Home > Trane > Air Conditioner > Trane Intellipak 2 Service Manual

Trane Intellipak 2 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							General Information
    RT-SVX24K-EN11
    modules, sensors, remote panels, and customer binary
    contacts to satisfy the applicable request for economizing,
    mechanical cooling, heating, and ventilation. Refer to the
    following discussion for an explanation of each module
    function.
    Rooftop Module (RTM - Standard on all units)
    The rooftop Module (RTM) responds to cooling, heating,
    and ventilation requests by energizing the proper unit
    components based on information received from other
    unit modules, sensors,
    remote panels, and customer supplied binary inputs. It
    initiates supply fan, exhaust fan, exhaust damper
    positioning or variable frequency drive output, and
    economizer operation based on
    that information.
    Compressor Module (MCM - standard on all
    units)
    The Compressor module, upon receiving a request formechanical cooling, energizes the appropriate
    compressors and condenser fans. It monitors the
    compressor operation through feedback information it
    receives from various protection devices.
    Human Interface Module (HI - standard on all
    units)
    The Human Interface module enables the operator toadjust the operating parameters for the unit using a 16 key
    keypad. The 2 line, 40 character LCD screen provides
    status information for the various unit functions as well as
    menus for the operator to set or modify the operating
    parameters.
    Heat Module (used on heating units)
    The Heat module, upon receiving a request for Heating,energizes the appropriate heating stages or strokes the
    Modulating Heating valve as required.
    Ventilation Override Module (VOM - Optional)
    The Ventilation Override module initiates specifiedfunctions such as; space pressurization, exhaust, purge,
    purge with duct pressure control, and unit off when any
    one of the five (5) binary inputs to the module are
    activated. The compressors and condenser fans are
    disabled during the ventilation operation. If more than one
    ventilation sequence is activated, the one with the highest
    priority is initiated.
    Interprocessor Communications Board (IPCB -
    Optional used with the Optional Remote
    Human Interface)
    The Interprocessor Communication Board expandscommunications from the rooftop unit UCM network to a
    Remote Human Interface Panel. DIP switch settings on the
    IPCB module for this application should be; Switches 1 and
    2“Off” , Switch 3 “On”.
    Lontalk®/BACnet® Communication Interface
    Module (LCI/BCI - Optional - used on units
    with Trane ICS™ or 3rd party Building
    Automation Systems)
    The LonTalk/BACnet Communication Interface modules
    expand communications from the unit UCM network to a
    TraneTracer Summit™ or a 3rd party building automation system and allow external setpoint and configuration
    adjustment and monitoring of status and diagnostics.
    Exhaust/Comparative Enthalpy Module
    (ECEM - Optional used on units with Statitrac
    and/or comparative enthalpy options)
    The Exhaust/Comparative Enthalpy module receivesinformation from the return air humidity sensor, the
    Table 1. Resistance input vs. setpoint temperature
    RTM cooling or 
    heating setpoint 
    input used as the 
    source for a ZONE 
    temp setpoint (°F) RTM cooling 
    setpoint input 
    used as the source  for SUPPLY AIR temp setpoint  cooling (°F) Resistance (Ohms) 
    Max. 
    Tolerance 5%
    40 401084
    45 45992
    50 50899
    55 55796
    60 60695
    65 65597
    70 70500
    75 75403
    80 80305
    n/a 85208
    n/a 90111
    Table 2. RTM resistance value vs. system operating
    mode
    Resistance applied to 
    RTM MODE input 
    Terminals (Ohms) 
    Max. Tolerance 5% Constant Volume Units
    Fan Mode System Mode
    2320 AutoOff
    4870 AutoCool
    7680 AutoAuto
    10770 OnOff
    13320 OnCool
    16130 OnAuto
    19480 AutoHeat
    27930 OnHeat 
    						
    							General Information
    12RT-SVX24K-EN
    outside air humidity sensor, and the return air temperature
    sensor to utilize the lowest possible humidity level when
    considering economizer operation. In addition, it receives
    space pressure information which is used to maintain the
    space pressure to within the setpoint control band. Refer
    toFigure 1 for the Humidity vs. Voltage input values.
    Multi Purpose Module MPM (Optional - used
    with Return Fan Control, Energy Recovery, and
    Evaporative Condensers)
    The MPM supports three optional features. The first of
    which is return plenum pressure control by receiving
    analog voltage information for measuring return plenum
    pressure, calibrating that reading, and providing an output
    to control the return fan speed (if variable speed
    configured) in response to control algorithm requests.
    This module also provides inputs and outputs for control of all Energy Recovery feature devices including the
    energy wheel, exhaust and outdoor air bypass dampers,
    and recovery preheat. The liquid line pressure sensor
    inputs for both refrigeration circuits are received through
    the MPM in support of head pressure control on water-
    cooled condenser units.
    Variable Speed Module (VSM - Optional -Used with Fault Detection and Diagnostics
    FDD)
    The VSM is used with FDD. The VSM will accept a 0-10Vdc
    actuator feedback position signal which will then be used
    to determine the state of OutsideAir Damper system.
    Modulating Dehumidification Module MDM
    (Optional - used with Dehumidification
    Control)
    The MDM supports specific control inputs and outputs forModulating Dehumidification control including
    modulating Reheat and Cooling valve control as well as
    the Reheat Pumpout Coil Relay output. The Modulating
    Dehumidification control algorithm provides control
    requests to the MDM to accomplish proper
    Dehumidification control.
    Ventilation Control Module (VCM)
    The Ventilation Control Module (VCM) is located in thefilter section of the unit and is linked to the unit UCM
    network. Using a “velocity pressure” sensing ring located
    in the outside air section allows the VCM to monitor and
    control the quantity of outside air entering the unit to a
    minimum airflow setpoint.
    An optional temperature sensor can be connected to the
    VCM which enables it to control a field installed outside air preheater. An optional CO
    2sensor can be connected to the
    VCM to control CO
    2reset. The reset function adjusts the
    minimum CFM upward as the CO
    2concentrations
    increase.
    The maximum effective (reset) setpoint value for outside air entering the unit is limited to the systems operating
    CFM. The following table lists the velocity pressure vs.
    Input Voltage (see also Figure 6, p. 18.).
    The velocity pressure transducer/solenoid assembly is illustrated below. Refer to the “Units withTRAQ™ Sensor,”
    p. 103 for VCM operation.
    Figure 1. Humidity vs. current
    Table 3. Minimum outside air setpoint w/VCM and
    TRAQ™ sensing
    Unit Input Volts CFM
    90-162 Tons 0.5 - 4.5 VDC  0 - 46000 
    						
    							General Information
    RT-SVX24K-EN13
    Generic Building Automation System Module
    (GBAS - Optional used with
    non-Trane building control systems)
    The Generic Building Automation System (GBAS) module
    allows a non-Trane building control system to
    communicate with the rooftop unit and accepts external
    setpoints in the form of analog inputs for cooling, heating,
    supply air pressure, and a binary Input for demand limit. Refer to the “Field Installed Control Wiring” section for the
    input wiring to the GBAS module and the various desired
    setpoints with the corresponding DC voltage inputs for
    both VAV, SZVAV, RR and CV applications.
    Input Devices and System Functions
    The descriptions of the following basic Input Devices used
    within the UCM network are to acquaint the operator with
    their function as they interface with the various modules.
    Refer to the unit electrical schematic for the specific
    module connections.
    Constant Volume (CV) and
    Variable Air Volume (VAV) Units
    Supply Air Temperature Sensor
    An analog input device used with CV and VAV applications
    that monitors the supply air temperature for: supply air
    temperature control (VAV), supply air temperature reset
    (VAV), supply air temperature low limiting (CV), supply air
    tempering (CV/VAV). It is mounted in the supply air
    discharge section of the unit and is connected to the RTM.
    Figure 2. Velocity pressure transducer/solenoid assembly
    Figure 3. Outside air tubing schematic
    Figure 4. Return air pressure tubing schematic 
    						
    							General Information
    14RT-SVX24K-EN
    Return Air Temperature Sensor
    An analog input device used with a return humidity sensor
    on CV and VAV applications when the comparative
    enthalpy option is ordered. It monitors the return air
    temperature and compares it to the outdoor temperature
    to establish which temperature is best suited to maintain
    the cooling requirements. It is mounted in the return air
    section and is connected to the ECEM.
    Leaving Evaporator Temperature Sensor
    An analog input device used with CV and VAV applicationsthat monitors the refrigerant temperature inside the
    evaporator coil to prevent coil freezing. It is attached to the
    suction line near the evaporator coil and is connected to
    the MCM. It is factory set for 30°F and has an adjustable
    range of 25°F to 35°F.The compressors are staged “Off” as
    necessary to prevent icing. After the last compressor stage
    has been turned “Off”, the compressors will be allowed to
    restart once the evaporator temperature rises 10°F above
    the “coil frost cutout temperature” and the minimum three
    minute “Off” time has elapsed.
    Entering Evaporator Temperature Sensors
    Analog input devices used with CV and VAV applications.
    This device is used in conjunction with the Leaving Evaporator Temperature Sensor to prevent the unit from
    running compressors with insufficient charge.
    Filter Switch
    A binary input device used on CV and VAV applicationsthat measures the pressure differential across the unit
    filters. It is mounted in the filter section and is connected
    to the RTM. A diagnostic SERVICE signal is sent to the
    remote panel if the pressure differential across the filters
    is at least 0.5 w.c. The contacts will automatically open
    when the pressure differential across the filters decrease
    to 0.4 w.c. The switch differential can be field adjusted
    between 0.17 w.c. to 5.0 w.c. ± 0.05 w.c.
    Leaving Recovery Exhaust Temp Sensor
    Analog input device used on CV and VAV applications withEnergy Recovery option installed. It is used to monitor the
    temperature of the leaving air on the Exhaust Fan side of
    the energy recovery wheel. This temperature is used to
    determine if the temperature of the wheel is too cold as
    compared to the Recovery Frost Avoidance Setpoint. The
    result is used to determine when to enable energy wheel
    frost avoidance functions.
    Supply, Exhaust and Return Fan Airflow
    Proving Switches
    Supply Airflow Proving Switch is a binary input device
    used on CV and VAV applications to signal the RTM when
    the supply fan is operating. It is located in the supply fan
    section of the unit and is connected to the RTM. During a
    request for fan operation, if the differential switch is
    detected to be open for 40 consecutive seconds; compressor operation is turned “Off”, heat operation is
    turned “Off”, the request for supply fan operation is turned
    “Off” and locked out, exhaust dampers (if equipped) are
    “closed”, economizer dampers (if equipped) are “closed”, and a manual reset diagnostic is initiated.
    Exhaust/return Airflow Proving Switch is a binary input
    device used on all rooftop units equipped with an exhaust
    fan. It is located in the exhaust/return fan section of the unit
    and is connected to the RTM. During a request for fan
    operation, if the differential switch is detected to be open
    for 40 consecutive seconds, the economizer is closed to
    the minimum position setpoint, the request for exhaust
    fan operation is turned “Off” and locked out, and a manual
    reset diagnostic is initiated. The fan failure lockout can be
    reset at the Human Interface located in the unit control
    panel, by Tracer, or by cycling the control power to the
    RTM Off/On.
    Lead-Lag
    A selectable mode of operation through the HumanInterface. It alternates the starting between the first
    compressor of each refrigeration circuit. Only the
    compressor banks will switch, not the order of the
    compressors within a bank, providing the first compressor
    in each circuit had been activated during the same request
    for cooling.
    Charge Isolation
    During the OFF cycle, most of the charge is isolated
    between the compressor (internal) discharge check valves
    and liquid line solenoid valve. This reduces the OFF cycle
    charge migration, and liquid feedback during subsequent
    startup.The liquid line solenoid is energized (opened) with
    the start of the circuit compressor.
    Supply, Exhaust and Return Fan Circuit
    Breakers
    The supply fan and exhaust fan motors are protected by circuit breakers or fuses. They will trip and interrupt the
    power supply to the motors if the current exceeds the
    breakers “must trip” value. The rooftop module (RTM)
    will shut all system functions “Off” when an open fan
    proving switch is detected.
    Low Pressure Control
    Low Pressure Control is accomplished using a binary input
    device on CV and VAV applications. LP cutouts are located
    on the suction lines near the scroll compressors. The LPC
    contacts are designed to close when the suction pressure
    exceeds 41 ± 4 psig. If the LP control is open when a
    compressor is requested to start, none of the compressors
    on that circuit will be allowed to operate. They are locked
    out and a manual reset diagnostic is initiated.
    The LP cutouts are designed to open if the suction pressure approaches 22 ± 4 psig. If the LP cutout opens
    after a compressor has started, all compressors operating
    on that circuit will be turned off immediately and will 
    						
    							General Information
    RT-SVX24K-EN15
    remain off for a minimum of three minutes. If the LP cutout
    trips four consecutive times during the first three minutes
    of operation, the compressors on that circuit will be locked
    out and a manual reset diagnostic is initiated.
    Saturated Condenser Temperature Sensors
    Analog input devices used on CV and VAV applications
    mounted inside a temperature well located on a
    condenser tube bend. They monitor the saturated
    refrigerant temperature inside the condenser coil and are
    connected to the MCM. As the saturated refrigerant
    temperature varies due to operating conditions, the
    condenser fans are cycled “On” or “Off” as required to
    maintain acceptable operating pressures.
    Head Pressure Control
    Accomplished using two saturated refrigeranttemperature sensors on CV and VAV applications. During
    a request for compressor operation, when the condensing
    temperature rises above the “lower limit” of the
    controlband, the Compressor Module (MCM) starts
    sequencing condenser fans “On”. If the operating fans can
    not bring the condensing temperature to within the
    controlband, more fans are turned on. As the saturated
    condensing temperature approaches the lower limit of the
    controlband, fans are sequenced “Off”.
    The minimum “On/Off” time for condenser fan staging is 5.2 seconds. If the system is operating at a given fan stage
    below 100% for 30 minutes and the saturated condensing
    temperature is above the “efficiency check point” setting,
    a fan stage will be added. If the saturated condensing
    temperature falls below the “efficiency check point”
    setting, the fan control will remain at the present operating
    stage. If a fan stage cycles four times within a 10 minute
    period, the control switches from controlling to the “lower
    limit” to a temperature equal to the “lower limit” minus
    the “temporary low limit suppression” setting. It will
    utilize this new “low limit” temperature for one hour to
    reduce condenser fan short cycling.
    For evaporative condensing units, head pressure is
    monitored with pressure transducers attached to the
    saturated condensing line and converted to a temperature
    by the MPM. This temperature is used to control the
    variable speed fan and sump pump. When the
    temperature rises above the upper limit (120°F) the sump
    pump is energized. If the condensing temperature drops
    below the lower limit (70°F) the sump pump is de-
    energized.
    High Pressure Limit Controls
    High Pressure controls are located on the discharge lines
    near the scroll compressors. They are designed to open
    when the discharge pressure approaches 650 ± 10 psig.
    The controls reset automatically when the discharge pressure decreases to approximately 550 ± 10 psig.
    However, the compressors on that circuit are locked out
    and a manual reset diagnostic is initiated after the fourth
    occurrence of a high pressure condition.
    Outdoor Air Humidity Sensor
    An analog input device used on CV and VAV applicationswith 100% economizer. It monitors the outdoor humidity
    levels for economizer operation. It is mounted in the
    outside air intake section and is connected to the RTM.
    Return Air Humidity Sensor
    An analog input device used on CV and VAV applicationswith the comparative enthalpy option. It monitors the
    return air humidity level and compares it to the outdoor
    humidity level to establish which conditions are best
    suited to maintain the cooling requirements. It is mounted
    in the return air section and is connected to the ECEM.
    Space Humidity Sensor
    Analog input device used on CV and VAV applications withmodulating dehumidification option and/or
    humidification field installed option. It is used to monitor
    the humidity level in the space and compared to
    dehumidification and humidification setpoints to maintain
    space humidity requirements. It is field mounted in the
    space and connected to the RTM.
    Status/Annunciator Output
    An internal function within the RTM module on CV and
    VAV applications that provides:
    c. diagnostic and mode status signals to the remotepanel (LEDs) and to the Human Interface
    d. control of the binary Alarm output on the RTM
    e. control of the binary outputs on the GBAS module to inform the customer of the operational status
    and/or diagnostic conditions
    Low Ambient Compressor Lockout
    Utilizes an analog input device for CV and VAV
    applications. When the system is configured for low
    ambient compressor lockout, the compressors are not
    allowed to operate if the temperature of the outside air
    falls below the lockout setpoint. When the temperature
    rises 5°F above the lockout setpoint, the compressors are
    allowed to operate. The factory preset is 50°F.
    These compressors come equipped with a protection module that monitors phase loss, phase sequencing and
    motor temperature.
    Space Pressure Transducer
    An analog input device used on CV and VAV applicationswith the Statitrac option. It modulates the exhaust
    dampers to keep the space pressure within the building to
    a customer designated controlband. It is mounted on the
    bottom support below the return damper blade assembly
    and is connected to the ECEM. Field supplied pneumatic
    tubing must be connected between the space being
    controlled and the transducer assembly. 
    						
    							General Information
    16RT-SVX24K-EN
    Morning Warm-Up—Zone Heat
    When a system changes from an unoccupied to an
    occupied mode, or switches from STOPPED to AUTO, or
    power is applied to a unit with the MWU option, the heater
    in the unit or external heat will be brought on if the space
    temperature is below the MWU setpoint. The heat will
    remain on until the temperature reaches the MWU
    setpoint.
    If the unit is VAV, then the VAV box/unocc relay will
    continue to stay in the unoccupied position and the VFD
    output will stay at 100% during the MWU mode. When the
    MWU setpoint is reached and the heat mode is terminated,
    then the VAV box/unocc relay will switch to the occupied
    mode and the VFD output will be controlled by the duct
    static pressure. During Full Capacity MWU the economizer
    damper is held closed for as long as it takes to reach
    setpoint. During Cycling Capacity MWU the economizer
    damper is allowed to go to minimum position after one
    hour of operation if setpoint has not been reached.
    Compressor Motor Winding Thermostats
    A thermostat is embedded in the motor windings of eachScroll compressor. Each thermostat is designed to open if
    the motor windings exceed approximately 221°F. The
    thermostat will reset automatically when the winding
    temperature decreases to approximately 181°F.
    Rapid cycling, loss of charge, abnormally high suction
    temperatures, or the compressor running backwards
    could cause the thermostat to open. During a request for
    compressor operation, if the Compressor Module detects
    a problem outside of normal parameters, it turns any
    operating compressor(s) on that circuit “Off”, locks out all
    compressor operation for that circuit, and initiates a
    manual reset diagnostic (compressor trip).
    These compressors come equipped with a protection module that monitors phase loss, phase sequencing and
    motor temperature.
    Supply Air Temperature Low Limit
    Uses the supply air temperature sensor input to modulate
    the economizer damper to minimum position in the event
    the supply air temperature falls below the occupied
    heating setpoint temperature.
    Discharge Line Thermostat for Evaporative
    Condensers
    The first compressor on each circuit is equipped with aDischarge Line Thermostat. If the temperature of the line
    exceeds 210°F the thermostat interrupts the 115V circuit for
    the compressors and both of the compressors on that circuit will be de-energized. Once the temperature drops
    below 170°F the thermostat will close and allow the
    compressor to be energized.
    Freezestat
    A binary input device used on CV and VAV units with
    Hydronic Heat. It is mounted in the heat section and
    connected to the Heat Module. If the temperature of the air
    leaving the heating coil falls to 40°F, the normally open
    contacts on the freezestat closes signalling the Heat
    Module and the Rooftop Module (RTM) to:
    f. drive the Hydronic Heat Actuator to the full openposition
    Figure 5. Transducer voltage output vs. pressure input for supply, return and building pressure
    -0.75 to 9.0 Iwc Pressure Transducer Voltage Output vs. Pressure Input
    0.00 0.50
    1.00
    1.50
    2.00
    2.50
    3.00
    3.50
    4.00
    4.50
    -0. 75
    -0. 25
    0.2
    5
    0. 7
    5
    1. 2
    5
    1. 7
    5
    2. 2
    5
    2. 7
    5
    3. 2
    5
    3. 7
    5
    4. 2
    5
    4. 7
    5
    5. 2
    5
    5. 7
    5
    6. 2
    5
    6. 7
    5
    7. 2
    5
    7. 7
    5
    8. 2
    5
    8. 7
    5Pressure (inches w.c.)
    Volts 
    						
    							General Information
    RT-SVX24K-EN17
    g. turn the supply fan “Off”
    h. closes the outside air damper
    i. turns “On” the SERVICE light at the Remote Panel
    j. initiates a “Low Temp Limit” diagnostic to the
    Human Interface
    Compressor Circuit Breakers
    The Scroll Compressors are protected by circuit breakerswhich interrupt the power supply to the compressors if the
    current exceeds the breakers “must trip” value. During a
    request for compressor operation, if the Compressor
    Module detects a problem outside normal parameters, it
    turns any operating compressor(s) on that circuit “Off”,
    locks out all compressor operation for that circuit, and
    initiates a manual reset diagnostic (compressor trip).
    Constant Volume (CV) Units
    Zone Temperature—Cooling
    Relies on input from a sensor located directly in the space,
    while a system is in the occupied “Cooling” mode. It
    modulates the economizer (if equipped) and/or stages the
    mechanical cooling “On and Off” as required to maintain
    the zone temperature to within the cooling setpoint
    deadband.
    Zone Temperature—Heating
    Relies on input from a sensor located directly in the space,
    while a system is in the occupied “Heating” mode or an
    unoccupied period, to stage the heat “on and off” or to
    modulate the heating valve (hydronic heat only) as
    required to maintain the zone temperature to within the
    heating setpoint deadband. The supply fan will be
    requested to operate any time there is a request for heat.
    On gas heat units, the fan will continue to run for 60
    seconds after the furnace is turned off.
    Supply Air Tempering
    On CV units equipped with staged gas heat, if the supply
    air temperature falls 10°F below the occupied heating
    setpoint temperature while the heater is “Off”, the first
    stage of heat will be turned “On”.The heater is turned “Off”
    when the supply air temperature reaches 10°F above the
    occupied heating setpoint temperature.
    Variable Air Volume (VAV) Units
    Occupied Heating—Supply Air Temperature
    When a VAV unit is equipped with “Modulating Heat”, andthe system is in an occupied mode, and the field supplied
    changeover relay contacts have closed or per a BAS
    command, the supply air temperature will be controlled to
    the customer specified supply air heating setpoint. It will
    remain in the heating status until the changeover relay
    contacts are opened or BAS has released the heat
    command.
    Occupied Cooling—Supply Air Temperature
    When a VAV unit is in the occupied mode, the supply airtemperature will be controlled to the customer specified
    supply air cooling setpoint by modulating the economizer
    and/or staging the mechanical cooling “On and Off” as
    required.The changeover relay contacts must be open, or
    BAS command set to auto or cool, for the cooling to
    operate.
    Daytime Warm-up
    On VAV units equipped with heat, if the zone temperature
    falls below the daytime warm-up initiate temperature
    during the occupied mode, the system will switch to full
    airflow. During this mode, the VAV box/unocc relay will be
    energized (this is to signal the VAV boxes to go to 100%).
    After the VAV box max stroke time has elapsed (factory set at 6 minutes), the VFD output will be set to 100%. The
    airflow will be at 100% and the heat will be turned on to
    control to the occupied heating setpoint.
    When the zone temperature reaches the daytime warm-up termination setpoint, the heat will be turned off, the relay
    will be de-energized, releasing the VAV boxes, the VFD
    output will go back to duct static pressure control and the
    unit will return to discharge air control. If the occ zone
    heating setpoint is less than the DWU terminate setpoint,
    the heat will turn off when the occ zone heat setpoint is
    reached, but it will stay in DWU mode and cycle the heat
    to maintain setpoint.
    Unoccupied Heating—Zone Temperature
    When a VAV unit is equipped with gas, electric, or hydronicheat and is in the unoccupied mode, the zone temperature
    will be controlled to within the customer specified setpoint
    deadband. During an unoccupied mode for a VAV unit, the
    VAV box/unocc relay will be in the unoccupied position and the VFD output will be at 100%.This means that if there
    is a call for heat (or cool) and the supply fan comes on, it
    will be at full airflow and the VAV boxes in the space will
    need to be 100% open as signaled by the VAV box/unocc
    relay.
    Supply Air Tempering
    On VAV units equipped with “Modulating Heat” ,ifthe
    supply air temperature falls 10°F below the supply air
    temperature setpoint, the heat will modulate to maintain
    the supply air temperature to within the low end of the
    setpoint deadband.
    Supply Duct Static Pressure Control
    (Occupied)
    The RTM relies on input from the duct pressure transducer when a unit is equipped with a Variable Frequency Drive to
    set the supply fan speed to maintain the supply duct static
    pressure to within the static pressure setpoint deadband.
    The transducer compares supply duct pressure to ambient pressure. Refer to Figure 43, p. 67. 
    						
    							General Information
    18RT-SVX24K-EN
    Space Temperature Averaging
    Space temperature averaging for Constant Volume
    applications is accomplished by wiring a number of
    remote sensors in a series/parallel circuit.
    The fewest number of sensors required to accomplish space temperature averaging is four. The Space
    Temperature Averaging with Multiple Sensors figure illustrates a single sensor circuit (Single Zone), four
    sensors wired in a series/parallel circuit (Four Zone), nine
    sensors wired in a series/parallel circuit (Nine Zone). Any
    number squared, is the number of remote sensors
    required.
    Wiring termination will depend on the type of remote panel or control configuration for the system. Refer to the
    wiring diagrams that shipped with the unit.
    Figure 6. Transducer voltage output vs. pressure input
    with VCM and TRAQ™ sensing
    Transducer Voltage Output vs.   Pre ssure  Input
    0. 0 0. 5
    1. 0 1. 5 2. 0
    2. 5 3. 0 3. 5 4. 0
    -0.5 0. 0 0.5 1. 0 1. 5 2.0 2.5 3. 0 3.5 4. 0 4. 5 5.0 P r e ssu r e  ( i n c h e s w . c . )
    Volts
    Figure 7. Unit component layout and “ship with” locations
    Return/
    Exhaust Fan Outside Air
    Dampers
    Supply Fan Condenser
    Fans
    Compressor Section
    Heating
    Section
    Exhaust Damper Hood
    Evap Coil Evap Coil
    Controls
    Variable
    Frquency
    Drive (VFD)
    Filter Section
    Reheat Coil Option
    Outside Air Dampers
    Return Air Dampers
    Flue Vent  Access
    Variable
    Frquency
    Drive (VFD)
    Hot Water/Steam 
    Hydronic ConnectionOutside Air 
    Static Kit and sensors 
    						
    							General Information
    RT-SVX24K-EN19
    Unit Control Modules
    Unit control modules are microelectronic circuit boards
    designed to perform specific unit functions. The control
    modules, through proportional/integral control
    algorithms, provide the best possible comfort level for the
    customer. They are mounted in the control panel and are
    factory wired to their respective internal components.
    The control modules receive and interpret information from other unit modules, sensors, remote panels, and
    customer binary contacts to satisfy the applicable request
    for economizing, mechanical cooling, heating, and
    ventilation. Figure 9illustrates the typical location of each
    designated module. Figure 8. Space temperature averaging with multiple sensors 
    						
    							General Information
    20RT-SVX24K-EN
    Single Zone Variable Air Volume
    (SZVAV) Only
    The IntelliPak controls platform will support Single Zone
    VAV as an optional unit control type in order to meetASHRAE 90.1. The basic control will be a hybrid VAV/CV configured unit that provides discharge temperature
    control to a varying discharge air temperature target
    setpoint based on the space temperature and/or humidity
    conditions. Concurrently, the unit will control and optimize
    the supply fan speed to maintain the zone temperature to
    a zone temperature setpoint.
    Supply Fan Output Control
    Units configured for Single Zone VAV control will utilize
    the same supply fan output control scheme as on
    traditional VAV units except the VFD signal will be based
    on zone heating and cooling demand instead of the supply
    air pressure.
    VFD Control
    Single Zone VAV units will be equipped with a VFD-
    controlled supply fan which will be controlled via a 0-
    10VDC signal from the Rooftop Module (RTM). With the
    RTM supply fan output energized and the RTM VFD output at 0VDC, the fan speed output is 37% (22Hz) from the VFD
    by default; and at 10VDC the fan speed output is 100%
    (60Hz). The control scales the 0-10VDC VFD output from
    the RTM linearly to control between the 37-100% range.
    The VFD will modulate the supply fan motor speed, accelerating or decelerating as required to maintain the
    zone temperature to the zone temperature setpoint. When
    subjected to high ambient return conditions the VFD will
    reduce its output frequency to maintain operation. Bypass
    control is offered to provide full nominal airflow in the
    event of drive failure.
    Ventilation Control
    Units configured for Single Zone VAV control will require
    special handling of the OA Damper Minimum Position
    control in order to compensate for the non-linearity of
    airflow associated with the variable supply fan speed and
    damper combinations. Units configured for TRAQ with or
    without DCV will operate identically to traditional units
    with no control changes.
    Space Pressure Control
    For units configured with Space Pressure Control with or
    without Statitrac, the new schemes implemented for
    economizer minimum position handling require changes
    to the existing Space Pressure Control scheme in order to
    Figure 9. Control module locations
    BCI 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Intellipak 2 Service Manual