Home > Trane > Air Conditioner > Trane Intellipak 2 Service Manual

Trane Intellipak 2 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Unit Startup
    RT-SVX24K-EN141
    Figure 94. Operating pressure curve (all comp. and cond. fans per ckt. on)—90 tons high capacity
    Figure 95. Operating pressure curve (all comp. and cond. fans per ckt. on)—105 tons standard capacity 
    						
    							Unit Startup
    142RT-SVX24K-EN
    Figure 96. Operating pressure curve (all comp. and cond. fans per ckt. on)—105 tons high capacity
    Figure 97. Operating pressure curve (all comp. and cond. fans per ckt. on)—120 tons standard capacity 
    						
    							Unit Startup
    RT-SVX24K-EN143
    Figure 98. Operating pressure curve (all comp. and cond. fans per ckt. on)—120 tons high capacity
    Figure 99. Operating pressure curve (all comp. and cond. fans per ckt. on)—130 tons standard capacity 
    						
    							Unit Startup
    144RT-SVX24K-EN
    Note:Due to the variable speed fans on evaporative
    condenser units, typical operating pressure curves
    are not relevant. If operating pressures at certain
    conditions are needed, contact a local Trane sales
    representative.
    Figure 100. Operating pressure curve (all comp. and cond. fans per ckt. on)—130 tons high capacity
    Figure 101. Operating pressure curve (all comp. and cond. fans per ckt. on)—150 tons standard capacity 
    						
    							Unit Startup
    RT-SVX24K-EN145
    Components
    Standard Unit without Energy Recovery
    Wheel
    Economizer Damper Adjustment
    Exhaust Air Dampers
    Verify that the exhaust dampers (if equipped) close tightly
    when the unit is off. Adjust the damper linkage as
    necessary to ensure proper closure. An access panel is
    provided under each damper assembly.
    Outside Air & Return Air Damper Operation
    The outside air and return air damper linkage is accessible from the filter section of the unit. The damper linkage
    connecting the outside air dampers to the return air
    dampers is preset from the factory in the number 1
    position. Refer to Figure 102, p. 146 for the appropriate
    linkage position for the unit and operating airflow (CFM).
    Note: Bridging between the unit main supports may
    consist of multiple 2 by 12 boards or sheet metal
    grating.
    Arbitrarily adjusting the outside air dampers to open fully when the return air dampers are closed or; failing to
    maintain the return air pressure drop with the outside air
    dampers when the return air dampers are closed, can
    overload the supply fan motor and cause building
    pressurization control problems due to improper CFM
    being delivered to the space.
    The outside air/return air damper linkage is connected to a crank arm with a series of holes that allows the installer
    or operator to modify the amount of outside air damper
    travel in order to match the return static pressure. Refer to
    Table 43, p. 148 for the equivalent return air duct losses
    that correspond to each of the holes illustrated in
    Figure 102, p. 146 .
    To Adjust the Outside Air Damper Travel:
    1. Drill a 1/4 hole through the unit casing up stream of
    the return air dampers. Use a location that will produce
    an accurate reading with the least amount of
    turbulence. Several locations may be necessary, and
    average the reading. HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
    UNIT DISCONNECT SWITCH.
    2. Close the disconnect switch or circuit protector switch
    that provides the supply power to the unit terminal
    block or the unit mounted disconnect switch.
    3. Turn the 115 volt control circuit switch and the 24 volt control
     circuit switch to the “On” position.
    4. Open the Human Interface access door, located in the unit
     control panel, and press the SERVICE MODE key to
    display the first service screen. Refer to the latest
    edition of the applicable programming manual for
    applications for the SERVICE TEST screens and
    programming instructions.
    5. Use Table37, p.11 2to program the following system
    components for operation by scrolling through the
    displays;
    Supply Fan (On)
    V
     ariable Frequency Drive (100% Output, if applicable)
    RTM Occ/Unocc Output (Unoccupied)
    Outside Air Dampers (Closed)
    6. Once the configuration for the components is complete,
     press the NEXT key until the LCD displays
    the “Start test in __Sec.” screen. Press the + key to
    designate the delay before the test is to start. This
    service test will begin after the TEST START key is
    pressed and the delay designated in this step has
    elapsed. Press the ENTER key to confirm this choice.
    7. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before
    the fan will begin to operate.
    8. With the outside air dampers fully closed and the supply
     fan operating at 100% airflow requirements,
    WARNING
    No Step Surface!
    Do not walk on the sheet metal drain pan. Walking on
    the drain pan could cause the supporting metal to
    collapse, resulting in the operator/technician to fall.
    Failure to follow this recommendation could result in
    death or serious injury.
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury.
    WARNING
    Rotating Components!
    During installation, testing, servicing and
    troubleshooting of this product it may be necessary to
    work with live and exposed rotating components. Have
    a qualified or licensed service individual who has been
    properly trained in handling exposed rotating
    components, perform these tasks. Failure to follow all
    safety precautions could result in rotating components
    cutting and slashing technician which could result in
    death or serious injury. 
    						
    							Unit Startup
    146RT-SVX24K-EN
    measure the return static pressure at the location
    determined in step 1.
    9. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the fan operation.
    10. Open the field supplied main power disconnect switch upstream
     of the rooftop unit. Lock the disconnect
    switch in the “Open” position while working on the
    dampers.
    Note: Gravity
     will cause the damper to close. Support or
    secure the damper blades while removing the
    actuator to prevent unexpected damper rotation.
    11. Compare the static pressure reading to the static pressure
     ranges and linkage positions in Table43,
    p. 148 for the unit size and operating CFM.
    To relocate the outside air/return air connecting rod to balance
     the outside air damper pressure drop against the
    return static pressure, use the following steps. If no
    adjustment is necessary, proceed to step 17.
    12. Remove the drive rod and swivel from the crank arm(s).
     If only one hole requires changing, loosen only
    that end.
    13. Manually open the return air dampers to the full open position.
    14. Manually close the outside air dampers.
    15. Reattach the drive rod and swivel to the appropriate hole(s).
     The length of the drive rod may need to be
    adjusted to align with the new hole(s) location. If so,
    loosen the lock nut on the drive rod against the swivel.
    Turn the swivel “in” or “out” to shorten or lengthen the rod as necessary. For some holes, both ends of the rod
    may need to be adjusted.
    16. Tighten the lock nut against the swivel(s).
    17. Plug the holes after the proper CFM has been established.
    Figure 102. Outside air and return air damper assembly
    Outside air damper level
    Configuration BConfiguration A
    All Top view
    Jackshaft lever
    Economizer Linkage Adjustment 
    						
    							Unit Startup
    RT-SVX24K-EN147
    Figure 103. Outside air and return air economizer
    assembly (w/TRAQ™ dampers)
    TRAQ Damper Linkage 
    Top view
    Jackshaft 
    TRAQ damper  
    						
    							Unit Startup
    148RT-SVX24K-EN
    Standard Unit with Energy Recovery
    Wheel
    Economizer Damper Adjustment - ERW units
    Outside & Return Air Damper Operation
    The outside air and return air damper actuators are
    accessible through from the filter section of the unit. The
    outside air and return air dampers have individual
    actuators that are linked electronically. The actuators are
    preset to 0 degrees from the factory. Refer to Table 44,
    p. 150 for the appropriate actuator position for the unit and
    operating airflow (CFM).
    To Adjust Damper Travel
    1. Drill a 1/4 hole through the unit casing up stream of the return air dampers and below the energy recovery
    wheel. Use a location that will produce an accurate
    reading with the least amount of turbulence. Several
    locations may be necessary, and average the reading.
    HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
    UNIT DISCONNECT SWITCH.
    2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal
    block or the unit mounted disconnect switch.
    3. Turn the 115 volt control circuit switch and the 24 volt control
     circuit switch to the “On” position.
    4. Open the Human Interface access door, located in the unit
     control panel, and press the SERVICE MODE key to
    display the first service screen. Refer to the latest
    edition of the applicable programming manual for
    applications for the SERVICE TEST screens and
    programming instructions.
    5. Use Table 29, p. 77 to program the following system components
     for operation by scrolling through the
    displays:
    Supply Fan (On)
    VFD
     Cmd (100%, if applicable)
    RTM Occ/Unocc Output
    (Unoccupied)
    OA Damper Pos (0%)
    Outside Air Bypass Damper Pos (0%)
    Exhaust Air Bypass Damper Pos (0%)
    Table 43. Standard unit (no ERW) (economizer) outside
    air damper travel adjustment/pressure drop
    (inches w.c.)
    Damper Position
    Economizer 
    Linkage Set-up 1 2 3 4 5 6
    Jackshaft rod end location 1 1 2 2 2 2
    Damper lever  configuration A B B B B B
    Damper lever 
    rod end location 1 2 3 4 5 6
    120-162 Ton w/Economizer (includes mist eliminator) CFM Pressure Drop (inches w.c. )
    58500 0.80 1.64 2.96 - - -
    54000 0.68 1.40 2.52 - - -
    45500 0.48 0.99 1.79 2.22 2.62 -
    42000 0.41 0.85 1.53 1.89 2.23 2.69
    38000 0.34 0.69 1.25 1.55 1.83 2.20
    34000 0.27 0.56 1.00 1.24 1.46 1.76
    30000 0.21 0.43 0.78 0.97 1.14 1.37
    90-118 Ton w/Economizer (includes mist eliminator)
    CFM Pressure Drop (inches w.c. )
    47250 0.81 1.88 - - - -
    40500 0.60 1.39 2.62 - - -
    36750 0.49 1.14 2.16 2.71 - -
    31500 0.36 0.84 1.59 1.99 2.36 2.87
    28000 0.28 0.66 1.25 1.57 1.87 2.27
    25000 0.22 0.53 1.00 1.25 1.49 1.81
    23000 0.19 0.45 0.85 1.06 1.26 1.53
    Damper Position
    Jackshaft rod  end location 1 1 1 2 1
    Damper lever 
    rod end location 1 2 3 5 4
    Jackshaft rod end location 1 1 1 2 1
    120-162 Ton w/TRAQ™ Damper (includes mist  eliminator)
    CFM Pressure Drop ( inches w.c.)
    58500 1.10 1.52 2.16 2.73
    54000 0.93 1.28 1.83 2.33
    45500 0.64 0.89 1.28 1.64 2.14
    42000 0.54 0.75 1.09 1.40 1.83
    38000 0.44 0.60 0.88 1.14 1.50
    34000 0.35 0.47 0.69 0.90 1.20
    30000 0.27 0.35 0.53 0.69 0.93
    90-118 Ton w/TRAQ™ Damper (includes mist 
    eliminator)
    CFM Pressure Drop ( inches w.c.)
    47250 1.37 1.89 2.72
    40500 0.99 1.35 1.97 2.54
    36750 0.80 1.09 1.60 2.08 2.74
    31500 0.58 0.77 1.15 1.51 2.01
    28000 0.46 0.59 0.89 1.17 1.58
    25000 0.37 0.45 0.69 0.92 1.24
    23000 0.31 0.37 0.57 0.76 1.04
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury. 
    						
    							Unit Startup
    RT-SVX24K-EN149
    6. Once the configuration for the components is
    complete, press the NEXT key until the LCD displays
    the “Start test in __Sec. screen. Press the + key to
    designate the delay before the test is to start. This
    service test will begin after the TEST START key is
    pressed and the delay designated in this step has
    elapsed. Press the ENTER key to confirm this choice.
    7. Press the TEST START key to start the test. Rememberthat the delay designated in step 6 must elapse before
    the fan will begin to operate.
    8. With the outside air dampers fully closed and the supply
     fan operating at 100% airflow requirements,
    measure the return static pressure at the location
    determined in step 1.
    9. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the fan operation.
    10. Open the field supplied main power disconnect switch upstream
     of the rooftop unit. Lock the disconnect
    switch in the “Open” position while working on the
    dampers.
    11. Locate the static pressure reading in Table44, p. 150
    and determine which damper needs to be adjusted and
    the
     degree reading. Proceed to the appropriate damper
    actuator procedure.
    To Adjust the Outside Air Damper Actuators:
    12. Remove the shaft coupling from the damper shaft by loosening the bolt and removing the retainer clip. Be
    careful not to rotate the shaft.
    13. Position the shaft coupling so that the indicator points to
     the degree value obtained from step 11. The shaft
    coupling is adjustable in 5 degree increments.
    14. Replace the retainer clip and tighten the shaft coupling on
     the shaft (120-180 in-lbs).
    15. Close the disconnect switch or circuit protector switch that
     provides the supply power to the unit terminal
    block or the unit mounted disconnect switch.
    16. Rotate the actuator control signal dial to Auto-Adapt. The
     actuator will drive open and then closed to
    determine the new open and closed positions.
    17. Return the actuator control signal dial to 2-10 VDC Modulating
     input signal position. 18. Plug the holes drilled in the cabinet after the proper
    airfow
     has been established.
    To Adjust the Return Damper Actuators:
    19. Support or secure the damper blades in the wide openposition.
    Note: Gravity
     will cause the damper to close. Support or
    secure the damper blades while removing the
    actuator to prevent unexpected damper rotation.
    20. Do not remove the shaft coupling from the shaft. R
     emove the retainer clip from the shaft coupling.
    21. Unscrew the actuator bracket from the damper wall.
    22. Slide the actuator down the damper shaft off of the shaf
     t coupling.
    23. Rotate the actuator and reinstall the shaft coupling in the
     actuator so that the indicator points to the degree
    value obtained in Step 11. The shaft coupling is
    adjustable in 5 degree increments.
    24. Replace the retainer clip and remove the blade stops to allow
     the blades to rotate.
    25. Rotate the actuator to the original position and reattach the
     actuator bracket to the damper wall.
    26. Close the disconnect switch or circuit protector switch that
     provides the supply power to the unit terminal
    block or the unit mounted disconnect switch.
    27. Rotate the actuator control signal dial to Auto-Adapt. The
     actuator will drive open and then closed to
    determine the new open and closed positions.
    28. Return the actuator control signal dial to the factory set input
     signal position.
    29. Plug the holes drilled in the cabinet after the proper airfow
     has been established.
    WARNING
    Rotating Components!
    During installation, testing, servicing and
    troubleshooting of this product it may be necessary to
    work with live and exposed rotating components. Have
    a qualified or licensed service individual who has been
    properly trained in handling exposed rotating
    components, perform these tasks. Failure to follow all
    safety precautions could result in rotating components
    cutting and slashing technician which could result in
    death or serious injury. 
    						
    							Unit Startup
    150RT-SVX24K-EN
    Table 44. Standard units with ERW — field measured plenum pressureLow CFM ERW — 90-162 Tons
    90/100 Ton Low CFM ERW - Field measured plenum pressure (inches wc)
    OA Actuator Reading [Degrees]  RA Actuator Reading [Degrees]
    60
    50
    40
    30
    20
    10
    0
    10
    20
    30
    35
    40
    45
    50
    CFM
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    E/T
    E/T
    E/T
    E/T
    E/T
    E/T
    E/T
    E/T
    16000 1.29 — 0.87 1.52 0.71 1.05 0.64 0.84 0.60 0.64 0.58 0.63 0.46 0.45 0.43 0.41 0.38 0.35 0.32 0.20
    20000 1.99 — 1.34 2.34 1.09 1.62 0.98 1.28 0.92 0.97 0.89 0.96 0.69 0.68 0.65 0.62 0.57 0.52 0.48 0.29
    25000 — — 2.07 — 1.68 2.49 1.50 1.97 1.41 1.49 1.36 1.47 1.04 1.02 0.99 0.93 0.86 0.78 0.71 0.42
    30000 — — 2.94 — 2.39 — 2.13 2.79 1.99 2.09 1.93 2.08 1.46 1.43 1.37 1.30 1.19 1.08 0.98 0.56
    33000 ———— 2.86 — 2.54 — 2.38 2.50 2.30 2.48 1.73 1.70 1.63 1.54 1.41 1.28 1.15 0.65
    36000 —————— 3.00 — 2.80 2.94 2.71 2.92 2.02 1.98 1.91 1.79 1.64 1.48 1.34 0.74
    40000 ———————————— 2.46 2.41 2.32 2.18 1.98 1.79 1.61 0.87105/118 Ton Low CFM ERW - Field measured plenum pressure (inches wc)
    OA Actuator Reading [Degrees]  RA Actuator Reading [Degrees]
    60
    50
    40
    30
    20
    10
    0
    10
    20
    30
    35
    40
    45
    50
    CFM
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    E/T
    E/T
    E/T
    E/T
    E/T
    E/T
    E/T
    E/T
    19000 1.80 — 1.22 2.12 0.99 1.46 0.89 1.16 0.83 0.88 0.81 0.88 0.63 0.62 0.59 0.56 0.52 0.48 0.44 0.27
    23000 2.63 — 1.76 — 1.44 2.12 1.29 1.68 1.21 1.27 1.17 1.26 0.90 0.88 0.85 0.80 0.74 0.68 0.62 0.37
    28000 — — 2.57 — 2.09 — 1.86 2.45 1.74 1.84 1.69 1.82 1.28 1.25 1.21 1.14 1.05 0.95 0.86 0.50
    33000 ———— 2.86 — 2.54 2.38 2.50 2.30 2.48 1.73 1.70 1.63 1.54 1.41 1.28 1.15 0.65
    38000 ———————————— 2.24 2.20 2.11 1.98 1.81 1.64 1.48 0.81
    43000 ———————————— 2.80 2.74 2.64 2.47 2.25 2.03 1.83 0.97
    45000 ———————————— 3.04 2.98 2.86 2.68 2.44 2.20 1.97 1.04120/128 Ton Low CFM ERW - Field measured plenum pressure (inches wc)
    OA Actuator Reading [Degrees]  RA Actuator Reading [Degrees]
    60
    50
    40
    30
    20
    10
    0
    10
    20
    30
    35
    40
    45
    50
    CFM
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    Econ
    TRAQ
    E/T
    E/T
    E/T
    E/T
    E/T
    E/T
    E/T
    E/T
    21000 1.54 — 1.08 1.69 0.90 1.08 0.82 0.89 0.78 0.87 0.76 0.75 0.58 0.56 0.54 0.50 0.44 0.39 0.34 0.14
    26000 2.33 — 1.62 2.56 1.35 1.62 1.23 1.33 1.16 1.30 1.13 1.11 0.84 0.82 0.78 0.72 0.64 0.56 0.49 —
    31000 — — 2.26 — 1.88 2.25 1.70 1.85 1.61 1.80 1.56 1.53 1.15 1.12 1.07 0.98 0.87 0.75 0.65 —
    36000 — — 2.99 — 2.48 2.98 2.24 2.44 2.11 2.37 2.05 2.00 1.50 1.46 1.38 1.27 1.11 0.96 0.81 —
    41000 —————— 2.85 — 2.68 — 2.60 2.54 1.89 1.84 1.74 1.59 1.39 1.19 1.00 —
    46000 ———————————— 2.31 2.24 2.12 1.93 1.68 1.42 1.19 —
    51000 ———————————— 2.77 2.69 2.54 2.31 2.00 1.69 1.40 —
    54000 ———————————— 3.16 3.06 2.89 2.64 2.29 1.94 1.61 —continued on next page 
    						
    All Trane manuals Comments (0)