compressors if the current exceeds the breakers “must trip” value. During a request for compressor operation, if the Compressor Module detects a problem outside normal parameters, it turns any operating compressor(s) on that circuit “Off”, locks out all compressor operation for that circuit, and initiates a manual reset diagnostic (compressor trip). Constant Volume (CV) Units Zone Temperature—Cooling Relies on input from a sensor located directly in the space, while a system is in the occupied “Cooling” mode. It modulates the economizer (if equipped) and/or stages the mechanical cooling “On and Off” as required to maintain the zone temperature to within the cooling setpoint deadband. Zone Temperature—Heating Relies on input from a sensor located directly in the space, while a system is in the occupied “Heating” mode or an unoccupied period, to stage the heat “on and off” or to modulate the heating valve (hydronic heat only) as required to maintain the zone temperature to within the heating setpoint deadband. The supply fan will be requested to operate any time there is a request for heat. On gas heat units, the fan will continue to run for 60 seconds after the furnace is turned off. Supply Air Tempering On CV units equipped with staged gas heat, if the supply air temperature falls 10°F below the occupied heating setpoint temperature while the heater is “Off”, the first stage of heat will be turned “On”.The heater is turned “Off” when the supply air temperature reaches 10°F above the occupied heating setpoint temperature. Variable Air Volume (VAV) Units Occupied Heating—Supply Air Temperature When a VAV unit is equipped with “Modulating Heat”, andthe system is in an occupied mode, and the field supplied changeover relay contacts have closed or per a BAS command, the supply air temperature will be controlled to the customer specified supply air heating setpoint. It will remain in the heating status until the changeover relay contacts are opened or BAS has released the heat command. Occupied Cooling—Supply Air Temperature When a VAV unit is in the occupied mode, the supply airtemperature will be controlled to the customer specified supply air cooling setpoint by modulating the economizer and/or staging the mechanical cooling “On and Off” as required.The changeover relay contacts must be open, or BAS command set to auto or cool, for the cooling to operate. Daytime Warm-up On VAV units equipped with heat, if the zone temperature falls below the daytime warm-up initiate temperature during the occupied mode, the system will switch to full airflow. During this mode, the VAV box/unocc relay will be energized (this is to signal the VAV boxes to go to 100%). After the VAV box max stroke time has elapsed (factory set at 6 minutes), the VFD output will be set to 100%. The airflow will be at 100% and the heat will be turned on to control to the occupied heating setpoint. When the zone temperature reaches the daytime warm-up termination setpoint, the heat will be turned off, the relay will be de-energized, releasing the VAV boxes, the VFD output will go back to duct static pressure control and the unit will return to discharge air control. If the occ zone heating setpoint is less than the DWU terminate setpoint, the heat will turn off when the occ zone heat setpoint is reached, but it will stay in DWU mode and cycle the heat to maintain setpoint. Unoccupied Heating—Zone Temperature When a VAV unit is equipped with gas, electric, or hydronicheat and is in the unoccupied mode, the zone temperature will be controlled to within the customer specified setpoint deadband. During an unoccupied mode for a VAV unit, the VAV box/unocc relay will be in the unoccupied position and the VFD output will be at 100%.This means that if there is a call for heat (or cool) and the supply fan comes on, it will be at full airflow and the VAV boxes in the space will need to be 100% open as signaled by the VAV box/unocc relay. Supply Air Tempering On VAV units equipped with “Modulating Heat” ,ifthe supply air temperature falls 10°F below the supply air temperature setpoint, the heat will modulate to maintain the supply air temperature to within the low end of the setpoint deadband. Supply Duct Static Pressure Control (Occupied) The RTM relies on input from the duct pressure transducer when a unit is equipped with a Variable Frequency Drive to set the supply fan speed to maintain the supply duct static pressure to within the static pressure setpoint deadband. The transducer compares supply duct pressure to ambient pressure. Refer to Figure 43, p. 67.
General Information 18RT-SVX24K-EN Space Temperature Averaging Space temperature averaging for Constant Volume applications is accomplished by wiring a number of remote sensors in a series/parallel circuit. The fewest number of sensors required to accomplish space temperature averaging is four. The Space Temperature Averaging with Multiple Sensors figure illustrates a single sensor circuit (Single Zone), four sensors wired in a series/parallel circuit (Four Zone), nine sensors wired in a series/parallel circuit (Nine Zone). Any number squared, is the number of remote sensors required. Wiring termination will depend on the type of remote panel or control configuration for the system. Refer to the wiring diagrams that shipped with the unit. Figure 6. Transducer voltage output vs. pressure input with VCM and TRAQ™ sensing Transducer Voltage Output vs. Pre ssure Input 0. 0 0. 5 1. 0 1. 5 2. 0 2. 5 3. 0 3. 5 4. 0 -0.5 0. 0 0.5 1. 0 1. 5 2.0 2.5 3. 0 3.5 4. 0 4. 5 5.0 P r e ssu r e ( i n c h e s w . c . ) Volts Figure 7. Unit component layout and “ship with” locations Return/ Exhaust Fan Outside Air Dampers Supply Fan Condenser Fans Compressor Section Heating Section Exhaust Damper Hood Evap Coil Evap Coil Controls Variable Frquency Drive (VFD) Filter Section Reheat Coil Option Outside Air Dampers Return Air Dampers Flue Vent Access Variable Frquency Drive (VFD) Hot Water/Steam Hydronic ConnectionOutside Air Static Kit and sensors
General Information RT-SVX24K-EN19 Unit Control Modules Unit control modules are microelectronic circuit boards designed to perform specific unit functions. The control modules, through proportional/integral control algorithms, provide the best possible comfort level for the customer. They are mounted in the control panel and are factory wired to their respective internal components. The control modules receive and interpret information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for economizing, mechanical cooling, heating, and ventilation. Figure 9illustrates the typical location of each designated module. Figure 8. Space temperature averaging with multiple sensors
General Information 20RT-SVX24K-EN Single Zone Variable Air Volume (SZVAV) Only The IntelliPak controls platform will support Single Zone VAV as an optional unit control type in order to meetASHRAE 90.1. The basic control will be a hybrid VAV/CV configured unit that provides discharge temperature control to a varying discharge air temperature target setpoint based on the space temperature and/or humidity conditions. Concurrently, the unit will control and optimize the supply fan speed to maintain the zone temperature to a zone temperature setpoint. Supply Fan Output Control Units configured for Single Zone VAV control will utilize the same supply fan output control scheme as on traditional VAV units except the VFD signal will be based on zone heating and cooling demand instead of the supply air pressure. VFD Control Single Zone VAV units will be equipped with a VFD- controlled supply fan which will be controlled via a 0- 10VDC signal from the Rooftop Module (RTM). With the RTM supply fan output energized and the RTM VFD output at 0VDC, the fan speed output is 37% (22Hz) from the VFD by default; and at 10VDC the fan speed output is 100% (60Hz). The control scales the 0-10VDC VFD output from the RTM linearly to control between the 37-100% range. The VFD will modulate the supply fan motor speed, accelerating or decelerating as required to maintain the zone temperature to the zone temperature setpoint. When subjected to high ambient return conditions the VFD will reduce its output frequency to maintain operation. Bypass control is offered to provide full nominal airflow in the event of drive failure. Ventilation Control Units configured for Single Zone VAV control will require special handling of the OA Damper Minimum Position control in order to compensate for the non-linearity of airflow associated with the variable supply fan speed and damper combinations. Units configured for TRAQ with or without DCV will operate identically to traditional units with no control changes. Space Pressure Control For units configured with Space Pressure Control with or without Statitrac, the new schemes implemented for economizer minimum position handling require changes to the existing Space Pressure Control scheme in order to Figure 9. Control module locations BCI