Trane Intellipak 2 Service Manual
Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Service and Maintenance RT-SVX24K-EN181 Fan Belt Adjustment The supply fan belts and optional exhaust fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length. When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base. Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent), see Figure 121, adjust the belt tension as follows: 1. To determine the appropriate belt deflection: a. Measure the center-to-center shaft distance (ininc hes) between the fan and motor sheaves. b. Divide the distance measured in Step 1a by 64; the resulting value represents the amount of belt deflection that corresponds to the proper belt tension. Table 57. Grease Recommendation Recommended Grease for Fan Bearings Recommended Operating Range Exxon Unirex #2 Mobil 532 -20 F to 250 F Mobil SHC #220 Texaco Premium RB Table 58. Air-Cooled Condenser—Refrigerant Coil Fin Data Tons Coil Type Coil Fin Config. Tube Dia. Coil Rows Fins per foot Coil Face Area (sq. ft.) Tube Type 90 Evaporator Enhanced 1/2 3 16873.75 Internally Finned Hi-Cap Evap Enhanced 1/2 5168 73.75 Internally Finned Condenser Enhanced 25 mm 1240 134 Microchannel 105 EvaporatorInternally Finned 1/2 4 168 73.75 Internally Finned Hi-Cap Evap Internally Finned 1/2 6 168 73.75 Internally Finned Condenser Enhanced 25 mm 1 240 161 Microchannel 120 Evaporator Internally Finned 1/2 3 168 106.25 Internally Finned Hi-Cap Evap Internally Finned 1/2 6 168 106.25 Internally Finned Condenser Enhanced 18 mm 2 276 161 Microchannel 130Evaporator Internally Finned 1/2 4 168 106.25 Internally Finned Hi-Cap Evap Internally Finned 1/2 6 168 106.25 Internally Finned Condenser Enhanced 18 mm 2 276 161 Microchannel 150Evaporator Internally Finned 1/2 6 168 106.25 Internally Finned Condenser Smooth 18 mm 2 276 161 Microchannel WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN
Service and Maintenance 182RT-SVX24K-EN 2. Set the large O-ring on the belt tension gauge at the deflection value determined in Step 1b. 3. Set the small O-ring at zero on the force scale of the g auge plunger. 4. Place the large end of the gauge at the center of the belt span; then depress the gauge plunger until the large O- ring is even with the top of the next belt—-or even with a straightedge placed across the fan and motor sheaves. See Table59, p. 183. 5. Remove the belt tension gauge. The small O-ring now indicates a number other than zero on the plunger’s force scale. This number represents the force (in pounds) required to give the needed deflection. 6. Compare the “force” scale reading (Step 5) with the appropriate “force” value listed in Table59, p. 183.If the “force ”reading is outside the range, readjust the belt tension. Note: Actual belt deflection “force” must not exceed the maximum “force” value shown in Table 59, p. 183. 7. Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension will decrease rapidly until the new belts are “run in”. Figure 121.Tension GaugeFigure 122.Belt Tension
Service and Maintenance RT-SVX24K-EN183 Scroll Compressor Replacement The compressor manifold system was purposely designed to provide proper oil return to each compressors. The refrigerant manifold system must not be modified in any way. Note: Altering the compressor manifold piping may cause oil return problems and compressor failure. Should a compressor replacement become necessary and a suction line filter drier is to be installed, install it a minimum of 18 inches upstream of the oil separator tee. See Figure 123, p. 183. Anytime a compressor is replaced, the oil for each compressor within the manifolded set must be replaced. The scroll compressor uses Trane OIL00079 (one quart container) or OIL00080 (one gallon container) without substitution. The appropriate oil charge for CSHN250 and CSHN315 scroll compressors is 14.2 pints. For CSHN374 scroll compressor, use 15.2 pints. The recommended method for evacuation and dehydration is to evacuate both the high side and the low side to 500 microns or less. To establish that the unit is leak-free, use a standing vacuum test. The maximum allowable rise over a 15 minute period is 200 microns. If the rise exceeds this, there is either still moisture in the system or a leak is present. Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all Federal, State and local laws. Table 59. Belt Tension Measurement and Deflection Ranges Belt Cross Section Smallest Sheave Diameter Range (In.) RPM Range Belt Deflection Force (Lbs.) Super Gripbelts and Unnotched Gripbands Gripnotch Belts and Notched Gripbands Min. Max. Min. Max. A, AX 3.0-3.6 1000-2500 3.7 5.54.1 6.1 3.8-4.8 1000-2500 4.5 6.85.0 7.4 5.0-7.0 1000-2500 5.4 8.05.7 8.4 B, BX3.4 – 4.2 860-2500 ----4.9 7.2 4.4 – 5.6 860-2500 5.37.97.110.5 5.8 – 8.6 860-2500 6.39.48.512.6 3V, 3VX2.2 - 2.4 1000-2500 ----3.3 4.9 2.65 - 3.65 1000-2500 3.6 5.14.2 6.2 4.12 - 6.90 1000-2500 4.9 7.35.3 7.9 5V, 5VX4.4 – 6.7500-1749 1750-3000 -- -- 10.2 8.8 15.2 13.2 7.1 –10.9 500-1740 12.7 18.9 14.8 22.1 11.8-16.0 500-1740 15.5 23.417.125.5 Figure 123.Suction Line Filter/Drier Installation Sight glass Suction servicevalve Replaceable core drier Note: These components are also located at circuit #1 side
Service and Maintenance 184RT-SVX24K-EN VFD Programming Parameters Units shipped with an optional variable frequency drive (VFD) are preset and run tested at the factory. If a problem with a VFD occurs, ensure that the programmed parameters listed inTable 60, p. 185have been set before replacing the drive. Note: Check to make sure that parameter 1-23 is set to 60 Hz.To check parameter 1-23 press the [Main Menu] button (press [Back] button if the main menu does not display), use the [▼] button to scroll down to Load & Motor, press OK, use the [▼] button to select 1-2, press OK, and finally use the [▼] button until parameter 1-23 is displayed. Parameter 1-23 can then be modified by pressing OK button and using [▲] and [▼] buttons. When the desired selection has been made, press the OK button. Should replacing the VFD become necessary, the replacement is not configured with all ofTranes operating parameters. The VFD must be programmed before attempting to operate the unit. To verify and/or program a VFD, use the following steps: 1. At the unit, turn the 115 volt control circuit switch to the “Off” position. 2. Turn the 24 volt control circuit switch to the “Off position. HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. 3. To modify parameters: a. Press Main Menu button (press [Back] button if themain menu does not display) b. Use the [▲] and [▼] buttons to find the parameter menu group (first part of parameter number) c. Press [OK] d. Use the [▲] and [▼] buttons to select the correct parameter sub-group (first digit of second part of parameter number) e. Press [OK] f. Use the [▲] and [▼] buttons to select the specific parameter g. Press [OK] h. To move to a different digit within a parameter setting, use the [ ►◄] buttons (Highlighted area indicates digit selected for change) i. Use the [▲] and [▼] buttons to adjust the digit j. Press [Cancel] button to disregard change, or press [OK] to accept change and enter the new setting 4. Repeat step (3) for each menu selection setting in Table 60, p. 185. 5. To reset all programming parameters back to the factory defaults: a. Go to parameter 14-22 Operation Mode b. Press [OK] c. Select “Initialization” d. Press [OK] e. Cut off the mains supply and wait until the displayturns off. f. Reconnect the mains supply - the frequency converter is now reset. WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN
Service and Maintenance RT-SVX24K-EN185 g. Ensure parameter 14-22 Operation Mode has reverted back to “Normal Operation”. Notes: Item 5 resets the drive to the default factory settings. The program parameters listed in Table 60, p. 185will need to be verified or changed as described in Item 3 and 4. Some of the parameters listed in the Table are motor specific. Due to various motors and efficiencies available, use only the values stamped on the specific motor nameplate. Do not use the Unit nameplate values. A backup copy of the current setup may be saved to the LCP before changing parameters or resetting the drive. See LCP Copy in the VFD Operating Instructions for details. 6. Follow the startup procedures for supply fan in the “Variable Air Volume System” section or the “Exhaust Airflow Measurement” startup proceduresfor the exhaust fan. 7. After verifying that the VFD(s) are operating properly , press the STOP key at the Human Interface Module to stop the unit operation. 8. Follow the applicable steps in the “Final Unit Chec kout” section to return the unit to its normal operating mode. Note: If a problem with a VFD occurs, ensure that the programmed parameters listed for supply and exhaust VFD Table 60, p. 185 andTable 61, p. 190 have been set before replacing the drive. Monthly Maintenance Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open. Filters Inspect the return air filters. Clean or replace them if necessary. Refer to Table 55, p. 179andTable 56, p. 180 for filter information. Cooling Season [ ] Check the unit drain pans and condensate piping to ensure that there are no blockages. [ ] Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in “Coil Cleaning” later in this section. [ ] Manually rotate the condenser fans to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight. [ ] Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary. Table 60. Supply and Exhaust VFD Programming Parameters Menu Parameter Description SettingDescription Load & Motor 1-21 Motor Power Set Based on Motor Nameplate Set only for application using 3hp motors. Set to 2.2 kW/3 hp 1-22 Motor Voltage Set Based on Motor Nameplate Set only for 380/415 50 Hz applications 1-24 Motor Current Set Based on Motor Nameplate Sets the motor FLA 1-25 Motor Speed Set Based on Motor Nameplate Sets the motor RPM Limits & Warnings 4-18 Current Limit Rated Current 100% Limits the maximum current to motor Notes: 1. These parameters are motor specific and the actual motor nameplate rating must be used. Do not use the unit nameplate. WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN WARNING Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury.
Service and Maintenance 186RT-SVX24K-EN [ ] Verify that all damper linkages move freely; lubricate with white grease, if necessary. [ ] Check supply fan motor bearings; repair or replace the motor as necessary. [ ] Check the fan shaft bearings for wear. Replace the bearings as necessary. [ ] Lubricate the supply fan shaft bearings with a lithium based grease. Refer to Table57, p.181for recommended greases. Note: The bearings are manufactured using a special synthetic lithium based grease designed for long life and minimum lube intervals. Over lubrication can be just as harmful as not enough. Use a hand grease gun to lubricate these bearings; add grease until a light bead appears all around the seal. Do not over lubricate! After greasing the bearings, check the setscrews to ensure that the shaft is held securely to the bearings and fan wheels. Make sure that all bearing supports are tight. [ ] Check the supply fan belt(s). If the belts are frayed or worn, replace them. Refer to the “Fan Belt Adjustment” section for belt replacement and adjustments. [ ] Check the condition of the gasket around the control panel doors.These gaskets must fit correctly and be in good condition to prevent water leakage. [ ] Verify that all wire terminal connections are tight. [ ] Remove any corrosion present on the exterior surfaces of the unit and repaint these areas. [ ] Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.) [ ] Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete. [ ] With the unit running, check and record the: ambient temperature; compressor oil level (each circuit); compressor suction and discharge pressures (each circuit); superheat and subcooling (each circuit); Record this data on an “operator’s maintenance log” like the one shown in Table 63, p. 191. If the operating pressures indicate a refrigerant shortage, measure the system superheat and system subcooling. For guidelines, refer to “Charging by Subcooling”. Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state and local laws. Heating Season Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open. Inspect the unit air filters. If necessary, clean or replace them. Check supply fan motor bearings; repair or replace the motor as necessary. Lubricate the supply fan shaft bearings with a lithium based grease. Refer to Table57, p.181for recommended greases. Note: The bearings are manufactured using a special synthetic lithium based grease designed for long life and minimum lube intervals. Too much lubrication in a bearing can be just as harmful as not enough. Use a hand grease gun to lubricate the bearings; add grease until a light bead appears all around the seal. Do not over lubricate! After greasing the bearings, check the setscrews to ensure that the shaft is held securely. Make sure that all bearing braces are tight. [ ] Inspect both the main unit control panel and heat section control box for loose electrical components and terminal connections, as well as damaged wire insulation. Make any necessary repairs. [ ] Gas Heat Units only - Check the heat exchanger for an y corrosion, cracks, or holes. [ ] Check the combustion air blower for dirt. Clean as necessary . Note:Typically, it is not necessary to clean the gas furnace. However, if cleaning does become necessary, remove the burner inspection plate from the rear of the heat exchanger to access the drum. Be sure to replace the existing gaskets with new ones before reinstalling the inspection plate. WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN
Service and Maintenance RT-SVX24K-EN187 [ ] Open the main gas valve and apply power to the unit heating section; then initiate a “Heat” test using the startup procedure described in “Gas Furnace Startup”. [ ] Verify that the ignition system operates properly. Air-Cooled Coil Cleaning Regular coil maintenance, including annual cleaning enhances the unit operating efficiency by minimizing: – compressor head pressure and amperage draw; – water carryover; – fan brake horsepower; and, – static pressure losses At least once each year—or more often if the unit is located in a “dirty” environment—clean the evaporator and Microchannel Condenser Coil and Hot Gas Reheat Coil using the instructions outlined below. Follow these instructions as closely as possible to avoid damaging the coils. Refrigerant Coils To clean refrigerant coils, use a soft brush and a sprayer. Important: DO NOT use any detergents with microchannel condenser coils. Pressurized water or air ONLY. For evaporator and reheat coil cleaners, contact the local Trane Parts Center for appropriate detergents. 1. Remove enough panels from the unit to gain safe access to coils. Important: Bridging between the main supports required before attempting to enter into the unit. Bridging may consist of multiple 2 by 12 boards or sheet metal grating. 2. Straighten any bent coil fins with a fin comb. 3. For accessible areas, remove loose dirt and debris from both sides of the coil. For dual row microchannel condenser coil applications, seek pressure coil wand extension through the local Trane Parts Center. 4. When cleaning evaporator and reheat coils, mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution to 150° F maximum to improve its cleansing capability. Important: DO NOT use any detergents with microchannel coils. Pressurized water or air ONLY. 5. Pour the cleaning solution into the sprayer. If a high- pressure sprayer is used: a. The minimum nozzle spray angle is 15 degrees. b. Do not allow sprayer pressure to exceed 600 psi. WARNING Hazardous Gases and Flammable Vapors! Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures or lead to excessive carbon monoxide. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual. Failure to follow all instructions could result in death or serious injury. WARNING Hazardous Pressures! When using dry nitrogen cylinders for pressurizing units for leak testing, always provide a pressure regulator on the cylinder to prevent excessively high unit pressures. Never pressurize unit above the maximum recommended unit test pressure as specified in applicable unit literature. Failure to properly regulate pressure could result in a violent explosion, which could result in death or serious injury or equipment or property-only-damage. WARNING Hazardous Chemicals! Coil cleaning agents can be either acidic or highly alkaline and can burn severely if contact with skin occurs. Handle chemical carefully and avoid contact with skin. ALWAYS wear Personal Protective Equipment (PPE) including goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices. Failure to follow all safety instructions could result in death or serious injury. WARNING No Step Surface! Do not walk on the sheet metal base. Walking on the base could cause the supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this recommendation could result in death or serious injury.
Service and Maintenance 188RT-SVX24K-EN c. Spray the solution perpendicular (at 90 degrees) to the coil face. d. For evaporator and reheat coils, maintain a minimum clearance of 6 between the sprayer nozzle and the coil. For microchannel condenser coils, optimum clearance between the sprayer nozzle and the microchannel coil is 1-3”. 6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. For evaporator and reheat coils, allow the cleaning solution to stand on the coil for five minutes. 7. Rinse both sides of the coil with cool, clean water. 8. Inspect both sides of the coil; if it still appears to be dir ty, repeat Steps 6 and 7. 9. Reinstall all of the components and panels removed in Step 1; then restore power to the unit. 10. For evaporator and reheat coils, use a fin comb to straighten any coil fins which were inadvertently bent during the cleaning process. Steam or Hot Water Coils To clean a steam or hot water coil, use a soft brush, a steam-cleaning machine, and water. 1. Verify that switches 1S1 and 1S70 are turned “OFF”, and that the main unit disconnect is locked open. 2. Remove enough panels and components from the unit to gain sufficient access to the coil. 3. Straighten any bent coil fins with a fin comb. (Use the data inTable 58, p.181to determine the appropriate fin comb size.) 4. Remove loose dirt and debris from both sides of the coil with a soft brush. 5. Use the steam-cleaning machine to clean the leaving- air side of the coil first; start at the top of the coil and work downward; then clean the entering-air side of the coil, starting at the top of the coil and working downward. 6. Check both sides of the coil; if it still appears dirty, repeat Step 5. 7. Reinstall all of the components and panels removed in Step 2; then restore power to the unit. Evaporative Condenser Coil Cleaning Sump Water Management Water Supply Overall performance of any water- cooled device can be affected by suspended particulates, mineral concentration, trash and debris resulting in clogging and heat transfer loss.The unit is designed to greatly minimize problems with these impurities, however, float valves and solenoid valves are used to control the incoming water. If the incoming water contains contaminants, sand or other objects, it is best to insert an incoming line strainer having a mesh of 80 to 100.The inlet line should be flushed prior to connection to the unit, whether or not there is a strainer. There is an air gap between the water inlet float valve and sump water level to prevent back flow; however, if local code dictates, a backflow prevention valve may be required (field-provided and installed by a qualified technician). Water Drain Local Site Discharge: Rooftop or simple storm sewer discharge is generally acceptable. Do not routinely direct the sump discharge onto an area that will be adversely affected. For example, continued sump discharge into a flower bed where the input water contains CaCO3 (lime) will eventually decrease the pH of the soil. Sewer Discharge: The quantities of mineral and debris flushed are actually very small and do not cause problems when diluted in normal sewer flow. However, local, state or federal standards and restrictions must be followed in any given locality. Traditional Bleed Method ASHRAE recommendation for continuous bleed rates: With good, quality makeup water, the bleed rates (0.8 - 2 GPH/ton) may be as low as one-half the evaporation rate (1.6 -2 GPH), and the total water consumption would range from 2.4 GPH/ton for air conditioning to 3 GPH/ton for refrigeration (Chapter 36.17 of ASHRAEs “Systems and Equipment Handbook”) Operation and Care The sump should be inspected at least every 6 months for possible build up of scale pieces that has been shed from the coils. The sump flush frequency or bleed rate should be increased if large amounts of scale are present. If the water has a “milky or cloudy” appearance, then minerals are concentrating in the sump and the number of flushes should be increased. If the water remains clear between flushes, then the number of flushes can be decreased. Through field trials, the optimum flush frequency can be determined. Please note that in some areas, water quality can vary during WARNING No Step Surface! Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this recommendation could result in death or serious injury.
Service and Maintenance RT-SVX24K-EN189 different times of the year. The sump water clarity should be checked periodically. The evaporative condenser has several design features to reduce the possibility of biological growth in the sump. These features include: air inlets constructed to eliminate direct sunlight in the sump The sump flush sequence replenishes the sump with fresh water 1 to 12 times per day depending on the flush setting The copper tubing in the coils is a natural biocide Important: Do not use chlorine tablets directly on stainless steel surface as it can adversely affect its corrosion resistance. Always consult local codes for water treatment and waste water removal requirements. Consult a water treatment expert for water analysis and chemical treatment methods and recommendations for specific applications. If deemed necessary after consultation with local water experts, there are various means of water treatment available which can be field installed. Microchannel Condenser Coil Repair and Replacement If microchannel condenser coil repair or replacement is required, seek HVAC Knowledge Center information or Service Guide document RT-SVB83*-EN for further details.
Service and Maintenance 19 0RT-SVX24K-EN Final Process Record the unit data in the blanks provided. Table 61. Evaporative Condenser Models—Maintenance and Troubleshooting Maintenance Schedule Component Action Frequency Comments Fan Motor None Required Non-grease bearings Sump Pump Inspect / Clean 1 – 2 times per year Clean inlet openings to pump Sump Inspect / Clean 1 – 2 times per year depending on water hardness and unit run time Sump can be drained and hosed out using hose bib provided at water fill solenoid valve. Vacuuming scale out is an alternate method Sump Float Switch Inspect 1 – 2 times per year Float should be free for full float travel Sump Float Make Up Valve Inspect for proper water level 1 – 2 times per year Spray Nozzles Inspect / Clean 1 – 2 times per year Inspection through access panel Conductivity Sensor Inspect / Clean 1 – 2 times per year Clean sensor to ensure accurate readings Conductivity Controller Inspect / Recalibrate 1 – 2 times per year Recalibrate controller Troubleshooting Component Problem Check Fix Fan Motor Does not run Condenser Fan Relay closure and control voltage indicating a call from compressor control panel for the condenser fan to operate. Sump Pump Overload Trip. Fan Motor Overload Trip. Fan fuse trip. Check each motor overload and reset if necessary. Check amp draw for each leg. Sump Pump Does not run Sump Pump Overload Trip Low Water Level or faulty float switch. Unit in ‘Dry Mode’ Operation Reset – check amps on each leg to determine if faulty motor. Check and clean debris around float switch. Check Ambient thermostat setting and mode of operation (close on rise). See section 2 for T’stat setup instructions. Sump Pump Low Flow Pump may be operating backwards or impeller inlet may be slightly blocked. Change pumping direction by changing any two legs to the pump motor. Disconnect Power and remove pump to inspect for possible impeller obstruction. Spray Nozzle Dry area on coil Check for proper spray pattern over each quadrant. Remove debris from clogged nozzle. Table 62. Unit Data Log Complete Unit Model Number: Unit Serial Number: Unit “DL” Number (“design special” units only): Wiring Diagram Numbers (from unit control panel): -schematic(s) -connections Network ID (LCI/BCI):