Trane Intellipak 2 Service Manual
Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Unit Startup RT-SVX24K-EN141 Figure 94. Operating pressure curve (all comp. and cond. fans per ckt. on)—90 tons high capacity Figure 95. Operating pressure curve (all comp. and cond. fans per ckt. on)—105 tons standard capacity
Unit Startup 142RT-SVX24K-EN Figure 96. Operating pressure curve (all comp. and cond. fans per ckt. on)—105 tons high capacity Figure 97. Operating pressure curve (all comp. and cond. fans per ckt. on)—120 tons standard capacity
Unit Startup RT-SVX24K-EN143 Figure 98. Operating pressure curve (all comp. and cond. fans per ckt. on)—120 tons high capacity Figure 99. Operating pressure curve (all comp. and cond. fans per ckt. on)—130 tons standard capacity
Unit Startup 144RT-SVX24K-EN Note:Due to the variable speed fans on evaporative condenser units, typical operating pressure curves are not relevant. If operating pressures at certain conditions are needed, contact a local Trane sales representative. Figure 100. Operating pressure curve (all comp. and cond. fans per ckt. on)—130 tons high capacity Figure 101. Operating pressure curve (all comp. and cond. fans per ckt. on)—150 tons standard capacity
Unit Startup RT-SVX24K-EN145 Components Standard Unit without Energy Recovery Wheel Economizer Damper Adjustment Exhaust Air Dampers Verify that the exhaust dampers (if equipped) close tightly when the unit is off. Adjust the damper linkage as necessary to ensure proper closure. An access panel is provided under each damper assembly. Outside Air & Return Air Damper Operation The outside air and return air damper linkage is accessible from the filter section of the unit. The damper linkage connecting the outside air dampers to the return air dampers is preset from the factory in the number 1 position. Refer to Figure 102, p. 146 for the appropriate linkage position for the unit and operating airflow (CFM). Note: Bridging between the unit main supports may consist of multiple 2 by 12 boards or sheet metal grating. Arbitrarily adjusting the outside air dampers to open fully when the return air dampers are closed or; failing to maintain the return air pressure drop with the outside air dampers when the return air dampers are closed, can overload the supply fan motor and cause building pressurization control problems due to improper CFM being delivered to the space. The outside air/return air damper linkage is connected to a crank arm with a series of holes that allows the installer or operator to modify the amount of outside air damper travel in order to match the return static pressure. Refer to Table 43, p. 148 for the equivalent return air duct losses that correspond to each of the holes illustrated in Figure 102, p. 146 . To Adjust the Outside Air Damper Travel: 1. Drill a 1/4 hole through the unit casing up stream of the return air dampers. Use a location that will produce an accurate reading with the least amount of turbulence. Several locations may be necessary, and average the reading. HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. 2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal block or the unit mounted disconnect switch. 3. Turn the 115 volt control circuit switch and the 24 volt control circuit switch to the “On” position. 4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the applicable programming manual for applications for the SERVICE TEST screens and programming instructions. 5. Use Table37, p.11 2to program the following system components for operation by scrolling through the displays; Supply Fan (On) V ariable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied) Outside Air Dampers (Closed) 6. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 7. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fan will begin to operate. 8. With the outside air dampers fully closed and the supply fan operating at 100% airflow requirements, WARNING No Step Surface! Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this recommendation could result in death or serious injury. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. WARNING Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury.
Unit Startup 146RT-SVX24K-EN measure the return static pressure at the location determined in step 1. 9. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. 10. Open the field supplied main power disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the “Open” position while working on the dampers. Note: Gravity will cause the damper to close. Support or secure the damper blades while removing the actuator to prevent unexpected damper rotation. 11. Compare the static pressure reading to the static pressure ranges and linkage positions in Table43, p. 148 for the unit size and operating CFM. To relocate the outside air/return air connecting rod to balance the outside air damper pressure drop against the return static pressure, use the following steps. If no adjustment is necessary, proceed to step 17. 12. Remove the drive rod and swivel from the crank arm(s). If only one hole requires changing, loosen only that end. 13. Manually open the return air dampers to the full open position. 14. Manually close the outside air dampers. 15. Reattach the drive rod and swivel to the appropriate hole(s). The length of the drive rod may need to be adjusted to align with the new hole(s) location. If so, loosen the lock nut on the drive rod against the swivel. Turn the swivel “in” or “out” to shorten or lengthen the rod as necessary. For some holes, both ends of the rod may need to be adjusted. 16. Tighten the lock nut against the swivel(s). 17. Plug the holes after the proper CFM has been established. Figure 102. Outside air and return air damper assembly Outside air damper level Configuration BConfiguration A All Top view Jackshaft lever Economizer Linkage Adjustment
Unit Startup RT-SVX24K-EN147 Figure 103. Outside air and return air economizer assembly (w/TRAQ™ dampers) TRAQ Damper Linkage Top view Jackshaft TRAQ damper
Unit Startup 148RT-SVX24K-EN Standard Unit with Energy Recovery Wheel Economizer Damper Adjustment - ERW units Outside & Return Air Damper Operation The outside air and return air damper actuators are accessible through from the filter section of the unit. The outside air and return air dampers have individual actuators that are linked electronically. The actuators are preset to 0 degrees from the factory. Refer to Table 44, p. 150 for the appropriate actuator position for the unit and operating airflow (CFM). To Adjust Damper Travel 1. Drill a 1/4 hole through the unit casing up stream of the return air dampers and below the energy recovery wheel. Use a location that will produce an accurate reading with the least amount of turbulence. Several locations may be necessary, and average the reading. HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. 2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal block or the unit mounted disconnect switch. 3. Turn the 115 volt control circuit switch and the 24 volt control circuit switch to the “On” position. 4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the applicable programming manual for applications for the SERVICE TEST screens and programming instructions. 5. Use Table 29, p. 77 to program the following system components for operation by scrolling through the displays: Supply Fan (On) VFD Cmd (100%, if applicable) RTM Occ/Unocc Output (Unoccupied) OA Damper Pos (0%) Outside Air Bypass Damper Pos (0%) Exhaust Air Bypass Damper Pos (0%) Table 43. Standard unit (no ERW) (economizer) outside air damper travel adjustment/pressure drop (inches w.c.) Damper Position Economizer Linkage Set-up 1 2 3 4 5 6 Jackshaft rod end location 1 1 2 2 2 2 Damper lever configuration A B B B B B Damper lever rod end location 1 2 3 4 5 6 120-162 Ton w/Economizer (includes mist eliminator) CFM Pressure Drop (inches w.c. ) 58500 0.80 1.64 2.96 - - - 54000 0.68 1.40 2.52 - - - 45500 0.48 0.99 1.79 2.22 2.62 - 42000 0.41 0.85 1.53 1.89 2.23 2.69 38000 0.34 0.69 1.25 1.55 1.83 2.20 34000 0.27 0.56 1.00 1.24 1.46 1.76 30000 0.21 0.43 0.78 0.97 1.14 1.37 90-118 Ton w/Economizer (includes mist eliminator) CFM Pressure Drop (inches w.c. ) 47250 0.81 1.88 - - - - 40500 0.60 1.39 2.62 - - - 36750 0.49 1.14 2.16 2.71 - - 31500 0.36 0.84 1.59 1.99 2.36 2.87 28000 0.28 0.66 1.25 1.57 1.87 2.27 25000 0.22 0.53 1.00 1.25 1.49 1.81 23000 0.19 0.45 0.85 1.06 1.26 1.53 Damper Position Jackshaft rod end location 1 1 1 2 1 Damper lever rod end location 1 2 3 5 4 Jackshaft rod end location 1 1 1 2 1 120-162 Ton w/TRAQ™ Damper (includes mist eliminator) CFM Pressure Drop ( inches w.c.) 58500 1.10 1.52 2.16 2.73 54000 0.93 1.28 1.83 2.33 45500 0.64 0.89 1.28 1.64 2.14 42000 0.54 0.75 1.09 1.40 1.83 38000 0.44 0.60 0.88 1.14 1.50 34000 0.35 0.47 0.69 0.90 1.20 30000 0.27 0.35 0.53 0.69 0.93 90-118 Ton w/TRAQ™ Damper (includes mist eliminator) CFM Pressure Drop ( inches w.c.) 47250 1.37 1.89 2.72 40500 0.99 1.35 1.97 2.54 36750 0.80 1.09 1.60 2.08 2.74 31500 0.58 0.77 1.15 1.51 2.01 28000 0.46 0.59 0.89 1.17 1.58 25000 0.37 0.45 0.69 0.92 1.24 23000 0.31 0.37 0.57 0.76 1.04 WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Unit Startup RT-SVX24K-EN149 6. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec. screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 7. Press the TEST START key to start the test. Rememberthat the delay designated in step 6 must elapse before the fan will begin to operate. 8. With the outside air dampers fully closed and the supply fan operating at 100% airflow requirements, measure the return static pressure at the location determined in step 1. 9. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. 10. Open the field supplied main power disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the “Open” position while working on the dampers. 11. Locate the static pressure reading in Table44, p. 150 and determine which damper needs to be adjusted and the degree reading. Proceed to the appropriate damper actuator procedure. To Adjust the Outside Air Damper Actuators: 12. Remove the shaft coupling from the damper shaft by loosening the bolt and removing the retainer clip. Be careful not to rotate the shaft. 13. Position the shaft coupling so that the indicator points to the degree value obtained from step 11. The shaft coupling is adjustable in 5 degree increments. 14. Replace the retainer clip and tighten the shaft coupling on the shaft (120-180 in-lbs). 15. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal block or the unit mounted disconnect switch. 16. Rotate the actuator control signal dial to Auto-Adapt. The actuator will drive open and then closed to determine the new open and closed positions. 17. Return the actuator control signal dial to 2-10 VDC Modulating input signal position. 18. Plug the holes drilled in the cabinet after the proper airfow has been established. To Adjust the Return Damper Actuators: 19. Support or secure the damper blades in the wide openposition. Note: Gravity will cause the damper to close. Support or secure the damper blades while removing the actuator to prevent unexpected damper rotation. 20. Do not remove the shaft coupling from the shaft. R emove the retainer clip from the shaft coupling. 21. Unscrew the actuator bracket from the damper wall. 22. Slide the actuator down the damper shaft off of the shaf t coupling. 23. Rotate the actuator and reinstall the shaft coupling in the actuator so that the indicator points to the degree value obtained in Step 11. The shaft coupling is adjustable in 5 degree increments. 24. Replace the retainer clip and remove the blade stops to allow the blades to rotate. 25. Rotate the actuator to the original position and reattach the actuator bracket to the damper wall. 26. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal block or the unit mounted disconnect switch. 27. Rotate the actuator control signal dial to Auto-Adapt. The actuator will drive open and then closed to determine the new open and closed positions. 28. Return the actuator control signal dial to the factory set input signal position. 29. Plug the holes drilled in the cabinet after the proper airfow has been established. WARNING Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury.
Unit Startup 150RT-SVX24K-EN Table 44. Standard units with ERW — field measured plenum pressureLow CFM ERW — 90-162 Tons 90/100 Ton Low CFM ERW - Field measured plenum pressure (inches wc) OA Actuator Reading [Degrees] RA Actuator Reading [Degrees] 60 50 40 30 20 10 0 10 20 30 35 40 45 50 CFM Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T E/T 16000 1.29 — 0.87 1.52 0.71 1.05 0.64 0.84 0.60 0.64 0.58 0.63 0.46 0.45 0.43 0.41 0.38 0.35 0.32 0.20 20000 1.99 — 1.34 2.34 1.09 1.62 0.98 1.28 0.92 0.97 0.89 0.96 0.69 0.68 0.65 0.62 0.57 0.52 0.48 0.29 25000 — — 2.07 — 1.68 2.49 1.50 1.97 1.41 1.49 1.36 1.47 1.04 1.02 0.99 0.93 0.86 0.78 0.71 0.42 30000 — — 2.94 — 2.39 — 2.13 2.79 1.99 2.09 1.93 2.08 1.46 1.43 1.37 1.30 1.19 1.08 0.98 0.56 33000 ———— 2.86 — 2.54 — 2.38 2.50 2.30 2.48 1.73 1.70 1.63 1.54 1.41 1.28 1.15 0.65 36000 —————— 3.00 — 2.80 2.94 2.71 2.92 2.02 1.98 1.91 1.79 1.64 1.48 1.34 0.74 40000 ———————————— 2.46 2.41 2.32 2.18 1.98 1.79 1.61 0.87105/118 Ton Low CFM ERW - Field measured plenum pressure (inches wc) OA Actuator Reading [Degrees] RA Actuator Reading [Degrees] 60 50 40 30 20 10 0 10 20 30 35 40 45 50 CFM Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T E/T 19000 1.80 — 1.22 2.12 0.99 1.46 0.89 1.16 0.83 0.88 0.81 0.88 0.63 0.62 0.59 0.56 0.52 0.48 0.44 0.27 23000 2.63 — 1.76 — 1.44 2.12 1.29 1.68 1.21 1.27 1.17 1.26 0.90 0.88 0.85 0.80 0.74 0.68 0.62 0.37 28000 — — 2.57 — 2.09 — 1.86 2.45 1.74 1.84 1.69 1.82 1.28 1.25 1.21 1.14 1.05 0.95 0.86 0.50 33000 ———— 2.86 — 2.54 2.38 2.50 2.30 2.48 1.73 1.70 1.63 1.54 1.41 1.28 1.15 0.65 38000 ———————————— 2.24 2.20 2.11 1.98 1.81 1.64 1.48 0.81 43000 ———————————— 2.80 2.74 2.64 2.47 2.25 2.03 1.83 0.97 45000 ———————————— 3.04 2.98 2.86 2.68 2.44 2.20 1.97 1.04120/128 Ton Low CFM ERW - Field measured plenum pressure (inches wc) OA Actuator Reading [Degrees] RA Actuator Reading [Degrees] 60 50 40 30 20 10 0 10 20 30 35 40 45 50 CFM Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T E/T 21000 1.54 — 1.08 1.69 0.90 1.08 0.82 0.89 0.78 0.87 0.76 0.75 0.58 0.56 0.54 0.50 0.44 0.39 0.34 0.14 26000 2.33 — 1.62 2.56 1.35 1.62 1.23 1.33 1.16 1.30 1.13 1.11 0.84 0.82 0.78 0.72 0.64 0.56 0.49 — 31000 — — 2.26 — 1.88 2.25 1.70 1.85 1.61 1.80 1.56 1.53 1.15 1.12 1.07 0.98 0.87 0.75 0.65 — 36000 — — 2.99 — 2.48 2.98 2.24 2.44 2.11 2.37 2.05 2.00 1.50 1.46 1.38 1.27 1.11 0.96 0.81 — 41000 —————— 2.85 — 2.68 — 2.60 2.54 1.89 1.84 1.74 1.59 1.39 1.19 1.00 — 46000 ———————————— 2.31 2.24 2.12 1.93 1.68 1.42 1.19 — 51000 ———————————— 2.77 2.69 2.54 2.31 2.00 1.69 1.40 — 54000 ———————————— 3.16 3.06 2.89 2.64 2.29 1.94 1.61 —continued on next page