Trane Intellipak 2 Service Manual
Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Unit Startup RT-SVX24K-EN101 Set Drain Duration Timer Enter service test mode from unit Human Interface. Navigate to the compressor condenser fan submenu. Under head pressure control, use manual control. Close drain valve and energize water inlet solenoid valve until water reaches nominal level. Once level is achieved, de-energize fill solenoid. Open drain valve and time how long it takes for the water level to drop one inch, make sure to take into account the closing time of the valve. Chemical Water Treatment Tree TheTrane evaporative condenser comes with a PVC tree to allow easier inputs for third party water treatment.The tee labeled A is a ¾ inch NPT threaded input, see Figure 65. Tees B and C are 1/2 inch NPT threaded inputs. The ball valve can be used to stop the water flow through the tree to allow the customer to add hookup of water treatment, or to change and update water treatment with the unit running. Units with Dolphin WaterCare™or conductivity sensor will have the conductivity sensor installed into the ¾ inch tee with the other tees plugged. For all other units, A, B and C will be plugged, see Figure 65. Ensure the ball valve is in the open position when water treatment is being operated in the system to make sure water flows through the tree and transports treatment to the unit sump. Conductivity Controller Upon startup, the conductivity controller must be calibrated and setup for operation. Below are the necessary steps to accomplish those tasks. The controller has two setpoints that control two relays. Both of these setpoints will need to be set by Dolphin or a local water treatment expert. 1. The first setpoint is the standard point blowdown point. – When the setpoint is exceeded the relay (K1) will beenergized and a blowdown request will close the Water treatment request binary input on the MCM. Figure 63. Actuator shaft adapter removal/assembly Figure 64. Actuator is shipped in “Drain during power loss” configuration Locking clip Shaft adapter 1 2 To drain during power loss, set shaft adapter to 0 degrees To hold during power loss, set shaft adapter to 90 degrees Figure 65. Chemical water treatment tree
Unit Startup 10 2RT-SVX24K-EN 2. The second setpoint will be the emergency point – The second setpoint will open the normally closedK2 relay which will interrupt the sump proving circuit which will generate a manual lockout. This second setpoint will be used to protect the unit from extremely high conductivity that would indicate a failure in the system. 3. Inside the enclosure for the controller, there will be a thermostat and strip heater that will protect LCD from cracking at low ambient conditions. The thermostat closes at 15°F and opens at 25°F. Procedure to calibrate conductivity Note: Visit this webpage for additional documentation: Use a calibrated thermometer and a known conductivity rating. There are two different options for having a liquid with known conductivity. Purchase a liquid with known conductivity rating and purchase a handheld conductivity reader. 1. Close the ball valve on the chemical treatment tree and remove the conductivity sensor from the tree. 2. Enter service test mode on the unit and turn the pump on, ensuring the compressors are set to Off. 3. With the conductivity controller connected to the sensor and power, enter the CALIBRATE menu by holding down the enter key for 2 seconds. 4. When asked for the calibration key code, hit the UP-UP- UP -DOWN arrow keys in sequence. 5. Using the UP and DOWN arrows go to Chan 1 Cell: Standard. Ensure this channel is set to standard. 6. If not press the RIGHT arrow key and set to standard then press the ENTER key to return to the CALIBRATION menu. 7. Using the UP and DOWN arrows go to Chan 1 Cell. Ensure that the cell constant is set to 1.0. 8. If not press the RIGHT arrow key and set the cell constant to 1.0 then press the ENTER key to return to the CALIBRATION menu. 9. Using the UP and DOWN arrows go to Chan 1 Set: T emperature and press the RIGHT arrow key to enter the edit mode. 10. Adjust the temperature on the controller to match the actual temperature. 11. Press the ENTER key to save the input and return to the CALIBRA TE menu. 12. Using the UP and DOWN arrows, go to the Chan 1 Set: Conducti vity and press the RIGHT arrow key to enter the edit mode. 13. Adjust the conductivity on the controller to match the actual conductivity rating of the liquid. 14. Press the ENTER key to save the conductivity rating and return to the CALIBRATE menu. 15. When finished calibrating the controller, press the UP and DOWN key simultaneously to return to normal operating mode. Procedure to set purge setpoints on the conductivity controller Note: Visit this webpage for additional documentation: Work with local water treatment expert to identify nominal purge and emergency purge conductivity value. 1. Close the ball valve on the chemical treatment tree and remove the conductivity sensor from the tree. 2. Enter Service test mode on the unit HI and energize the sump pump, ensuring the compressors are set to OFF. 3. With the conductivity controller connected to the sensor and power, enter the CALIBRATE menu by holding down the enter key for 2 seconds. 4. When asked for the calibration key code, hit the UP-UP- UP -DOWN arrow keys in sequence. 5. Using the UP and DOWN arrows, go to Relay 1 S etpoint: and press the RIGHT arrow key to enter edit mode (K1). 6. Adjust the set point to the nominal blowdown conducti vity value. 7. Press the ENTER key to return to the CALIBRATE menu. 8. Using the UP and DOWN arrows, go to Relay 2 S etpoint: and press the RIGHT arrow key to enter edit mode (K2). 9. Adjust the set point to the emergency conductivity value. 10. Press the ENTER key to return to the CALIBRATE menu. 11. When finished setting the values, press the UP and DO WN key simultaneously to return to normal operating mode. Units Without an Economizer Upon entering an “occupied” mode of operation, the RTM receives input from the remote panel to start the supply fan. For constant volume applications, the RTM supply fan contacts close which energizes the supply fan contactor. When the supply fan starts, the fan proving switch closes, signaling the RTM that airflow has been established and the VFD will begin to ramp the fan (if equipped). When a cooling request is sent to the RTM from a zone temperature sensor, the RTM evaluates the operating condition of the system using the supply air temperature input and the outdoor temperature input before sending the request to the MCM. Once the request is sent to the MCM, the compressor module checks the compressor
Unit Startup RT-SVX24K-EN10 3 protection circuit before closing “Stage 1. After the first functional stage has started, the compressor module monitors the saturated refrigerant temperature and closes the condenser fan output contact, when the saturated refrigerant temperature rises above the “lower limit” setpoint. Units with an Economizer Upon entering an “occupied” mode of operation, the RTM receives input from the remote panel to start the supply fan. For constant volume applications, the RTM supply fan contacts close which energizes the supply fan contactor. When the supply fan starts, the fan proving switch closes, signaling the RTM that airflow has been established. The RTM opens the economizer dampers to the specified “minimum position”. When a cooling request is sent to the RTM from the zone temperature sensor, the RTM evaluates the operating condition of the system using the supply air temperature input and the outdoor temperature input before sending the request to the MCM for mechanical cooling. If the outdoor conditions are suitable for cooling (temperature and humidity are within specified setpoints), the RTM will attempt to maintain the zone temperature without using any compressors. If the zone temperature can not be maintained within the setpoint deadband, the RTM sends a cooling request to the MCM. The compressor module checks the compressor protection circuit before closing “Stage 1. After the first functional stage has started, the compressor module monitors the saturated refrigerant temperature and closes the condenser fan output contact, when the saturated refrigerant temperature rises above the “lower limit” setpoint. Units with TRAQ™ Sensor The outside air enters the unit through the TRAQ Sensor assemblies and is measured by velocity pressure flow rings. The velocity pressure flow rings are connected to a pressure transducer/solenoid assemblies. The solenoid is used for calibration purposes to compensate for temperature swings that could affect the transducer. The Ventilation Control Module (VCM) utilizes the velocity pressure inputs, the RTM outdoor air temperature input, and the minimum outside air CFM setpoint to modify the volume (CFM) of outside air entering the unit as the measured airflow deviates from setpoint. When the optional temperature sensor is installed and the Preheat function is enabled, the sensor will monitor the combined (averaged) outside air and return air temperatures. As this mixed air temperature falls below the Preheat Actuate Temperature Setpoint, the VCM will activate the preheat binary output used to control a field installed heater. The output will be deactivated when the temperature rises 5 above the Preheat Actuate Temperature Setpoint. When the optional CO 2sensor is installed and DCV is enabled, the OA damper will be modulated to control CO 2 concentrations. If the CO2concentration is greater than the Design Minimum CO 2Setpoint the OA damper will be opened to the Design Minimum OA Damper Setpoint (w/ oTRAQ) or until the Design Minimum OA Flow Setpoint is met (w/ TRAQ). If the CO 2concentration is less than the DCV Minimum CO 2Setpoint the OA damper will be closed to the DCV Minimum OA Damper Setpoint (w/o TRAQ) or until the DCV Minimum OA Flow Setpoint is met (w/ TRAQ). If the CO 2concentration is between the Design Minimum CO 2Setpoint and the DCV Minimum CO2Setpoint the OA damper will be modulated proportionally between the Design Minimum OA Damper Setpoint and the DCV Minimum OA Damper Setpoint (w/ TRAQ) and between the Design Minimum OA Flow Setpoint and the DCV Minimum OA Flow Setpoint (w/o TRAQ). Frostat™ Control The compressor module utilizes an evaporator temperature sensor, mounted on the suction line of each circuit, to protect the evaporator from freezing. If the evaporator temperature approaches the specified setpoint, adjustable between 25°F and 35°F, the compressor(s) will be cycled “off”. The compressors will not be allowed to restart until the evaporator temperature has risen 10 F above the specified cutout temperature and the compressor(s) have been off for a minimum of three minutes. Lead/Lag Operation When Lead/Lag is enabled, each time the system cyclesafter having stages 1 and 2 “On”, “Stage 2 and the corresponding condenser fan output will start first. The compressor module cycles the compressors “On” and “Off” to keep the zone temperature within the cooling setpoint deadband. The condenser fans are cycled “On” and “Off” to maintain the saturated refrigerant temperature within the specified controlband. Units equipped with 100% modulating exhaust The exhaust dampers are controlled through an Exhaust/ Comparative Enthalpy Module (ECEM).The ECEM module receives input from a space transducer and modulates the exhaust dampers to maintain the space pressure to within the specified setpoint controlband. Modulating Dehumidification (Hot Gas Reheat) Sequence of Operation When the relative humidity in the controlled space (asmeasured by the sensor assigned to space humidity sensing) rises above the space humidity setpoint, compressors and the supply fan will energize to reduce the humidity in the space. All compressors on both refrigerant circuits will be staged up during active dehumidification. Circuit #1 is designated the reheat circuit and will feature additional refrigerant
Unit Startup 10 4RT-SVX24K-EN control devices as well as a split condenser coil with one section in the indoor air stream and the other in the outdoor coil compartment. During active dehumidification the discharge air will be controlled to the Supply Air Reheat Setpoint by modulating the amount of reheat produced by the reheat coil. The Supply Air Reheat Setpoint, Occupied and Unoccupied Dehumidification Setpoints are adjustable via the human interface, BAS/Network control, or GBAS. Active dehumidification will be terminated when the humidity in the space is reduced to the active space humidity setpoint - 5% or when an overriding condition such as heating or cooling demand or a failure occurs in a component required for dehumidification. On VAV units, at startup, satisfying the VAV Occupied Cooling setpoint, MWU setpoint, and DWU setpoint will have priority over dehumidification mode. Once heating modes are satisfied, and the unit is satisfying the SA Cooling Setpoint, dehumidification mode will be entered if no more than half the unit mechanical cooling capacity is requested. On SZVAV units, dehumidification will be similar to VAV modulating dehumidification with the exception of a dynamic Supply Air Reheat Setpoint. Rather than utilizing a static Supply Air Reheat Setpoint, once the unit enters dehumidification, the Discharge Air Setpoint will be calculated based on the Zone temperature vs. Zone Cooling Setpoint error and will be capped at the user selected Supply Air Reheat setpoint. Dehumidification is not allowed during VAV Heating Modes (Changeover input closed). Once active, dehumidification control will remain active for a minimum of three minutes unless a priority unit shutdown request is received or the High Pressure Control input opens on either circuit. Dehumidification control can be enabled separately for occupied and unoccupied modes of operation via the Human Interface and is overridden/disabled whether active or inactive by the following methods: – Priority unit shutdown conditions (Emergency stop,Ventilation Override, Network Stop, etc.) – Compressor circuit manual reset lockouts on either circuit. Low Refrigerant Charge monitoring is active during dehumidification mode and will lockout compressor circuits based on the same criteria used for cooling mode. – Outdoor Air Temp is less then 40°F or greater the 100°F. – Humidity Sensor Failure – For VAV units, (in occupied) dehumidification will be disabled if space temp is less than the Dehumid Override Low Zone Setpoint or higher than the Dehumid Override High Zone Setpoint. If dehumidification is inactive it will not be allowed until it space temp rises higher than the Dehumid Override Low Zone Setpoint + 1.0°F or lower than the Dehumid Override High Zone Setpoint - 2.0°F. – For SZVAV units, dehumidification will be disabled if space humidity levels have fallen below the Active Occ/Unocc Dehumidification Setpoint -5% Dehumidification Hysteresis Offset, the zone temperature has dropped too close to the Zone Heating Setpoint in any unit mode (Zone Temp. is less than ZHSP + 0.5°F), the zone temperature rises above the Zone Cooling Setpoint +2°F in any unit mode, Entering Evaporator Temperature falls too low, Froststat input becomes active, or Dehumidification/Reheat becomes disabled. – For CV and all units in unoccupied, if space temp is less than the Zone Heating Setpoint (ZHSP) + 0.5° F if dehumidification is active, or less than ZHSP + 1.0° F if not dehumidification mode will be disabled. If zone conditions result in a cooling request for more than one-half the available cooling capacity of the unit dehumidification will be disabled and will transition to cooling control. If dehumidification is inactive, dehumidification will not be allowed until the active unit cooling capacity request drops to half the available cooling capacity or less, unless the space temp is less than the Zone Cooling Setpoint. – In CV units in occupied mode, if the unit is not in “AUTO” system mode and is set to “HEAT” systemmode via the HI, BAS, or Zone Sensor device, dehumidification control will be disabled at space temps above Occupied ZCSP + 1.0° F. If dehumidification is inactive it will not be allowed to activate if space temp is greater than the OZCSP. All units configured for modulating dehumidification will have a reheat condenser coil purge function to ensure proper refrigerant distribution in the reheat circuit. This feature is always enabled and will monitor the amount of cumulative compressor run time while the reheat condenser coil pumpout relay is in a certain state. If compressors accrue an amount of run time equal to the HI- adjustable purge interval time without the pumpout relay changing states a purge cycle will be initiated lasting for three minutes. During this cycle all compressors but the 2nd compressor on circuit #1 will be energized if not already, the reheat valve and cooling valves to will be set to 50%, and the reheat coil pumpout relay will be toggled to its opposite state. After the three-minute purge cycle completes the purge interval timer will be reset and all system components will return to the state they were in prior to entering purge. During dehumidification control an evaporator frost control function designed specifically for reheat modes will be active.This function will reduce refrigeration circuit capacity to 50% (1st compressor on each circuit remaining on) when the Entering Evaporator Temp drops below a
Unit Startup RT-SVX24K-EN10 5 non-adjustable limit of 35° F for 10 continuous minutes. Once capacity is reduced, it will remain reduced until the current cycle of dehumidification is terminated or a purge cycle occurs. If the Entering EvaporatorTemp remains below 35° F for an additional 10 minutes both circuits will be de-activated and remain off until the Entering EvaporatorTemp rises above 45°F. Even though all compressors have been de-activated the unit will remain in dehumidification mode and re- enable compressors up to 50% capacity when the Entering Evaporator Temp rises to 45°F or greater. Energy Recovery Sequence of Operation The primary components of the energy recovery system are the energy recovery wheel, exhaust air bypass damper, outdoor air bypass damper, and the energy recovery preheat output. See Figure 67, p. 106 Figure 68, p. 107 A filter is also placed between the wheel and the outdoor air damper and an indicator scheme similar to that for final filters is provided to notify the user when that filter needs to be changed. The energy recovery wheel will only be energized when both the Supply Fan and Exhaust Fan are requested on by the various functions that control them. Energy recovery is a passive function and can not request fan operation. Once the required airflow is present the wheel will be commanded on if the indoor vs. outdoor conditions are such that energy can be recovered. This is assessed differently in cooling and heating modes. In cooling mode, wheel activation conditions are assessed based on indoor (return air) vs. outdoor enthalpy. Indoor and outdoor enthalpy values are calculated using the same sensors as used for comparative enthalpy. If the outdoor enthalpy is 3 BTU/lb. greater than indoor enthalpy the wheel is activated to remove energy from the incoming outdoor air. In heating mode the wheel is activated based on indoor vs. outdoor dry bulb temperature. If the outdoor temperature is 5° F less than the indoor temperature. the wheel is activated to recover heat energy from the exhaust air. In cooling mode the exhaust air bypass damper is held closed, providing 100% energy recovery capacity during cooling modes of operation. In heating modes, including CV heating, VAV Heating, CV Supply Air Tempering, VAV Supply Air Tempering, Morning Warm-up, and Daytime Warm-up the exhaust air bypass damper is controlled to discharge air temperature. The damper is modulated to keep the supply air temp at the Supply Air Heating setpoint for VAV control, or for CV control, supply air temp will be controlled to a calculated Supply Air Heat Setpoint based on conditions in the space. If the wheel is active, supplemental heat (electric, hydronic, gas) control algorithms will be disabled until the exhaust air bypass damper is fully closed (maximum heating capacity from the wheel). At this point, supplemental heat algorithms are released to calculate supplemental heat capacity requests using standard setpoints until the setpoints are satisfied. In VAV occupied modes the energy recovery wheel will remain active after termination of supplemental heat above heating setpoint until the exhaust air bypass damper is opened fully for 3 minutes (indicating minimal capacity requested from the wheel). In CV occupied heating mode the wheel will remain active after termination of a heating cycle until the zone temp rises above the Occupied Zone Heating Setpoint + 1.0°F and the exhaust air bypass damper is fully open. The wheel will remain active if these conditions persist continuously until the expiration of a HI-adjustable time-out period or until the zone temp rises above the Occupied Zone Cooling Setpoint - 0.5°F. During active Economizing control the energy wheel will be disabled but the outdoor air bypass damper will open an amount that tracks the opening of the OA damper proportionally from minimum position to fully open. To protect the wheel from frost build-up in heating modes a frost avoidance function is included. This feature will energize the energy recovery preheat output (if configured) and modulate the outdoor air bypass damper open (to reduce incident cold outdoor air on the wheel) as necessary when the Leaving RecoveryTemp Sensor value is less than the Recovery Frost Avoidance Setpoint. The Leaving Recovery Temp Sensor is installed in the leaving air stream on the exhaust-fan side of the energy wheel. Figure 66 provides the exhaust air temperature setpoint for 70ºF return air at various percents of relative humidity. Where variable effectiveness / outside air bypass is not enough to prevent frosting conditions, the energy recovery wheel shuts off. Turning the wheel off during frost conditions is a reliable method of preventing the wheel from frosting, however, energy is not being recovered and the extreme heating load must be handled otherwise. Extreme winter design condition for energy recovery units may require return air preheat. An energy recovery wheel proving function is also provided to indicate when the wheel is not turning after it has been commanded on. WARNING Toxic Hazards! Do not use an energy wheel in an application where the exhaust air is contaminated with harmful toxins or biohazards. Failure to follow this instruction could result in death or serious injury.
Unit Startup 10 6RT-SVX24K-EN Figure 66. Energy recovery wheel exhaust air setpoint temperatures Figure 67. Energy recovery wheel operation Outside Air Intake Damper (Mist Eliminator not shown) Exhaust Air, Leaving Energy Recovery Wheel, Path to Exhaust Fan Building Return Air Outside Air Bypass Damper Unit Return Airflow Exhaust Air Bypass Damper Energy Recovery Wheel Conditioned Outside Air Return Air Damper Path to Filters & Coil ERW Unit Entering Air (Mixed Return Air & Conditioned Outside Air)
Unit Startup RT-SVX24K-EN10 7 Gas Heating Sequence of Operation Standard Two Stage Gas Furnace The control system for the rooftop units are wired to ensure that the heating and cooling do not occur simultaneously. Refer to the wiring diagram that shipped with the unit while reviewing the following sequence of operation. Honeywell Ignition System (850 & 1100 MBH Two Stage Natural Gas) When a heating requirement exists, the Rooftop Module(RTM) starts the supply fan and sends a request for heat to the Heat Module. The Heat Module closes contacts and starts the combustion blower motor. The combustion blower motor starts on low speed through the normally closed combustion blower relay contacts. The supply airflow switch and the combustion air switch closes. Power is applied through the high limit cutout to the Honeywell ignition control board. The ignition control board starts a pre-purge timing cycle. At the end of the pre- purge cycle, the ignition transformer and the pilot solenoid valve are energized. This starts a 10 second trial for pilot ignition. When the pilot flame is established and sensed by the flame sensing rod, stage 1 of the main gas valve and the 60 seconds sequencing time delay relay is energized. The system will operate in the low heat mode until an additional call for heat is established by closing the contacts on the Heat Module. The sequencing time delay relay will energize the combustion blower motor relay which switches the combustion blower motor to high speed and energizes the 2nd stage solenoid on the gas valve after approximately 60 seconds. If the flame rod does not detect a pilot flame within the 10 second trial for ignition period, the control will lockout. If a flame failure occurs during operation, the gas valve, the sequencing time delay relay, and the combustion blower relay is de-energized. The system will purge and attempt to relight the pilot. If a flame is not detected after this attempt, the Honeywell ignition control will lock out. The combustion blower motor will continue to operate as long as a heating demand exists and the system switch is “On”. Once the heating demand has been satisfied, the combustion blower and the Honeywell ignition control board is de-energized. Note: The above sequence is the same for Propane. The orifices are smaller and the manifolds are adjusted to different values Figure 68. Energy recovery wheel economizer operation Outside Air Intake Damper (Mist Eliminator not shown) Exhaust Air, Path to Exhaust Fan Building Return Air Outside Air Bypass Damper Unit Return Airflow Exhaust Air Bypass Damper Un- Conditioned Outside Air Return Air Damper Path to Filters & Coil Path to Filters & Coil
Unit Startup 10 8RT-SVX24K-EN (1800 & 2500 MBH Two Stage Natural Gas) When a heating requirement exists, the Rooftop Module (RTM) starts the supply fan and sends a request for heat to the Heat Module. The Heat Module closes contacts and starts the combustion blower motor through the combustion blower relay. The supply airflow switch and the combustion air switch closes. Power is applied through the high limit cutout to the Honeywell ignition control board. The ignition control board begins the pre-purge timing cycle with the damper in the light off position and the low fire start interlock is closed At the end of the pre-purge cycle, the ignition transformer and the pilot solenoid valve are energized.This starts a 10- second trial for pilot ignition. When the pilot flame is established and sensed by the flame sensing rod, the stage 1 of the main gas valve will begin. The gas butterfly control valve is in the low fire setting by the linkage arm connection between the combustion air actuator and the butterfly valve. The system will operate in the low heat mode until there is an additional call for heat established by closing the contacts on the Heat Module. If the flame rod does not detect a pilot flame within the 10 second trial for ignition period, the ignition control board will lockout. The combustion blower motor will continue to operate as long as a heating demand exists and the system switch is “On”. Once locked out on flame failure, the IC board will not reactivate the ignition/combustion control circuit until it is reset manually. To do this, press the reset button on the front of the IC board case. A set of relay contacts is available for external use for heat fail (Information Only). Once the heating demand has been satisfied, the combustion blower and the Honeywell ignition control board is de-energized. Modulating Gas Sequence of Operation The control system for the rooftop units is wired to ensure that the heating and cooling do not occur simultaneously. Refer to the modulating heat wiring diagram that shipped with the unit while reviewing the following sequence of operation. As you review the sequence of operation, keep the following in mind: 1. The furnace will not light unless the manual gas valves are open and the control circuit switch is closed. 2. The control systems are wired to ensure that heatingand cooling cannot occur simultaneously. 3. The unit supply fans must run continuously so airflow switc h will stay closed. 4. Modulating Gas heat is available during both occupied and unoccupied operation. When there is a call for heat, the heat module energizes the combustion blower which causes the combustion air flow switch to close. The ignition control board will energize providing that the indoor air flow switch, high limit, and low and high pressure gas switches are closed. The ignition control board then causes the combustion air actuator to drive the inlet air damper to the fully open position for a 30 second pre-purge. The pre-purge time does not begin until the purge interlock switches are made. After the pre-purge, the combustion air actuator drives the inlet air damper and the gas butterfly control valve to a nearly closed position for light off. When the Low fire interlock switch is closed the ignition transformer is energized, the igniter begins to spark and the pilot valve opens. This begins a 10-second trial for ignition period during which the flame rod must detect the flame. If does not detect a flame at the end of the period, it will shut down and lock out the ignition/ combustion circuit. Once the pilot flame has been established, the heat module will open the main gas valve and auxiliary gas valve. After the main flame is established, the pilot valve closes. The ignition sequence is completed and the heat module will drive the combustion air actuator to a firing rate based on a 2-10 VDC signal. The gas butterfly control valve will respond through the connecting linkage. The heater will continue to run until the call for heat is removed or a limit opens. Following the completion of the call for heat, there is a 15- second post-purge. Flame Failure In the event that (IC) board loses the “proof-of-flame” input signal during furnace operation, it will lock out and the must be manually reset (Combustion blower motor continues to run as long as a heating requirement exists and control circuit switch is ON.) Once locked out on flame failure, the (IC) board will not reactivate the ignition/combustion control circuit until it is reset manually. To do this, press the reset button on the front of the (IC) board case. A set of relay contacts is available for external use for heat fail (Information Only). Note: The modulating gas heaters are factory adjusted for safe operation and to reach the nameplate rated firing MBH for most areas of the country. The proper air/gas ratio must be reached by the service tech during startup.. Electric Heat Sequence of Operation The control system for the rooftop units are wired toensure that heating and cooling do not occur simultaneously. Refer to electric heat wiring diagrams that shipped with the unit while reviewing the following
Unit Startup RT-SVX24K-EN10 9 sequence of operation. As you review the sequence of operations, remember these points: 1. The high limit switch will trip if exposed to a temperature greater than the trip point, and will reset automatically once the temperature falls below the reset point. 2. The linear high limit switch is encased in a capillarythat extends across the unit supply air opening. The limit will trip if any 6” span of the capillary exceeds the trip point. Refer to Table42, p. 135. 3. Electric heat will only energize if both of the high limit safety controls are closed. Electric Heat—CV, VAV Daytime Warm-up CV electric heat operation is done with discrete stages of electric heat. Stages 2 and 3 will not energize unless Stage 1 is already operating and unable to satisfy the heating load. The heat will be staged to control to the Heating Setpoint. VAV Active Occupied Discharge Heating When the changeover input is closed (or whencommanded by BAS) the unit will control discrete stages of electric heat to the active supply air heating setpoint. VAV occupied electric heating operation is done with discrete stages (steps) of electric heat. The heat staging is dependent on unit tonnage and heater selection.The heat will be staged to control to the Supply Air Heating Setpoint. SZVAV Occupied Heating Single Zone VAV heating will only be available with modulating types of heat - IPak II units can use hydronic and modulating gas and will include electric heat. During SZVAV heating, the unit will calculate a discharge heating setpoint based on zone heating demands, and the unit will modulate heat to maintain the discharge temperature to this setpoint. Demand Control Ventilation Sequence of Operation Note: CO2sensor used with Demand Control Ventilation must be powered from an external power source or separate 24 VAC transformer. Sequence of Operation without TRAQ If the space CO2level is greater than or equal to the Design Minimum CO 2Setpoint, the outdoor air damper will open to the Design Minimum Outdoor Air Damper Setpoint. If there is a call for economizer cooling, the damper may be opened further to satisfy the cooling request. If the space CO 2level is less than or equal to the DCV Minimum CO 2Setpoint, the outdoor air damper will close to the DCV Minimum Outdoor Air Damper Setpoint. If there is a call for economizer cooling, the damper may be opened further to satisfy the cooling request. If the space CO 2level is greater than the DCV Minimum CO 2Setpoint and less than the Design Minimum CO2 Setpoint, the outdoor air damper position is modulated proportionally to the space CO 2level relative to a target position between the DCV Minimum CO 2Setpoint and the Design Minimum CO 2Setpoint. If there is a call for economizer cooling, the damper may be opened further to satisfy the cooling request. Sequence of Operation with TRAQ If the space CO2level is greater than or equal to the Design Minimum CO 2Setpoint, the outdoor air damper will open to the Design Minimum Outdoor Air Flow Setpoint. If there is a call for economizer cooling, the damper may be opened further to satisfy the cooling request. If the space CO 2level is less than or equal to the DCV Minimum CO 2Setpoint, the outdoor air damper will close to the DCV Minimum Outdoor Air Flow Setpoint. If there is a call for economizer cooling, the damper may be opened further to satisfy the cooling request. If the space CO 2level is greater than the DCV Minimum CO 2Setpoint and less than the Design Minimum CO2 Setpoint, the outdoor air damper position is modulated proportionally to the space CO 2level relative to a target position between the DCV Minimum CO 2Setpoint and the Design Minimum CO 2Setpoint. If there is a call for economizer cooling, the damper may be opened further to satisfy the cooling request. Return Fan Sequence of Operation Whenever the Supply Fan is turned ON, the return fan will be turned ON. The speed of the return fan will control to the Return Air Plenum Pressure Target. The target is calculated internal to the control and will be between the Minimum Return Air Plenum Pressure Setpoint and the Maximum Return Air Plenum Pressure Setpoint depending on unit operation conditions. A Return Air Pressure High Limit will be set at 3.5 IWC. If the pressure inside the return plenum exceeds the limit the unit will shut down. Unit Clustering A cluster is a master unit and one or more similarlyconfigured slave units operative cooperatively, as a group, to provide higher capacity and/or redundancy at partial capacity. Clustering is accomplished by binding variables between unit LCI-I modules, communicating common setpoints and allowing each unit to run independent algorithms. A cluster will share a common supply and return duct network. Low Charge Protection For each refrigeration circuit, the entering and leaving evaporator temperatures are used to calculate superheat. When the calculated superheat exceeds the Evaporator
Unit Startup 11 0RT-SVX24K-EN Temperature Differential Setpoint minus 5°F but not the Evaporator Temperature Differential Setpoint, an information only, auto-reset, High Superheat diagnostic is initiated. If the calculated superheat exceeds the Evaporator Temperature Differential Setpoint, a manual reset, low refrigerant charge diagnostic is initiated and all compressors on the circuit are locked out. Wet Heat Sequence of Operation Electrical circuitry for units with steam or hot water heat is limited to the connections associated with the modulating valve actuator and the freezestat. Like the furnaces described earlier, steam and hot water heat control systems are wired to ensure that simultaneous heating and cooling do not occur. The supply fan will cycle “On” and “Off” with each call for heat during both an occupied and unoccupied period. Whenever there is a call for heat, the relay on the heat module energizes. This allows a modulated voltage signal to be sent to the “Wet” heat actuator. The value of this signal regulates the flow of steam or hot water through the coil by positioning the valve stem at some point between fully closed (6 VDC) and fully open (8.5 VDC). Freeze Protection A freezestat is mounted inside the heat section of hot water and steam heat units to prevent the “wet” heat coil from freezing during the “Off” cycle. If the temperature of the air leaving the heating coils falls to 40 F, the freezestat normally open contacts close, completing the heat fail circuit on the UCM. When this occurs: a. The supply fan is turned “Off”. b. “Wet” heat actuator fully opens to allow hot wateror steam to pass through the heating coil and prevent freeze-up. c. A “Low Air Temperature Unit Trip” diagnostic is displayed on the Human Interface LCD screen. For heating control settings and time delay specifications, refer to Table 45, p. 158. Unit Startup Check List Use the following checklist, in conjunction with the “General Unit Requirement” checklist”, to ensure that the unit is properly installed and ready for operation. Be sure to complete all of the procedures described in this section before starting the unit for the first time. [ ]Turn the field supplied disconnect switch, located upstream of the rooftop unit, to the “Off” position. [ ] Turn the 115 volt control circuit switch 1S2 to the “Off” position. It is located in the secondary of the 1T1transformer. [ ]Turn the 24 volt control circuit switch 1S3 to the “Off” position. It is located in the secondary of the 1T2 - 1T5 transformers. [ ] Turn the “System” selection switch (at the Remote P anel) to the “Off” position and the “Fan” selection switch (if Applicable) to the “Auto” or “Off” position. [ ] Check all electrical connections for tightness and “point of termination” accuracy. [ ] Verify that the condenser airflow will be unobstructed. [ ] Check the compressor crankcase oil level. Oil should be visible in the compressor oil sight glass. The oil level should be 1/2 to 3/4 high in the sight glass with the compressor “Off”. [ ] Verify that all refrigerant service valves are back seated on each circuit. Do not start the unit in the cooling mode if the ambient temperature is below the following minimum recommended operating temperature: Standard unit with or without HGBP-+45°F [ ] Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearings need lubricating, refer to the Service/Maintenance section of this manual for instructions. [ ] Inspect the interior of the unit for tools and debris. Install all panels in preparation for starting the unit. Electrical Phasing Scroll compressors are phase sensitive. Proper phasing of the electrical supply to the unit is critical for proper operation and reliability. The compressor motor is WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. CAUTION Compressor Damage! Do not allow liquid refrigerant to enter the suction line. Excessive liquid accumulation in the liquid lines could result in compressor damage.Compressor service valves must be fully opened before startup (suction, discharge, liquid line, and oil line).