Home > Trane > Air Conditioner > Trane Intellipak 2 Service Manual

Trane Intellipak 2 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							General Information
    RT-SVX24K-EN21
    prevent over/under pressurization. The overall scheme
    will remain very similar to VAV units with Space Pressure
    Control with the exception of the dynamic Exhaust Enable
    Setpoint.
    For SZVAV an Exhaust Enable Setpoint must be selected
    during the 100% Fan Speed Command. Once selected, the
    difference between the Exhaust Enable Setpoint and
    Design OA Damper Minimum Position at 100% Fan Speed
    Command will be calculated.The difference calculated will
    be used as an offset and added to the Active Building
    Design OA Minimum Position Target in order to calculate
    the dynamic Exhaust Enable Target, which will be used
    throughout the Supply Fan Speed/OA Damper Position
    range.
    The Exhaust Enable Target could be above or below the Active Building Design OA Minimum Position TargetSetpoint, based on the Active Exhaust Enable Setpoint
    being set above or below the Building Design Minimum
    Position at 100% Fan Speed Command. Note that an
    Exhaust Enable Setpoint of 0% will result in the same effect
    on Exhaust Fan control as on VAV applications with and
    without Statitrac.
    Occupied Cooling Operation
    For normal cooling operation, cooling capacity will be
    staged or modulated in order to meet the calculated
    discharge air target setpoint. If the current active cooling
    capacity is controlling the discharge air within the
    deadband, no additional cooling capacity change will be
    requested. As the Discharge Air Temperature rises above
    the deadband, the algorithm will request additional
    capacity as required (additional compressors or
    economizer). As the Discharge AirTemperature falls below
    the deadband, the algorithm will request a reduction in
    active capacity.
    Default Economizer Operation
    By default, the unit will be setup to optimize the minimum
    supply fan speed capability during Economizer Only
    operation. If the economizer is able to meet the demand
    alone, due to desirable ambient conditions, the supply fan
    speed will be allowed to increase above the minimum
    prior to utilizing mechanical cooling if discharge air
    setpoint falls below the discharge air Lower Limit
    (Cooling) setpoint.
    Unoccupied Mode
    In Unoccupied mode the unit will utilize setback setpoints,
    0% Minimum OA Damper position, and Auto Fan Mode
    operation as on normal CV units. The Supply Fan speed,
    and cooling and modulating types of heat, will be
    controlled to the discharge air target setpoint as is done
    during occupied periods. The Supply fan speed during
    staged heat control will be forced to 100% as on normal CV
    units.
    Occupied Heating Operation
    Occupied heating operation has two separate control
    sequences; staged and modulated. All staged heating
    types will drive the supply fan to maximum flow and stage
    heating to control to the Zone Heating Setpoint. For units
    with Hydronic and Gas heat, modulated SZVAV Heating.
    On an initial call for heating, the supply fan will drive to the
    minimum heating airflow.
    On an additional call for heating, the heat will control in
    order to meet the calculated discharge air target setpoint.
    As the load in the zone continues to request heat operation, the supply fan will ramp-up while the control
    maintains the heating discharge air temperature. Heating
    can be configured for either the energy saving SZVAV
    Heating solution as described above, or the traditional,
    less efficient CV Heating solution.
    Compressor (DX) Cooling
    Compressor control and protection schemes will function
    identical to that of a traditional unit. Normal compressor
    proving and disable input monitoring will remain in effect
    as well as normal 3-minute minimum on, off, and inter-
    stage timers. Also, all existing head pressure control
    schemes will be in effect.
    Cooling Sequence
    If the control determines that there is a need for active
    cooling capacity in order to meet the calculated discharge
    air target setpoint, once supply fan proving has been
    made, the unit will begin to stage compressors
    accordingly. Note that the compressor staging order will
    be based on unit configuration and compressor lead/lag
    status.
    Once the discharge air target setpoint calculation has
    reached the Minimum Setpoint and compressors are
    being utilized to meet the demand, as the discharge air
    target setpoint value continues to calculate lower the
    algorithm will begin to ramp the supply fan speed up
    toward 100%. Note that the supply fan speed will remain
    at the compressor stage’s associated minimum value (as
    described below) until the discharge air target setpoint
    value is calculated below the discharge air temperature
    Minimum Setpoint (limited discharge air target setpoint).
    As the cooling load in the zone decreases the zone cooling algorithm will reduce the speed of the fan down to
    minimum per compressor stage and control the
    compressors accordingly. As the compressors begin to
    de-energize, the supply fan speed will fall back to the
    Cooling Stage’s associated minimum fan speed, but not
    below. As the load in the zone continues to drop, cooling
    capacity will be reduced in order to maintain the discharge
    air within the ± ½ discharge air target deadband.
    Fault Detection and Diagnostics
    Fault Detection of the Outdoor Air Damper will be
    evaluated based on the commanded position of the
    damper compared to the feedback position of the damper. 
    						
    							General Information
    22RT-SVX24K-EN
    The damper is commanded to a position based on a 2-10
    VDC signal. If the Damper position is outside of ±10% of the commanded position, a diagnostic is generated.
    Unit Not Economizing when it should be:
    The Unit is operating in Cooling Mode, Economizing is enabled and/or Mechanical Cooling is enabled. If the
    Commanded Economizer Position is greater than Current
    Economizer Feedback Position + 10% for 5 continuous
    minutes, Unit Not Economizing when it should be
    diagnostic is generated.
    Unit Economizing when it should not be:
    The unit is operating in Cooling Mode, Economizing is enabled and or Mechanical Cooling is enabled. If the
    commanded Economizer Position is less than the current
    Economizer Feedback Position - 10% for 5 continuous
    minutes, Unit Economizing When it should not be
    diagnostic is generated.
    Outdoor Air Damper Not Modulating
    The unit is operating in Ventilation Only Mode - not attempting to Economize and the Commanded Damper
    Position is greater than the Current Damper Feedback
    Position + 10% for 5 continuous minutes, Outdoor Air
    Damper Not Modulating diagnostic is generated.
    Excessive Outdoor Air
    The unit is operating in Ventilation Only Mode - not attempting to Economize and the Commanded Damper
    Position is less than the Current Damper Feedback Position
    - 10% for 5 continuous minutes. Excessive Outdoor Air
    diagnostic is generated.
    To change the Economizer Control Function to dry bulb, go to the Configuration Menu on the Human Interface Module
    and set Comparative Enthalpy to Not Installed.This
    allows the user to select dry bulb under the Economizer
    Control Function which is a Submenu of the Setup Menu.
    For additional instructions please see the Programming
    and Troubleshooting Guide. 
    						
    							RT-SVX24K-EN23
    Unit Clearances
    Figure 10. Minimum required clearance(a)
    (a) Unit drawing is representative only and may not accurately depict all mo\
    dels.
    Filters
    VFDVFDHeat
    Rtn/Exh
    MtrRtn/Exh
    VFDEvp(F)Fltr(F)SupMtrSup
    VFD
    Fltr(R)Evp(R)
    Heat(L&R
    Option
    Option
    As Req. As Req. As Req.
    Std
    Std Std
    Std
    Blank Section
    Final 
    Filter
    Fnl
    Fltr 
    As Req.
    Fnl
    Fltr  As Req.
    Ctrl Box(L&R)Std
    OutsideAir
    OutsideAir
      Exhaust
    Condenser
    Condenser
    Exh
    AH  R
    CBox
    AH  LCond L
    Cond R
    Left Side
    Table 4. Minimum required clearance
    Unit Option Selection (Door Swing Ft. and In.)
    Standard VFD Two-side Access
    Door Location Availability 90-118 120-162 Return/ 
    Exhaust Supply Heat Reheat 90-118 120-162  Final 
    Filter Energy 
    Recovery
    Exhaust/Ret Motor Std 2 2 2 2 * * * * * * *
    Exhaust/Ret VFD As Req. * * 2 2 * * * * * *
    ERW Fltr
    (a) (L & R) (F) Option * * * * * * * * * 2 2
    ERW Fltr(a) (L & R) (R) Option * * * * * * * * * 2 2
    Filter (Front) Std 2 8 2 8 * * * * * * *
    Filter (Rear) Option * * * * * * 2 2 2 8 *
    Evap (Front) Std 2 2 2 2 * * * * * * *
    Evap (Rear) Std 2 8 * * * * * * * *
    or Evap (Rear) Option * * * * * 2 2 * 2 2 *
    Supply Motor Std 2 8 2 8 * * * * * * *
    Supply VFD As Req. * * * 2 2 * * * * *
    Heat (Left & Right) As Req. * * * * 2 2 * * * * Final Filter (Front) As Req. * * * * * * * * 2 2
    Final Filter (Rear) As Req. * * * * * * * * 2 2
    Control Box (L & R) Std 3 2 3 2 * * * * * * *
    Minimum Required Clearance (Ft.)
    AH_L AH_R Exh Cond_L Cond_R Control 
    Box
    8 88 8 8 6
    (a) See Unit Dimensions for Energy Recovery Wheel location. 
    						
    							Unit Clearances
    24RT-SVX24K-EN
    Notes:
     1. Stagger units to minimize span deflection which deters sound 
    transmission and to maximize proper diffusion of the exhaust air 
    before it reaches the adjacent unit outside air intake.
     2. Cooling tower should be 5 feet above or 20 feet away from the outside 
    air intake. For additional information, see 2007 ASHRAE Handbook: 
    HVAC Applications, page 44.4.
    Figure 11. Multiple unit placement
    Outdoor
    Air Intake
    Outdoor
    Air Intake
    Exhaust Air 
    Outdoor
    Air Intake
    Outdoor
    Air Intake
    Exhaust Air 
    Outdoor
    Air Intake
    Outdoor
    Air Intake
    Exhaust Air 
    Minimum distance between units must be 16’! 
    						
    							RT-SVX24K-EN25
    Dimensional Data
    Figure 12. Unit Top/Front View
    1-1/4 NPT. DRAIN
    2X TYP. LEFT & RIGHT SIDES OF UNIT
    Detail A 
    						
    							Dimensional Data
    26RT-SVX24K-EN
    Table 5. Unit dimensions (in.)—one-piece unit air-cooled
    ONE-PIECE Dimensions without Energy Recovery Wheel (ERW)
    Tonnage  Blank 
    Section Unit Dimensions Lifting Lug Locations
    Unit Width
    Air Handler Side Condenser 
    Side
    A B C1 C2 C3 D1 M N
    90  None 437  3/16 159 15/16 66       252 14/16 N/A 27 11/16 139 13/16 143  8/16
    90  4 ft 485  6/16 159 15/16 66       252 14/16 N/A 54  2/16 139 13/16 143  8/16
    90 8 ft 533  9/16 159 15/16 66       252 14/16 N/A 54  2/16 139 13/16 143  8/16
    105 None 455  3/16 159 15/16 66       252 14/16 N/A 27 11/16 139 13/16 143  8/16
    105 4 ft 503  6/16 159 15/16 66       252 14/16 N/A 54  2/16 139 13/16 143  8/16
    105 8 ft 551  9/16 159 15/16 66       252 14/16 N/A 54  2/16 139 13/16 143  8/16
    120-150 (All  Units Except  High Heat 
    Gas Models)  None 528 15/16 197  1/16 66       269  6/16 N/A 63  2/16 139 13/16 143  8/16
    120-150 (All  Units Except  High Heat 
    Gas Models)  4 ft 577  2/16 197  1/16 66       269  6/16 N/A 63  2/16 139 13/16 143  8/16
    120-150 
    (High Heat 
    Gas Models  Only)  None 540 15/16 197  1/16 66       269  6/16 N/A 63  2/16 139 13/16 143  8/16
    Tonnage 
    Blank 
    Section Unit Height Return Fan
    Exhaust 
    Fan
    OP RJK
    90-150  None 103 12/16 97  9/16 103  7/16 29  3/16 17      
    90-150  4 ft 103 12/16 97  9/16 103  7/16 29  3/16 17      
    90-150  8 ft 103 12/16 97  9/16 103  7/16 29  3/16 17      
    ONE-PIECE Dimensions with Energy Recovery Wheel
    Tonnage  Blank 
    Section Unit Dimensions Lifting Lug Locations
    Unit Width
    Air Handler Side Condenser 
    Side
    A B C1 C2 C3 D1 M N
    90  None 533  9/16 256  5/16 66       201  1/16 349  4/16 27 11/16 139 13/16 143  8/16
    90  4 ft 581 13/16 256  5/16 66       201  1/16 349  4/16 54  2/16 139 13/16 143  8/16
    105 None 551  9/16 256  5/16 66       201  1/16 349  4/16 27 11/16 139 13/16 143  8/16
    105 4 ft 599 13/16 256  5/16 66       201  1/16 349  4/16 54  2/16 139 13/16 143  8/16
    Unit Height Return FanExhaust 
    Fan
    Tonnage  Blank 
    Section O PRJK
    90  None 103 12/16 97  9/16 103  7/16 N/A 17
    90  4 ft 103 12/16 97  9/16 103  7/16 N/A 17
    105 None 103 12/16 97  9/16 103  7/16 N/A 17
    105 4 ft 103 12/16 97  9/16 103  7/16 N/A 17 
    						
    							Dimensional Data
    RT-SVX24K-EN27
    Table 6. Unit dimensions (In.)—two-piece unit air-cooled
     TWO-PIECE Dimensions without Energy Recovery Wheel (ERW)
    Tonnage  Blank 
    Section Unit Dimensions Lifting Lug Locations
    Air Handler Side
    A B E F C1 C2 C3 C4
    90  None 454  4/16 159 15/16 330 14/16 121  6/16 66       252 14/16 N/A N/A
    90  4 ft 502  7/16 159 15/16 379  1/16 121  6/16 66       252 14/16 368  6/16 N/A
    90 8 ft 550 11/16 159 15/16 427  4/16 121  6/16 66       252 14/16 416 10/16 N/A
    105 None 472  4/16 159 15/16 330 14/16 139  6/16 66       252 14/16 N/A N/A
    105 4 ft 520  7/16 159 15/16 379  1/16 139  6/16 66       252 14/16 368  6/16 N/A
    105 8 ft 568 11/16 159 15/16 427  4/16 139  6/16 66       252 14/16 416 10/16 N/A
    120-150 
    (All Units 
    Except High  Heat Gas Models)  None 546       197  1/16 395 10/16 148  6/16 66       269  6/16 384 15/16 N/A
    120-150 
    (All Units 
    Except High  Heat Gas Models)  4 ft 594  4/16 197  1/16 443 13/16 148  6/16 66       269  6/16 433  2/16 N/A
    120-150 
    (All Units 
    Except High  Heat Gas Models)  8 ft 642  7/16 197  1/16 492  1/16 148  6/16 66       269  6/16 481  6/16 N/A
    120-150 
    (High Heat 
    Gas Models  Only) None 558       197  1/16 407 10/16 148  6/16 66       269  6/16 396 15/16 N/A
    Tonnage 
    Blank 
    Section Lug Locations
    Unit Width Unit Height
    Condenser Side
    D1 D2 M N O P R
    90  None 16       112  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    90  4 ft 16       112  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    90 8 ft 16       112  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    105 None 16       130  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    105 4 ft 16       130  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    105 8 ft 16       130  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    120-150 
    (All Units 
    Except High  Heat Gas Models)  None 16       139  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    120-150 
    (All Units 
    Except High  Heat Gas Models)  4 ft
    16       139  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    120-150 
    (All Units 
    Except High  Heat Gas Models)  8 ft
    16       139  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    120-150 
    (High Heat 
    Gas Models  Only) None 16       139  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    Continued on next page 
    						
    							Dimensional Data
    28RT-SVX24K-EN
    Tonnage Blank 
    Section Return Fan Exhaust Fan
    JK
    90  None 29  3/16 17
    90  4 ft 29  3/16 17
    90 8 ft 29  3/16 17
    105 None 29  3/16 17
    105 4 ft 29  3/16 17
    105 8 ft 29  3/16 17
    120-150 
    (All Units 
    Except High  Heat Gas Models)  None 29  3/16
    17
    120-150 
    (All Units 
    Except High  Heat Gas Models)  4 ft 29  3/16
    17
    120-150 
    (All Units 
    Except High  Heat Gas Models)  8 ft 29  3/16
    17
    120-150 
    (High Heat 
    Gas Models  Only) None 29  3/16
    17
     TWO-PIECE Dimensions with Energy Recovery Wheel (ERW)
    Tonnage  Blank 
    Section Unit Dimensions Lifting Lug Locations
    Air Handler Side
    A B E F C1 C2 C3 C4
    90  None 550 11/16 256  5/16 427  5/16 121  6/16 66       201  1/16 349  4/16 N/A
    90  4 ft 598 14/16 256  5/16 475  8/16 121  6/16 66       201  1/16 349  4/16 464 13/16
    90 8 ft 647  2/16 256  5/16 523 12/16 121  6/16 66       201  1/16 349  4/16 513      
    105 None 568 11/16 256  5/16 427  5/16 139  6/16 66       201  1/16 349  4/16 N/A
    105 4 ft 616 14/16 256  5/16 475  8/16 139  6/16 66       201  1/16 349  4/16 464 13/16
    105 8 ft 665  2/16 256  5/16 523 12/16 139  6/16 66       201  1/16 349  4/16 513      
    120-150 
    (All Units 
    Except High  Heat Gas 
    Models)  None 642  7/16 293  8/16 492  1/16 148  6/16 66       238  5/16 365  5/16 480 14/16
    120-150 
    (All Units 
    Except High  Heat Gas Models)  4 ft 690 10/16 293  8/16 540  4/16 148  6/16 66       238  5/16 365  5/16 529  2/16
    120-150 
    (All Units 
    Except High  Heat Gas Models)  8 ft 738 14/16 293  8/16 588  8/16 148  6/16 66       238  5/16 365  5/16 577  5/16
    120-150 
    (High Heat 
    Gas Models  Only) None 654  7/16 293  8/16 504  1/16 148  6/16 66       238  5/16 365  5/16 492 14/16
    Continued on next page
    Table 6. Unit dimensions (In.)—two-piece unit air-cooled (continued) 
    						
    							Dimensional Data
    RT-SVX24K-EN29
    Tonnage Blank 
    Section Lug Locations
    Unit Width
    Condenser Side Unit Height
    D1 D2 M N O P R
    90  None 16       112  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    90  4 ft 16       112  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    90 8 ft 16       112  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    105 None 16       130  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    105 4 ft 16       130  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    105 8 ft 16       130  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    120-150 
    (All Units 
    Except High  Heat Gas Models)  None 16       139  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    120-150 
    (All Units 
    Except High  Heat Gas Models)  4 ft
    16       139  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    120-150 
    (All Units 
    Except High  Heat Gas Models)  8 ft
    16       139  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    120-150 
    (High Heat 
    Gas Models  Only) None 16       139  7/16 139 13/16 143  8/16 103 12/16 97  9/16 103  7/16
    Tonnage 
    Blank 
    Section Return Fan Exhaust Fan
    JK
    90 None N/A 17  
    90  4 ft N/A 17  
    90 8 ft N/A 17  
    105 None N/A 17  
    105 4 ft N/A 17  
    105 8 ft N/A 17  
    120-150 
    (All Units 
    Except High  Heat Gas Models)  None N/A
    17  
    120-150 
    (All Units 
    Except High  Heat Gas Models)  4 ft N/A
    17  
    120-150 
    (All Units 
    Except High  Heat Gas Models)  8 ft N/A
    17  
    120-150 
    (High Heat 
    Gas Models  Only) None N/A
    17  
    Table 6. Unit dimensions (In.)—two-piece unit air-cooled (continued) 
    						
    							Dimensional Data
    30RT-SVX24K-EN
    Table 7. Unit dimensions (in.)—two-piece unit evaporative condenser
     TWO-PIECE Dimensions without Energy Recovery Wheel (ERW)
    Tonnage  Blank 
    Section Unit Dimensions Lifting Lug Locations
    Air Handler Side
    A B E F C1 C2 C3 C4
    100-118  None 475  8/16 159 15/16 330 14/16 142 10/16 66       252 14/16 N/A N/A
    100-118  4 ft 523 12/16 159 15/16 379  1/16 142 10/16 66       252 14/16 368  6/16 N/A
    100-118  8 ft 571 15/16 159 15/16 427  5/16 142 10/16 66       252 14/16 416 10/16 N/A
    128-162 
    (All Units 
    Except High  Heat Gas Models)  None 540  5/16 197  1/16 395 10/16 142 10/16 66       269  6/16 384 15/16 N/A
    128-162 
    (All Units 
    Except High  Heat Gas Models)  4 ft 588  8/16 197  1/16 443 14/16 142 10/16 66       269  6/16 433  2/16 N/A
    128-162 
    (All Units 
    Except High  Heat Gas Models)  8 ft 636 11/16 197  1/16 492  1/16 142 10/16 66       269  6/16 481  6/16 N/A
    128-162 
    (High Heat 
    Gas Models 
    Only) None 552 5/16 197  1/16 407 10/16 142 10/16 66       269  6/16 396 15/16 N/A
    Tonnage 
    Blank 
    Section Lug Locations
    Condenser Side Unit Width Unit Height
    D1 D2 M N O P R
    100-118  None 16       133 11/16 139 13/16 143  8/16 103 12/16 97  9/16 102 12/16
    100-118  4 ft 16       133 11/16 139 13/16 143  8/16 103 12/16 97  9/16 102 12/16
    100-118  8 ft 16       133 11/16 139 13/16 143  8/16 103 12/16 97  9/16 102 12/16
    128-162 
    (All Units 
    Except High  Heat Gas Models)  None 16       133 11/16 139 13/16 143  8/16 103 12/16 97  9/16 102 12/16
    128-162 
    (All Units 
    Except High  Heat Gas Models)  4 ft 16       133 11/16 139 13/16 143  8/16 103 12/16 97  9/16 102 12/16
    128-162 
    (All Units 
    Except High  Heat Gas Models)  8 ft 16       133 11/16 139 13/16 143  8/16 103 12/16 97  9/16 102 12/16
    128-162 
    (High Heat 
    Gas Models  Only) None 16       133 11/16 139 13/16 143  8/16 103 12/16 97  9/16 102 12/16
    Continued on next page 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Intellipak 2 Service Manual