Home > Trane > Air Conditioner > Trane Intellipak 2 Service Manual

Trane Intellipak 2 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Unit Startup
    RT-SVX24K-EN101
    Set Drain Duration Timer
    Enter service test mode from unit Human Interface.
    Navigate to the compressor condenser fan submenu.
    Under head pressure control, use manual control.
    Close drain valve and energize water inlet solenoid valve
    until water reaches nominal level. Once level is achieved,
    de-energize fill solenoid. Open drain valve and time how
    long it takes for the water level to drop one inch, make sure
    to take into account the closing time of the valve.
    Chemical Water Treatment Tree
    TheTrane evaporative condenser comes with a PVC tree to
    allow easier inputs for third party water treatment.The tee
    labeled A is a ¾ inch NPT threaded input, see Figure 65.
    Tees B and C are 1/2 inch NPT threaded inputs. The ball valve can be used to stop the water flow through the tree
    to allow the customer to add hookup of water treatment,
    or to change and update water treatment with the unit
    running.
    Units with Dolphin WaterCare™or conductivity sensor will
    have the conductivity sensor installed into the ¾ inch tee
    with the other tees plugged. For all other units, A, B and C
    will be plugged, see Figure 65. Ensure the ball valve is in
    the open position when water treatment is being operated
    in the system to make sure water flows through the tree
    and transports treatment to the unit sump.
    Conductivity Controller
    Upon startup, the conductivity controller must be
    calibrated and setup for operation. Below are the
    necessary steps to accomplish those tasks. The controller
    has two setpoints that control two relays. Both of these
    setpoints will need to be set by Dolphin or a local water
    treatment expert.
    1. The first setpoint is the standard point blowdown point.
    – When the setpoint is exceeded the relay (K1) will beenergized and a blowdown request will close the
    Water treatment request binary input on the MCM.
    Figure 63. Actuator shaft adapter removal/assembly
    Figure 64. Actuator is shipped in “Drain during power
    loss” configuration
    Locking clip
    Shaft adapter
    1
    2
    To drain during power loss,
    set shaft adapter to 0 degrees To hold during power loss,
    set shaft adapter to 90 degrees
    Figure 65. Chemical water treatment tree 
    						
    							Unit Startup
    10 2RT-SVX24K-EN
    2. The second setpoint will be the emergency point
    – The second setpoint will open the normally closedK2
     relay which will interrupt the sump proving
    circuit which will generate a manual lockout. This
    second setpoint will be used to protect the unit from
    extremely high conductivity that would indicate a
    failure in the system.
    3. Inside the enclosure for the controller, there will be a thermostat
     and strip heater that will protect LCD from
    cracking at low ambient conditions. The thermostat
    closes at 15°F and opens at 25°F.
    Procedure to calibrate conductivity
    Note: Visit this webpage for additional documentation:
    
    Use a calibrated thermometer and a known conductivity
    rating. There are two different options for having a liquid
    with known conductivity. Purchase a liquid with known
    conductivity rating and purchase a handheld conductivity
    reader.
    1. Close the ball valve on the chemical treatment tree and remove the conductivity sensor from the tree.
    2. Enter service test mode on the unit and turn the pump on,
     ensuring the compressors are set to Off.
    3. With the conductivity controller connected to the sensor
     and power, enter the CALIBRATE menu by
    holding down the enter key for 2 seconds.
    4. When asked for the calibration key code, hit the UP-UP- UP
     -DOWN arrow keys in sequence.
    5. Using the UP and DOWN arrows go to Chan 1 Cell: Standard.
     Ensure this channel is set to standard.
    6. If not press the RIGHT arrow key and set to standard then
     press the ENTER key to return to the
    CALIBRATION menu.
    7. Using the UP and DOWN arrows go to Chan 1 Cell. Ensure
     that the cell constant is set to 1.0.
    8. If not press the RIGHT arrow key and set the cell constant
     to 1.0 then press the ENTER key to return to
    the CALIBRATION menu.
    9. Using the UP and DOWN arrows go to Chan 1 Set: T
     emperature and press the RIGHT arrow key to enter
    the edit mode.
    10. Adjust the temperature on the controller to match the actual
     temperature.
    11. Press the ENTER key to save the input and return to the CALIBRA
     TE menu.
    12. Using the UP and DOWN arrows, go to the Chan 1 Set: Conducti
     vity and press the RIGHT arrow key to enter
    the edit mode.
    13. Adjust the conductivity on the controller to match the actual
     conductivity rating of the liquid. 14. Press the ENTER key to save the conductivity rating
    and
     return to the CALIBRATE menu.
    15. When finished calibrating the controller, press the UP and
     DOWN key simultaneously to return to normal
    operating mode.
    Procedure to set purge setpoints on the
    conductivity controller
    Note: Visit this webpage for additional documentation:
    
    Work with local water treatment expert to identify nominal purge and emergency purge conductivity value.
    1. Close the ball valve on the chemical treatment tree and remove the conductivity sensor from the tree.
    2. Enter Service test mode on the unit HI and energize the sump
     pump, ensuring the compressors are set to
    OFF.
    3. With the conductivity controller connected to the sensor
     and power, enter the CALIBRATE menu by
    holding down the enter key for 2 seconds.
    4. When asked for the calibration key code, hit the UP-UP- UP
     -DOWN arrow keys in sequence.
    5. Using the UP and DOWN arrows, go to Relay 1 S
     etpoint: and press the RIGHT arrow key to enter edit
    mode (K1).
    6. Adjust the set point to the nominal blowdown conducti
     vity value.
    7. Press the ENTER key to return to the CALIBRATE menu.
    8. Using the UP and DOWN arrows, go to Relay 2 S
     etpoint: and press the RIGHT arrow key to enter edit
    mode (K2).
    9. Adjust the set point to the emergency conductivity value.
    10. Press the ENTER key to return to the CALIBRATE menu.
    11. When finished setting the values, press the UP and DO
     WN key simultaneously to return to normal
    operating mode.
    Units Without an Economizer
    Upon entering an “occupied” mode of operation, the RTM
    receives input from the remote panel to start the supply
    fan. For constant volume applications, the RTM supply fan
    contacts close which energizes the supply fan contactor.
    When the supply fan starts, the fan proving switch closes, signaling the RTM that airflow has been established and
    the VFD will begin to ramp the fan (if equipped).
    When a cooling request is sent to the RTM from a zone temperature sensor, the RTM evaluates the operating
    condition of the system using the supply air temperature
    input and the outdoor temperature input before sending
    the request to the MCM. Once the request is sent to the
    MCM, the compressor module checks the compressor 
    						
    							Unit Startup
    RT-SVX24K-EN10 3
    protection circuit before closing “Stage 1. After the first
    functional stage has started, the compressor module
    monitors the saturated refrigerant temperature and closes
    the condenser fan output contact, when the saturated
    refrigerant temperature rises above the “lower limit”
    setpoint.
    Units with an Economizer
    Upon entering an “occupied” mode of operation, the RTM
    receives input from the remote panel to start the supply
    fan. For constant volume applications, the RTM supply fan
    contacts close which energizes the supply fan contactor.
    When the supply fan starts, the fan proving switch closes, signaling the RTM that airflow has been established. The
    RTM opens the economizer dampers to the specified
    “minimum position”.
    When a cooling request is sent to the RTM from the zone temperature sensor, the RTM evaluates the operating
    condition of the system using the supply air temperature
    input and the outdoor temperature input before sending
    the request to the MCM for mechanical cooling. If the
    outdoor conditions are suitable for cooling (temperature
    and humidity are within specified setpoints), the RTM will
    attempt to maintain the zone temperature without using
    any compressors. If the zone temperature can not be
    maintained within the setpoint deadband, the RTM sends
    a cooling request to the MCM. The compressor module
    checks the compressor protection circuit before closing
    “Stage 1. After the first functional stage has started, the compressor module monitors the saturated refrigerant
    temperature and closes the condenser fan output contact,
    when the saturated refrigerant temperature rises above
    the “lower limit” setpoint.
    Units with TRAQ™ Sensor
    The outside air enters the unit through the TRAQ Sensor assemblies and is measured by velocity pressure flow
    rings. The velocity pressure flow rings are connected to a
    pressure transducer/solenoid assemblies. The solenoid is
    used for calibration purposes to compensate for
    temperature swings that could affect the transducer. The
    Ventilation Control Module (VCM) utilizes the velocity pressure inputs, the RTM outdoor air temperature input,
    and the minimum outside air CFM setpoint to modify the
    volume (CFM) of outside air entering the unit as the
    measured airflow deviates from setpoint.
    When the optional temperature sensor is installed and the Preheat function is enabled, the sensor will monitor the
    combined (averaged) outside air and return air
    temperatures. As this mixed air temperature falls below
    the Preheat Actuate Temperature Setpoint, the VCM will
    activate the preheat binary output used to control a field
    installed heater. The output will be deactivated when the
    temperature rises 5 above the Preheat Actuate
    Temperature Setpoint.
    When the optional CO
    2sensor is installed and DCV is
    enabled, the OA damper will be modulated to control CO
    2
    concentrations. If the CO2concentration is greater than
    the Design Minimum CO
    2Setpoint the OA damper will be
    opened to the Design Minimum OA Damper Setpoint (w/
    oTRAQ) or until the Design Minimum OA Flow Setpoint is
    met (w/ TRAQ).
    If the CO
    2concentration is less than the DCV Minimum
    CO
    2Setpoint the OA damper will be closed to the DCV
    Minimum OA Damper Setpoint (w/o TRAQ) or until the
    DCV Minimum OA Flow Setpoint is met (w/ TRAQ).
    If the CO
    2concentration is between the Design Minimum
    CO
    2Setpoint and the DCV Minimum CO2Setpoint the OA
    damper will be modulated proportionally between the
    Design Minimum OA Damper Setpoint and the DCV
    Minimum OA Damper Setpoint (w/ TRAQ) and between
    the Design Minimum OA Flow Setpoint and the DCV
    Minimum OA Flow Setpoint (w/o TRAQ).
    Frostat™ Control
    The compressor module utilizes an evaporator temperature sensor, mounted on the suction line of each
    circuit, to protect the evaporator from freezing. If the
    evaporator temperature approaches the specified
    setpoint, adjustable between 25°F and 35°F, the
    compressor(s) will be cycled “off”. The compressors will
    not be allowed to restart until the evaporator temperature
    has risen 10 F above the specified cutout temperature and
    the compressor(s) have been off for a minimum of three
    minutes.
    Lead/Lag Operation
    When Lead/Lag is enabled, each time the system cyclesafter having stages 1 and 2 “On”, “Stage 2 and the
    corresponding condenser fan output will start first. The
    compressor module cycles the compressors “On” and
    “Off” to keep the zone temperature within the cooling setpoint deadband. The condenser fans are cycled “On”
    and “Off” to maintain the saturated refrigerant
    temperature within the specified controlband.
    Units equipped with 100% modulating
    exhaust
    The exhaust dampers are controlled through an Exhaust/ Comparative Enthalpy Module (ECEM).The ECEM module
    receives input from a space transducer and modulates the
    exhaust dampers to maintain the space pressure to within
    the specified setpoint controlband.
    Modulating Dehumidification (Hot Gas
    Reheat) Sequence of Operation
    When the relative humidity in the controlled space (asmeasured by the sensor assigned to space humidity
    sensing) rises above the space humidity setpoint,
    compressors and the supply fan will energize to reduce the
    humidity in the space.
    All compressors on both refrigerant circuits will be staged up during active dehumidification. Circuit #1 is designated
    the reheat circuit and will feature additional refrigerant 
    						
    							Unit Startup
    10 4RT-SVX24K-EN
    control devices as well as a split condenser coil with one
    section in the indoor air stream and the other in the
    outdoor coil compartment.
    During active dehumidification the discharge air will be
    controlled to the Supply Air Reheat Setpoint by
    modulating the amount of reheat produced by the reheat
    coil. The Supply Air Reheat Setpoint, Occupied and
    Unoccupied Dehumidification Setpoints are adjustable via
    the human interface, BAS/Network control, or GBAS.
    Active dehumidification will be terminated when the humidity in the space is reduced to the active space
    humidity setpoint - 5% or when an overriding condition
    such as heating or cooling demand or a failure occurs in a
    component required for dehumidification.
    On VAV units, at startup, satisfying the VAV Occupied
    Cooling setpoint, MWU setpoint, and DWU setpoint will
    have priority over dehumidification mode. Once heating
    modes are satisfied, and the unit is satisfying the SA
    Cooling Setpoint, dehumidification mode will be entered if
    no more than half the unit mechanical cooling capacity is
    requested.
    On SZVAV units, dehumidification will be similar to VAV
    modulating dehumidification with the exception of a
    dynamic Supply Air Reheat Setpoint. Rather than utilizing
    a static Supply Air Reheat Setpoint, once the unit enters
    dehumidification, the Discharge Air Setpoint will be
    calculated based on the Zone temperature vs. Zone
    Cooling Setpoint error and will be capped at the user
    selected Supply Air Reheat setpoint.
    Dehumidification is not allowed during VAV Heating
    Modes (Changeover input closed). Once active,
    dehumidification control will remain active for a minimum
    of three minutes unless a priority unit shutdown request is
    received or the High Pressure Control input opens on
    either circuit.
    Dehumidification control can be enabled separately for
    occupied and unoccupied modes of operation via the
    Human Interface and is overridden/disabled whether
    active or inactive by the following methods:
    – Priority unit shutdown conditions (Emergency stop,Ventilation Override, Network Stop, etc.)
    – Compressor circuit manual reset lockouts on either circuit. Low Refrigerant Charge monitoring is active
    during dehumidification mode and will lockout
    compressor circuits based on the same criteria
    used for cooling mode.
    – Outdoor Air Temp is less then 40°F or greater the 100°F.
    – Humidity Sensor Failure
    – For VAV units, (in occupied) dehumidification will be disabled if space temp is less than the Dehumid
    Override Low Zone Setpoint or higher than the
    Dehumid Override High Zone Setpoint. If
    dehumidification is inactive it will not be allowed
    until it space temp rises higher than the Dehumid Override Low Zone Setpoint + 1.0°F or lower than
    the Dehumid Override High Zone Setpoint - 2.0°F.
    – For SZVAV units, dehumidification will be disabled if space humidity levels have fallen below the
    Active Occ/Unocc Dehumidification Setpoint -5% Dehumidification Hysteresis Offset, the zone
    temperature has dropped too close to the Zone
    Heating Setpoint in any unit mode (Zone Temp. is
    less than ZHSP + 0.5°F), the zone temperature rises
    above the Zone Cooling Setpoint +2°F in any unit
    mode, Entering Evaporator Temperature falls too
    low, Froststat input becomes active, or
    Dehumidification/Reheat becomes disabled.
    – For CV and all units in unoccupied, if space temp is less than the Zone Heating Setpoint (ZHSP) + 0.5° F
    if dehumidification is active, or less than ZHSP + 1.0°
    F if not dehumidification mode will be disabled. If
    zone conditions result in a cooling request for more
    than one-half the available cooling capacity of the
    unit dehumidification will be disabled and will
    transition to cooling control. If dehumidification is
    inactive, dehumidification will not be allowed until
    the active unit cooling capacity request drops to
    half the available cooling capacity or less, unless
    the space temp is less than the Zone Cooling
    Setpoint.
    – In CV units in occupied mode, if the unit is not in “AUTO” system mode and is set to “HEAT” systemmode via the HI, BAS, or Zone Sensor device,
    dehumidification control will be disabled at space
    temps above Occupied ZCSP + 1.0° F. If
    dehumidification is inactive it will not be allowed to
    activate if space temp is greater than the OZCSP.
    All units configured for modulating dehumidification will have a reheat condenser coil purge function to ensure
    proper refrigerant distribution in the reheat circuit. This
    feature is always enabled and will monitor the amount of
    cumulative compressor run time while the reheat
    condenser coil pumpout relay is in a certain state. If
    compressors accrue an amount of run time equal to the HI-
    adjustable purge interval time without the pumpout relay
    changing states a purge cycle will be initiated lasting for
    three minutes.
    During this cycle all compressors but the 2nd compressor
    on circuit #1 will be energized if not already, the reheat
    valve and cooling valves to will be set to 50%, and the
    reheat coil pumpout relay will be toggled to its opposite
    state. After the three-minute purge cycle completes the
    purge interval timer will be reset and all system
    components will return to the state they were in prior to
    entering purge.
    During dehumidification control an evaporator frost
    control function designed specifically for reheat modes
    will be active.This function will reduce refrigeration circuit
    capacity to 50% (1st compressor on each circuit remaining
    on) when the Entering Evaporator Temp drops below a 
    						
    							Unit Startup
    RT-SVX24K-EN10 5
    non-adjustable limit of 35° F for 10 continuous minutes.
    Once capacity is reduced, it will remain reduced until the
    current cycle of dehumidification is terminated or a purge
    cycle occurs.
    If the Entering EvaporatorTemp remains below 35° F for an
    additional 10 minutes both circuits will be de-activated and
    remain off until the Entering EvaporatorTemp rises above
    45°F. Even though all compressors have been de-activated
    the unit will remain in dehumidification mode and re-
    enable compressors up to 50% capacity when the Entering
    Evaporator Temp rises to 45°F or greater.
    Energy Recovery Sequence of Operation
    The primary components of the energy recovery system
    are the energy recovery wheel, exhaust air bypass
    damper, outdoor air bypass damper, and the energy
    recovery preheat output. See Figure 67, p. 106 Figure 68,
    p. 107 A filter is also placed between the wheel and the
    outdoor air damper and an indicator scheme similar to that
    for final filters is provided to notify the user when that filter
    needs to be changed.
    The energy recovery wheel will only be energized when both the Supply Fan and Exhaust Fan are requested on by
    the various functions that control them. Energy recovery is
    a passive function and can not request fan operation.
    Once the required airflow is present the wheel will be
    commanded on if the indoor vs. outdoor conditions are
    such that energy can be recovered. This is assessed
    differently in cooling and heating modes.
    In cooling mode, wheel activation conditions are assessed
    based on indoor (return air) vs. outdoor enthalpy. Indoor
    and outdoor enthalpy values are calculated using the
    same sensors as used for comparative enthalpy. If the
    outdoor enthalpy is 3 BTU/lb. greater than indoor enthalpy
    the wheel is activated to remove energy from the
    incoming outdoor air. In heating mode the wheel is
    activated based on indoor vs. outdoor dry bulb
    temperature. If the outdoor temperature is 5° F less than
    the indoor temperature. the wheel is activated to recover
    heat energy from the exhaust air.
    In cooling mode the exhaust air bypass damper is held
    closed, providing 100% energy recovery capacity during
    cooling modes of operation. In heating modes, including
    CV heating, VAV Heating, CV Supply Air Tempering, VAV
    Supply Air Tempering, Morning Warm-up, and Daytime
    Warm-up the exhaust air bypass damper is controlled to discharge air temperature. The damper is modulated to
    keep the supply air temp at the Supply Air Heating setpoint for VAV control, or for CV control, supply air temp will be
    controlled to a calculated Supply Air Heat Setpoint based
    on conditions in the space.
    If the wheel is active, supplemental heat (electric,
    hydronic, gas) control algorithms will be disabled until the
    exhaust air bypass damper is fully closed (maximum
    heating capacity from the wheel). At this point,
    supplemental heat algorithms are released to calculate
    supplemental heat capacity requests using standard
    setpoints until the setpoints are satisfied. In VAV occupied
    modes the energy recovery wheel will remain active after
    termination of supplemental heat above heating setpoint
    until the exhaust air bypass damper is opened fully for 3
    minutes (indicating minimal capacity requested from the
    wheel). In CV occupied heating mode the wheel will
    remain active after termination of a heating cycle until the
    zone temp rises above the Occupied Zone Heating
    Setpoint + 1.0°F and the exhaust air bypass damper is fully
    open. The wheel will remain active if these conditions
    persist continuously until the expiration of a HI-adjustable
    time-out period or until the zone temp rises above the
    Occupied Zone Cooling Setpoint - 0.5°F.
    During active Economizing control the energy wheel will
    be disabled but the outdoor air bypass damper will open
    an amount that tracks the opening of the OA damper
    proportionally from minimum position to fully open.
    To protect the wheel from frost build-up in heating modes a frost avoidance function is included. This feature will
    energize the energy recovery preheat output (if
    configured) and modulate the outdoor air bypass damper
    open (to reduce incident cold outdoor air on the wheel) as
    necessary when the Leaving RecoveryTemp Sensor value
    is less than the Recovery Frost Avoidance Setpoint. The
    Leaving Recovery Temp Sensor is installed in the leaving
    air stream on the exhaust-fan side of the energy wheel.
    Figure 66 provides the exhaust air temperature setpoint
    for 70ºF return air at various percents of relative humidity.
    Where variable effectiveness / outside air bypass is not enough to prevent frosting conditions, the energy
    recovery wheel shuts off. Turning the wheel off during
    frost conditions is a reliable method of preventing the
    wheel from frosting, however, energy is not being
    recovered and the extreme heating load must be handled
    otherwise. Extreme winter design condition for energy
    recovery units may require return air preheat.
    An energy recovery wheel proving function is also provided to indicate when the wheel is not turning after it
    has been commanded on.
    WARNING
    Toxic Hazards!
    Do not use an energy wheel in an application where the
    exhaust air is contaminated with harmful toxins or
    biohazards. Failure to follow this instruction could
    result in death or serious injury. 
    						
    							Unit Startup
    10 6RT-SVX24K-EN
    Figure 66. Energy recovery wheel exhaust air setpoint temperatures
    Figure 67. Energy recovery wheel operation
     Outside Air Intake Damper
    (Mist Eliminator not shown)
     Exhaust Air,
     Leaving Energy Recovery Wheel, 
     Path to Exhaust Fan
     Building Return Air
     Outside Air Bypass Damper
     Unit Return
     Airflow
     Exhaust Air
     Bypass Damper
     Energy Recovery Wheel
     Conditioned Outside Air
     Return Air Damper
     Path to Filters & Coil
     ERW Unit Entering Air 
     (Mixed Return Air &
     Conditioned Outside Air) 
    						
    							Unit Startup
    RT-SVX24K-EN10 7
    Gas Heating Sequence of Operation
    Standard
    Two Stage Gas Furnace
    The control system for the rooftop units are wired to
    ensure that the heating and cooling do not occur
    simultaneously. Refer to the wiring diagram that shipped
    with the unit while reviewing the following sequence of
    operation.
    Honeywell Ignition System
    (850 & 1100 MBH Two Stage Natural Gas)
    When a heating requirement exists, the Rooftop Module(RTM) starts the supply fan and sends a request for heat to
    the Heat Module. The Heat Module closes contacts and
    starts the combustion blower motor. The combustion
    blower motor starts on low speed through the normally
    closed combustion blower relay contacts.
    The supply airflow switch and the combustion air switch closes. Power is applied through the high limit cutout to
    the Honeywell ignition control board. The ignition control
    board starts a pre-purge timing cycle. At the end of the pre-
    purge cycle, the ignition transformer and the pilot
    solenoid valve are energized. This starts a 10 second trial
    for pilot ignition. When the pilot flame is established and
    sensed by the flame sensing rod, stage 1 of the main gas valve and the 60 seconds sequencing time delay relay is
    energized.
    The system will operate in the low heat mode until an additional call for heat is established by closing the
    contacts on the Heat Module. The sequencing time delay
    relay will energize the combustion blower motor relay
    which switches the combustion blower motor to high
    speed and energizes the 2nd stage solenoid on the gas
    valve after approximately 60 seconds.
    If the flame rod does not detect a pilot flame within the 10
    second trial for ignition period, the control will lockout. If
    a flame failure occurs during operation, the gas valve, the
    sequencing time delay relay, and the combustion blower
    relay is de-energized. The system will purge and attempt
    to relight the pilot. If a flame is not detected after this
    attempt, the Honeywell ignition control will lock out. The
    combustion blower motor will continue to operate as long
    as a heating demand exists and the system switch is “On”.
    Once the heating demand has been satisfied, the
    combustion blower and the Honeywell ignition control
    board is de-energized.
    Note: The above sequence is the same for Propane. The
    orifices are smaller and the manifolds are adjusted
    to different values
    Figure 68. Energy recovery wheel economizer operation
     Outside Air Intake Damper
    (Mist Eliminator not shown)
     Exhaust Air,
     Path to Exhaust Fan
     Building Return Air
     Outside Air Bypass Damper
     Unit Return
     Airflow
     Exhaust Air
     Bypass Damper
     Un-
     Conditioned
     
    Outside Air
     Return Air Damper
     Path to
     Filters
     & Coil
     Path to
     Filters
     & Coil 
    						
    							Unit Startup
    10 8RT-SVX24K-EN
    (1800 & 2500 MBH Two Stage Natural Gas)
    When a heating requirement exists, the Rooftop Module
    (RTM) starts the supply fan and sends a request for heat to
    the Heat Module. The Heat Module closes contacts and
    starts the combustion blower motor through the
    combustion blower relay.
    The supply airflow switch and the combustion air switch closes. Power is applied through the high limit cutout to
    the Honeywell ignition control board. The ignition control
    board begins the pre-purge timing cycle with the damper
    in the light off position and the low fire start interlock is
    closed
    At the end of the pre-purge cycle, the ignition transformer and the pilot solenoid valve are energized.This starts a 10-
    second trial for pilot ignition.
    When the pilot flame is established and sensed by the flame sensing rod, the stage 1 of the main gas valve will
    begin. The gas butterfly control valve is in the low fire
    setting by the linkage arm connection between the
    combustion air actuator and the butterfly valve.
    The system will operate in the low heat mode until there is an additional call for heat established by closing the
    contacts on the Heat Module.
    If the flame rod does not detect a pilot flame within the 10
    second trial for ignition period, the ignition control board
    will lockout. The combustion blower motor will continue
    to operate as long as a heating demand exists and the
    system switch is “On”.
    Once locked out on flame failure, the IC board will not
    reactivate the ignition/combustion control circuit until it is
    reset manually. To do this, press the reset button on the
    front of the IC board case.
    A set of relay contacts is available for external use for heat fail (Information Only).
    Once the heating demand has been satisfied, the
    combustion blower and the Honeywell ignition control
    board is de-energized.
    Modulating Gas Sequence of Operation
    The control system for the rooftop units is wired to ensure that the heating and cooling do not occur simultaneously.
    Refer to the modulating heat wiring diagram that shipped
    with the unit while reviewing the following sequence of
    operation. As you review the sequence of operation, keep
    the following in mind:
    1. The furnace will not light unless the manual gas valves are open and the control circuit switch is closed.
    2. The control systems are wired to ensure that heatingand cooling cannot occur simultaneously.
    3. The unit supply fans must run continuously so airflow switc
     h will stay closed.
    4. Modulating Gas heat is available during both occupied and
     unoccupied operation. When there is a call for heat, the heat module energizes the
    combustion
     blower which causes the combustion air flow
    switch to close. The ignition control board will energize
    providing that the indoor air flow switch, high limit, and
    low and high pressure gas switches are closed.
    The ignition control board then causes the combustion air actuator to drive the inlet air damper to the fully open
    position for a 30 second pre-purge. The pre-purge time
    does not begin until the purge interlock switches are made.
    After the pre-purge, the combustion air actuator drives the inlet air damper and the gas butterfly control valve to a
    nearly closed position for light off. When the Low fire
    interlock switch is closed the ignition transformer is
    energized, the igniter begins to spark and the pilot valve
    opens.
    This begins a 10-second trial for ignition period during which the flame rod must detect the flame. If does not
    detect a flame at the end of the period, it will shut down
    and lock out the ignition/ combustion circuit.
    Once the pilot flame has been established, the heat
    module will open the main gas valve and auxiliary gas
    valve. After the main flame is established, the pilot valve
    closes. The ignition sequence is completed and the heat
    module will drive the combustion air actuator to a firing
    rate based on a 2-10 VDC signal. The gas butterfly control
    valve will respond through the connecting linkage.
    The heater will continue to run until the call for heat is removed or a limit opens.
    Following the completion of the call for heat, there is a 15-
    second post-purge.
    Flame Failure
    In the event that (IC) board loses the “proof-of-flame”
    input signal during furnace operation, it will lock out and
    the must be manually reset (Combustion blower motor
    continues to run as long as a heating requirement exists
    and control circuit switch is ON.)
    Once locked out on flame failure, the (IC) board will not
    reactivate the ignition/combustion control circuit until it is
    reset manually. To do this, press the reset button on the
    front of the (IC) board case.
    A set of relay contacts is available for external use for heat fail (Information Only).
    Note: The modulating gas heaters are factory adjusted
    for safe operation and to reach the nameplate rated
    firing MBH for most areas of the country. The
    proper air/gas ratio must be reached by the service
    tech during startup..
    Electric Heat Sequence of Operation
    The control system for the rooftop units are wired toensure that heating and cooling do not occur
    simultaneously. Refer to electric heat wiring diagrams that
    shipped with the unit while reviewing the following 
    						
    							Unit Startup
    RT-SVX24K-EN10 9
    sequence of operation. As you review the sequence of
    operations, remember these points:
    1. The high limit switch will trip if exposed to a
    temperature greater than the trip point, and will reset
    automatically once the temperature falls below the
    reset point.
    2. The linear high limit switch is encased in a capillarythat extends across the unit supply air opening. The
    limit will trip if any 6” span of the capillary exceeds the
    trip point. Refer to Table42, p. 135.
    3. Electric heat will only energize if both of the high limit safety
     controls are closed.
    Electric Heat—CV, VAV Daytime Warm-up
    CV electric heat operation is done with discrete stages of
    electric heat. Stages 2 and 3 will not energize unless Stage
    1 is already operating and unable to satisfy the heating
    load. The heat will be staged to control to the Heating
    Setpoint.
    VAV Active Occupied Discharge Heating
    When the changeover input is closed (or whencommanded by BAS) the unit will control discrete stages
    of electric heat to the active supply air heating setpoint.
    VAV occupied electric heating operation is done with discrete stages (steps) of electric heat. The heat staging is
    dependent on unit tonnage and heater selection.The heat
    will be staged to control to the Supply Air Heating
    Setpoint.
    SZVAV Occupied Heating
    Single Zone VAV heating will only be available with
    modulating types of heat - IPak II units can use hydronic
    and modulating gas and will include electric heat. During
    SZVAV heating, the unit will calculate a discharge heating
    setpoint based on zone heating demands, and the unit will
    modulate heat to maintain the discharge temperature to
    this setpoint.
    Demand Control Ventilation Sequence of
    Operation
    Note: CO2sensor used with Demand Control Ventilation
    must be powered from an external power source or
    separate 24 VAC transformer.
    Sequence of Operation without TRAQ
    If the space CO2level is greater than or equal to the Design
    Minimum CO
    2Setpoint, the outdoor air damper will open
    to the Design Minimum Outdoor Air Damper Setpoint. If
    there is a call for economizer cooling, the damper may be
    opened further to satisfy the cooling request.
    If the space CO
    2level is less than or equal to the DCV
    Minimum CO
    2Setpoint, the outdoor air damper will close
    to the DCV Minimum Outdoor Air Damper Setpoint. If there is a call for economizer cooling, the damper may be
    opened further to satisfy the cooling request.
    If the space CO
    2level is greater than the DCV Minimum
    CO
    2Setpoint and less than the Design Minimum CO2
    Setpoint, the outdoor air damper position is modulated
    proportionally to the space CO
    2level relative to a target
    position between the DCV Minimum CO
    2Setpoint and the
    Design Minimum CO
    2Setpoint. If there is a call for
    economizer cooling, the damper may be opened further to
    satisfy the cooling request.
    Sequence of Operation with TRAQ
    If the space CO2level is greater than or equal to the Design
    Minimum CO
    2Setpoint, the outdoor air damper will open
    to the Design Minimum Outdoor Air Flow Setpoint. If there
    is a call for economizer cooling, the damper may be
    opened further to satisfy the cooling request.
    If the space CO
    2level is less than or equal to the DCV
    Minimum CO
    2Setpoint, the outdoor air damper will close
    to the DCV Minimum Outdoor Air Flow Setpoint. If there is
    a call for economizer cooling, the damper may be opened
    further to satisfy the cooling request.
    If the space CO
    2level is greater than the DCV Minimum
    CO
    2Setpoint and less than the Design Minimum CO2
    Setpoint, the outdoor air damper position is modulated
    proportionally to the space CO
    2level relative to a target
    position between the DCV Minimum CO
    2Setpoint and the
    Design Minimum CO
    2Setpoint. If there is a call for
    economizer cooling, the damper may be opened further to
    satisfy the cooling request.
    Return Fan Sequence of Operation
    Whenever the Supply Fan is turned ON, the return fan will be turned ON. The speed of the return fan will control to
    the Return Air Plenum Pressure Target. The target is
    calculated internal to the control and will be between the
    Minimum Return Air Plenum Pressure Setpoint and the
    Maximum Return Air Plenum Pressure Setpoint
    depending on unit operation conditions. A Return Air
    Pressure High Limit will be set at 3.5 IWC. If the pressure
    inside the return plenum exceeds the limit the unit will
    shut down.
    Unit Clustering
    A cluster is a master unit and one or more similarlyconfigured slave units operative cooperatively, as a group,
    to provide higher capacity and/or redundancy at partial
    capacity. Clustering is accomplished by binding variables
    between unit LCI-I modules, communicating common
    setpoints and allowing each unit to run independent
    algorithms. A cluster will share a common supply and
    return duct network.
    Low Charge Protection
    For each refrigeration circuit, the entering and leaving
    evaporator temperatures are used to calculate superheat.
    When the calculated superheat exceeds the Evaporator 
    						
    							Unit Startup
    11 0RT-SVX24K-EN
    Temperature Differential Setpoint minus 5°F but not the
    Evaporator Temperature Differential Setpoint, an
    information only, auto-reset, High Superheat diagnostic is
    initiated. If the calculated superheat exceeds the
    Evaporator Temperature Differential Setpoint, a manual
    reset, low refrigerant charge diagnostic is initiated and all
    compressors on the circuit are locked out.
    Wet Heat Sequence of Operation
    Electrical circuitry for units with steam or hot water heat is
    limited to the connections associated with the modulating
    valve actuator and the freezestat.
    Like the furnaces described earlier, steam and hot water
    heat control systems are wired to ensure that
    simultaneous heating and cooling do not occur. The
    supply fan will cycle “On” and “Off” with each call for heat
    during both an occupied and unoccupied period.
    Whenever there is a call for heat, the relay on the heat
    module energizes. This allows a modulated voltage
    signal to be sent to the “Wet” heat actuator. The value of
    this signal regulates the flow of steam or hot water
    through the coil by positioning the valve stem at some
    point between fully closed (6 VDC) and fully open (8.5
    VDC).
    Freeze Protection
    A freezestat is mounted inside the heat section of hot water and steam heat units to prevent the “wet” heat coil from
    freezing during the “Off” cycle.
    If the temperature of the air leaving the heating coils falls
    to 40 F, the freezestat normally open contacts close,
    completing the heat fail circuit on the UCM. When this
    occurs:
    a. The supply fan is turned “Off”.
    b. “Wet” heat actuator fully opens to allow hot wateror steam to pass through the heating coil and
    prevent freeze-up.
    c. A “Low Air Temperature Unit Trip” diagnostic is displayed on the Human Interface LCD screen.
    For heating control settings and time delay specifications,
    refer to Table 45, p. 158.
    Unit Startup Check List
    Use the following checklist, in conjunction with the
    “General Unit Requirement” checklist”, to ensure that the unit is properly installed and ready for operation. Be sure
    to complete all of the procedures described in this section
    before starting the unit for the first time.
    [ ]Turn the field supplied disconnect switch, located
    upstream of the rooftop unit, to the “Off” position.
     [ ] Turn the 115 volt control circuit switch 1S2 to the “Off” position. It is located in the secondary of the 1T1transformer.
     [ ]Turn the 24 volt control circuit switch 1S3 to the “Off” position.
     It is located in the secondary of the 1T2 - 1T5
    transformers.
     [ ] Turn the “System” selection switch (at the Remote P
     anel) to the “Off” position and the “Fan” selection
    switch (if Applicable) to the “Auto” or “Off” position.
     [ ] Check all electrical connections for tightness and “point
     of termination” accuracy.
     [ ] Verify that the condenser airflow will be unobstructed.
     [ ] Check the compressor crankcase oil level. Oil should be
     visible in the compressor oil sight glass. The oil
    level should be 1/2 to 3/4 high in the sight glass with the
    compressor “Off”.
     [ ] Verify that all refrigerant service valves are back seated
     on each circuit.
    Do not start the unit in the cooling mode if the ambient
    temperature
     is below the following minimum
    recommended operating temperature:
    Standard unit with or without HGBP-+45°F
     [ ] Check the supply fan belts for proper tension and the fan
     bearings for sufficient lubrication. If the belts
    require adjustment, or if the bearings need lubricating,
    refer to the Service/Maintenance section of this
    manual for instructions.
     [ ] Inspect the interior of the unit for tools and debris. Install
     all panels in preparation for starting the unit.
    Electrical Phasing
    Scroll compressors are phase sensitive. Proper phasing of
    the electrical supply to the unit is critical for proper
    operation and reliability. The compressor motor is
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury.
    CAUTION
    Compressor Damage!
    Do not allow liquid refrigerant to enter the suction line.
    Excessive liquid accumulation in the liquid lines could
    result in compressor damage.Compressor service
    valves must be fully opened before startup (suction,
    discharge, liquid line, and oil line). 
    						
    All Trane manuals Comments (0)