Home > Trane > Air Conditioner > Trane Intellipak 2 Service Manual

Trane Intellipak 2 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Unit Startup
    RT-SVX24K-EN161
    8. Tighten the set screw to the drive shaft.
    9. Stretch the belt over the pulley and engage it in the
    groo
     ve.
    Compressor Startup
    1. Ensure that the “System” selection switch at theremote panel is in the “Off” position.
    2. Before closing the disconnect switch, ensure that the compressor
     discharge service valve and the liquid line
    service valve for each circuit is back seated.
    3. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal
    block or the unit mounted disconnect switch to allow
    the crankcase heater to operate a minimum of 8 hours
    before continuing.
    4. Turn the 115 volt control circuit switch and the 24 volt control
     circuit switch to the “On” position.
    5. Open the Human Interface access door, located in the unit
     control panel, and press the SERVICE MODE key to
    display the first service screen. Refer to the latest
    edition of the applications programming guide for
    applications for the SERVICE TEST screens and
    programming instructions.
    6. Use Table37, p.11 2to program the following system
    components for operation by scrolling through the
    displays;
    Compressors
    Compressor 1A (On)
    Compressor 1B (Off)
    Compressor 2A(Off)
    Compressor 2B (Off)
    Condenser Fans
    1. Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. See
    Figure 115, p. 165 for the various compressor
    locations.
    2. Once the configuration for the components is complete,
     press the NEXT key until the LCD displays
    the “Start test in __Sec.” screen. Press the + key to
    designate the delay before the test is to start. This
    service test will begin after the TEST START key is
    pressed and the delay designated in this step has
    elapsed. Press the ENTER key to confirm this choice.
    3. Press the TEST START key to start the test. Remember that the delay designated in step 8 must elapse before
    the system will begin to operate.
    4. Once each compressor or compressor pair has started, verify
     that the rotation is correct. If a scroll compressor
    is rotating backwards, it will not pump and a loud
    rattling sound can be observed. Check the electrical
    phasing at the load side of the compressor contactor.
    If the phasing is correct, before condemning the
    compressor, interchange any two leads to check the
    internal motor phasing. If the compressor runs
    backward for an extended period (15 to 30 minutes),
    the motor winding can over heat and cause the motor
    winding thermostats to open. This will cause a
    “compressor trip” diagnostic and stop the compressor.
    5. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the compressor
    operation.
    6. Repeat steps 5 through 11 for each compressor stage and
     the appropriate condenser fans.
    Refrigerant Charging
    1. Attach a set of service gauges onto the suction anddischarge gauge ports for each circuit.
    See Figure 115, p. 165 for the various compressor
    locations.
    2. Open the Human Interface access door, located in the unit
     control panel, and press the SERVICE MODE key to
    display the first service screen. Refer to the latest
    edition of the applications programming guide for CV
    or VAV applications for the SERVICETEST screens and
    programming instructions.
    NOTICE:
    Compressors Failure!
    Unit must be powered and crankcase heaters energized
    at least 8 hours BEFORE compressors are started. This
    will protect the compressors from premature failure.
    CAUTION
    Compressor Damage!
    Do not allow liquid refrigerant to enter the suction line.
    Excessive liquid accumulation in the liquid lines could
    result in compressor damage.
    COMPRESSOR SERVICE VALVES MUST BE FULLY
    OPENED BEFORE STARTUP (SUCTION, DISCHARGE,
    LIQUID LINE, AND OIL LINE).
    WARNING
    Rotating Components!
    The following procedure involves working with rotating components. Disconnect all electric power,
    including remote disconnects before servicing. Follow
    proper lockout/tagout procedures to ensure the power
    can not be inadvertently energized. Failure to
    disconnect power before servicing could result in
    rotating components cutting and slashing technician
    which could result in death or serious injury. 
    						
    							Unit Startup
    162RT-SVX24K-EN
    3. UseTable37, p.11 2to program the following system
    components for the number 1 refrigeration circuit by
    scrolling
     through the displays;
    Supply Fan (On)
    VFD
     (100%, if applicable)
    OCC/UNOCC Relay (Unoccupied for VAV units)
    All Compressors for each circuit (On) Condenser Fans for each circuit (On)
    4. Once the configuration for the components is complete,
     press the NEXT key until the LCD displays
    the “Start test in __Sec.” screen. Press the + key to
    designate the delay before the test is to start. This
    service test will begin after the TEST START key is
    pressed and the delay designated in this step has
    elapsed. Press the ENTER key to confirm this choice.
    5. Press the TEST START key to start the test. Remember that the delay designated in step 4 must elapse before
    the system will begin to operate.
    6. After all of the compressors and condenser fans for the number
     1 circuit have been operating for
    approximately 30 minutes, observe the operating
    pressures. Use the appropriate pressure curve
    beginning with Figure84, p.136to determine the
    proper operating pressures. For superheat and
    subcooling
     guidelines, refer to “Thermostatic
    Expansion Valves and Charging by Subcooling” at the
    end of this section.
    Note: Do
    Not release refrigerant to the atmosphere! If
    adding or removing refrigerant is required, the
    service technician must comply with all Federal,
    State and local laws.
    7. Verify that the oil level in each compressor is correct. The
     oil level may be down to the bottom of the
    sightglass but should never be above the sightglass.
    8. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the system operation.
    9. Repeat steps 1 through 8 for the number 2 refrigeration circuit.
    10. After shutting the system off, check the compressor oil appearance.
     Discoloration of the oil indicates that an
    abnormal condition has occurred. If the oil is dark and
    smells burnt, it has overheated because: the compressor is operating at extremely high condensing
    temperatures; high superheat; a compressor
    mechanical failure; or, occurrence of a motor burnout.
    If the oil is black and contains metal flakes, a
    mechanical failure has occurred. This symptom is
    often accompanied by a high compressor amperage
    draw.
    If a motor burnout is suspected, use an acid test kit to
    check the condition of the oil. Test results will indicate
    an acid level exceeding 0.05 mg KOH/g if a burnout
    occurred.
    The scroll compressor uses Trane OIL00079 (one quart container) or OIL00080 (one gallon container) without
    substitution. The appropriate oil charge for CSHN250
    and CSHN315 scroll compressors is 14.2 pints. For
    CSHN374 scroll compressor, use 15.2 pints.
    Compressor Crankcase Heaters
    Each scroll compressor is equipped with a 160-watt
    crankcase heater.
    Compressor Operational Sounds
    Because of the scroll compressor design, it emits a higher
    frequency tone (sound) than a reciprocating compressor.
    It is designed to accommodate liquids, both oil and
    refrigerant, without causing compressor damage. The
    following discussion describes some of the operational
    sounds that differentiate it from those typically associated
    with a reciprocating compressor. These sounds do not
    affect the operation or reliability of the compressor.
    At Shutdown
    When a Scroll compressor shuts down, the gas within thescroll expands and causes momentary reverse rotation
    until the discharge check valve closes. This results in a
    “flutter” type sound.
    At Low Ambient Startup
    When the compressor starts up under low ambient conditions, the initial flow rate of the compressor is low
    due to the low condensing pressure. This causes a low
    differential across the thermal expansion valve that limits
    its capacity. Under these conditions, it is not unusual to
    hear the compressor rattle until the suction pressure
    climbs and the flow rate increases.
    Note: Evaporative Condensers ordered with sump
    heaters will have low ambient down to 10 deg as
    standard
    WARNING
    Rotating Components!
    The following procedure involves working with rotating components. Disconnect all electric power, including
    remote disconnects before servicing. Follow proper
    lockout/tagout procedures to ensure the power can not
    be inadvertently energized. Failure to disconnect power
    before servicing could result in rotating components
    cutting and slashing technician which could result in
    death or serious injury. 
    						
    							Unit Startup
    RT-SVX24K-EN163
    Evaporative Condenser Startup
    Important:Water treatment by a qualified water
    treatment expert is required to ensure
    proper equipment life and product
    performance. Dolphin Water Care™ is an
    option offered by Trane that is NOT a
    subsitute for regular water treatment by a
    qualified water treatment professional. If a
    water treatment system is not operating on
    the unit, do not proceed.
    Startup for evaporative and air-cooled condensers is
    initially the same. In addition, the following is required for
    evaporative condensers prior to startup:
     All water and drain connections must be checked and verified
     Evaporative condensers will ship with a fan support c
     hannel to reduce damage caused by vibration during
    shipment. The shipping support brackets must be
    removed prior to unit startup. See “To remove
    shipping brackets,” p. 163and Figure 113, p.164for
    removal instructions.
     Verify that inlet water pressure is 35-60 PSIG, dynamic pressure
     (measured with the valve open)
     Verify that drain valve is set to drain during power loss
     or hold during power loss per job specification
     Upon a call for cooling, the sump will fill with water. V
     erify that the sump fills to a level within the slot on the
    max float bracket as shown in Figure114, p.164.
    To remove shipping brackets
    Important: Remove fan shipping brackets before
    startup. Failure to remove brackets could
    result in fan damage.
    Evaporative condensers are shipped with fan shipping
    brackets to reduce damage caused by vibration during
    shipment. The fan shipping brackets must be removed
    prior to unit startup.
    To remove the shipping brackets start from the side opposite to the drain actuator:
    1. Loosen the screw for the bracket that holds the inlet louvers below the door side.
    2. Remove inlet louvers and set to the side.
    Note: S
    ervice technician may need to step on the
    horizontal surface of FRP coated base.
    Step with care.
    3. Unscrew the bolt in the middle of the door. Keep the bolt
     in a safe place.
    4. Lift one door with handle until it touches the top. S
     wivel bottom of door to remove it from the door
    opening and set it to the side.
    5. Slide and remove the middle mist eliminator section so
     that the shipping bracket is visible. 6. Use screw gun to unscrew the two screws that hold the
    fan
     shipping bracket. The bracket should drop down
    but still remain engaged with a hook on the bracket.
    7. Go to the other side of the unit and follow the procedure
     for inlet louver and door removal
    (see steps1-6
     ).
    8. Hold the bracket with one hand and remove remaining two
     screws.
    9. Remove the bracket and all the removed screws from the
     unit.
    Important: Mak
     e sure there are no screws remaining in
    the coil area.
    10. Reinstall inlet louvers, mist eliminators and louvers.
    11. Check that the direction of arrow on the inlet louver is cor
     rect 
    						
    							Unit Startup
    164RT-SVX24K-EN
    Figure 113. Fan shipping bracket removal
    Mist Eliminator
    Fan Shipping Bracket ScrewsFan Shipping Bracket
    Access Doors
    Inlet Louvers
    Actuator Side
    Figure 114. Float bracket setting
    Fill sump so float shuts 
    off when water is within these slots 
    						
    							Unit Startup
    RT-SVX24K-EN165
    Thermostatic Expansion Valves
    The reliability and performance of the refrigeration system
    is heavily dependent upon proper expansion valve
    adjustment.Therefore, the importance of maintaining the
    proper superheat cannot be over emphasized.
    On air-cooled units, the expansion valves shipped
    installed were factory set to control between 14-18°F at the
    ARI full load rating conditions (approximately 45°/125°F saturated suction/discharge). On evaporative condenser
    units, the expansion valves shipped installed were factory
    set to control between 18-22°F at the ARI full load rating
    conditions (approximately 45°/105°F saturated suction/
    discharge). At part load, expect lower superheat. Systems
    operating with lower superheat could cause serious
    compressor damage due to refrigerant floodback.
    Pressure curves, included in the IOM, are based on
    outdoor ambient between 65° & 105°F, relative humidity
    above 40 percent. Measuring the operating pressures can
    be meaningless outside of these ranges.
    Measuring Superheat
    1. Measure the suction pressure at the suction line gauge access port located near the compressor.
    2. Using a Refrigerant/Temperature chart, convert thepressure reading to a corresponding saturated vapor
    temperature.
    3. Measure the suction line temperature as close to the expansion
     valve bulb, as possible. Use a thermocouple
    type probe for an accurate reading.
    4. Subtract the saturated vapor temperature obtained in step
     2 from the actual suction line temperature
    obtained in step 3. The difference between the two
    temperatures is known as “superheat”.
    When adjusting superheat, recheck the system subcooling before
     shutting the system “Off”.
    Note: If unit includes the modulating reheat
    dehumidification option, adjust superheat only in
    the cooling mode of operation.
    Charging by Subcooling
    The outdoor ambient temperature must be between 65
    and 105°F and the relative humidity of the air entering the
    evaporator must be above 40 percent. When the
    temperatures are outside of these ranges, measuring the
    operating pressures can be meaningless. Make sure hot
    gas bypass (if applicable) is not flowing when taking
    performance measurements. With the unit operating at
    “Full Circuit Capacity”, acceptable subcooling ranges for air-cooled units is between 14°F to 22°F.
    For evaporative condenser units, acceptable subcooling
    range is between 8°F to 14°F.
    Measuring Subcooling
    1. At the liquid line service valve, measure the liquid line pressure. Using a Refrigerant R410A pressure/
    temperature chart, convert the pressure reading into
    the corresponding saturated temperature.
    2. Measure the actual liquid line temperature as close to the
     liquid line service valve as possible. To ensure an
    accurate reading, clean the line thoroughly where the
    temperature sensor will be attached. After securing the
    sensor to the line, insulate the sensor and line to isolate
    it from the ambient air. Use a thermocouple type probe
    for an accurate reading.
    Note: Glass
     thermometers do not have sufficient contact
    area to give an accurate reading.
    3. Determine the system subcooling by subtracting the actual
     liquid line temperature (measured in step 2)
    from the saturated liquid temperature (converted in
    step 1).
    Standard Ambient Units
    The following Table gives the minimum starting temperatures for Standard Ambient Units. Do not start the
    unit in the cooling mode if the ambient temperature is
    below the recommended operating temperatures.
    Figure 115. Compressor locations and staging sequence
    Table 46. Staging sequence
    Compressor Staging  (Lead) Compressor Staging 
    (Lag)
    1A 1B 2A 2B 1A 1B 2A 2B
    Stage 1
    XX
    Stage 2XXXX
    Stage 3X XXXXX
    Stage 4XXXXXXXX
    K4 
    						
    							Unit Startup
    166RT-SVX24K-EN
    Electric, Steam and Hot Water Startup
    (Constant Volume & Variable Air Volume
    Systems)
    1. Ensure that the “System” selection switch at the
    remote panel is in the “Off” position.
    2. Close the disconnect switch or circuit protector switchthat provides the supply power to the unit terminal
    block or the unit mounted disconnect switch.
    HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
    UNIT
     DISCONNECT SWITCH.
    3. Turn the 115 volt control circuit switch and the 24 volt control
     circuit switch to the “On” position.
    4. Open the Human Interface access door, located in the unit
     control panel, and press the SERVICE MODE key to
    display the first service screen. Refer to the latest
    edition of the appropriate programming manual for CV
    or VAV applications for the SERVICETEST screens and
    programming instructions.
    5. Use Table37, p.11 2to program the following system
    components for operation by scrolling through the
    Human
     Interface displays;
    Electric Heat
    Supply Fan (On)
    Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied)
    Heat Stages1&2(On)
    Steam or Hot Water Heat
    Supply Fan (On)
    Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied)
    Hydronic Heat Actuator (100% Open)
    Open the main steam or hot water valve supplying the
    rooftop heater coils.
    6. Once the configuration for the appropriate heating system
     is complete, press the NEXT key until the LCD
    displays the “Start test in __Sec.” screen. Press the +
    key to designate the delay before the test is to start.
    This service test will begin after theTEST START key is pressed and the delay designated in this step has
    elapsed. Press the ENTER key to confirm this choice.
    7. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before
    the fan will begin to operate.
    8. Once the system has started, verify that the electric heat
     or the hydronic heat system is operating properly
    by using appropriate service technics; i.e. amperage
    readings, delta tees, etc.
    9. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the system operation.
    Gas Furnace Startup
    (Constant Volume and Variable Air Volume
    Systems)
    It is important to establish and maintain the appropriate
    air/fuel mixture to assure that the gas furnace operates
    safely and efficiently.
    Since the proper manifold gas pressure for a particular
    installation will vary due to the specific BTU content of the
    local gas supply, adjust the burner based on carbon
    dioxide and oxygen levels.
    The volume of air supplied by the combustion blower determines the amount of oxygen available for
    combustion, while the manifold gas pressure establishes
    fuel input. By measuring the percentage of carbon dioxide
    produced as a by-product of combustion, the operator can
    estimate the amount of oxygen used and modify the air
    volume or the gas pressure to obtain the proper air/fuel
    ratio.
    Arriving at the correct air/fuel mixture for a furnace results in rated burner output, limited production of carbon
    Table 47. Minimum ambient
    Minimum Starting Ambient
    Unit Size Standard Ambient
    with HGBP without HGBP
    90-162 4055
    Notes:
     1. Minimum starting ambients in degrees F and is based on unit 
    operating at min. step of unloading, and unloading and 5 mph wind 
    across condenser
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Do not open the service access
    doors while the unit is operating. Failure to disconnect
    power before servicing could result in death or serious
    injury.
    WARNING
    Rotating Components!
    During installation, testing, servicing and
    troubleshooting of this product it may be necessary to
    work with live and exposed rotating components. Have
    a qualified or licensed service individual who has been
    properly trained in handling exposed rotating
    components, perform these tasks. Failure to follow all
    safety precautions could result in rotating components
    cutting and slashing technician which could result in
    death or serious injury. 
    						
    							Unit Startup
    RT-SVX24K-EN167
    monoxide, and a steady flame that minimizes nuisance
    shutdowns.
    Two Stage Gas Furnace
    High-Fire Adjustment
    1. UseTable 37, p. 112 to program the following system
    components for operation by scrolling through the
    Human Interface displays;
    Gas Heat
    Supply Fan (On)
    Return Fan (On, if supplied)
    Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied)
    Heat Stages1&2(On)
    Turn the 115 volt control circuit switch 4S24 located in the heater control panel to the “On” position.
    Open the manual gas valve, located in the gas heat
    section.
    2. Once the configuration for the appropriate heating system is complete, press the NEXT key until the LCD
    displays the “Start test in __Sec.” screen. Press the +
    key to designate the delay before the test is to start.
    This service test will begin after theTEST START key is pressed and the delay designated in this step has
    elapsed. Press the ENTER key to confirm this choice.
    3. Press the TEST START key to start the test. Remember that
     the delay designated in step 2 must elapse before
    the system will begin to operate. 4. Once the system has started, check the appearance of
    the
     flame through the sight glass provided on the front
    of the heat exchanger. In appearance, a normal flame
    has a clearly defined shape, and is primarily (75%) blue
    in color with an orange tip.
    5. Check the manifold gas pressure by using the manifold pressure
     port on the gas valve. Refer to Table48, p.168
    for the required manifold pressure for high-fire
    operation.
     If it needs adjusting, remove the cap
    covering the high-fire adjustment screw on the gas
    valve. Refer to Figure118, p.169for the adjustment
    screw location. Turn the screw clockwise to increase
    the
     gas pressure or counterclockwise to decrease the
    gas pressure.
    6. Use a carbon dioxide analyzer and measure the percentage
     of carbon dioxide in the flue gas. Refer to
    the illustration in Figure11 7, p .169. Take several
    samples to assure that an accurate reading is obtained.
    R
     efer to Figure116, p.168for the proper carbon
    dioxide levels. A carbon dioxide level exceeding the
    listed
     range indicates incomplete combustion due to
    inadequate air or excessive gas.
    Combustion Air Adjustment (O2)
    7. Use an oxygen analyzer and measure the percentage of oxygen in the flue gas. Take several samples to
    assure an accurate reading. Compare the measured
    oxygen level to the combustion curve in Figure11 6 ,
    p. 168 . The oxygen content of the flue gas should be
    4% to 5%. If the oxygen level is outside this range,
    adjust
     the combustion air damper to increase or
    decrease the amount of air entering the combustion
    chamber. Refer to Figure120, p. 171for the location of
    the combustion air damper.
    8. Recheck the oxygen and carbon dioxide levels after eac
     h adjustment. After completing the high-fire
    checkout and adjustment procedure, the low-fire
    setting may require adjusting.
    Low-Fire Adjustment
    (850 & 1100 MBH only)
    1. Use the TEST initiation procedures outlined in the previous section to operate the furnace in the low-fire
    state (1st Stage).
    2. Use a carbon dioxide analyzer and measure the percentage
     of carbon dioxide in the flue gas. Refer to
    the illustration in Figure116, p.168, Inset A. Take
    several samples to assure that an accurate reading is
    obtained.
     Refer toTable48, p. 168for the proper
    carbon dioxide levels. If the measured carbon dioxide
    level
     is within the listed values, no adjustment is
    necessary. A carbon dioxide level exceeding the listed
    range indicates incomplete combustion due to
    inadequate air or excessive gas.
    3. Check the manifold gas pressure by using the manifold pressure
     port on the gas valve. Refer to Table48, p.168
    WARNING
    Hazardous Gases and Flammable Vapors!
    Exposure to hazardous gases from fuel substances
    have been shown to cause cancer, birth defects or other
    reproductive harm. Improper installation, adjustment,
    alteration, service or use of this product could cause
    flammable mixtures and result in a fire. To avoid
    hazardous gases and flammable vapors follow proper
    installation and set up of this product and all warnings
    as provided in this manual. Failure to follow all
    instructions could result in death or serious injury.
    WARNING
    Hazardous Pressures!
    When using dry nitrogen cylinders for pressurizing units for leak testing, always provide a pressure
    regulator on the cylinder to prevent excessively high
    unit pressures. Never pressurize unit above the
    maximum recommended unit test pressure as specified
    in applicable unit literature. Failure to properly regulate
    pressure could result in a violent explosion, which
    could result in death or serious injury or equipment or
    property-only-damage. 
    						
    							Unit Startup
    168RT-SVX24K-EN
    for the required manifold pressure during low-fire
    operation. If it needs adjusting, remove the cap
    covering the low-fire adjustment screw on the gas
    valve. Refer toFigure118, p.169for the adjustment
    screw location. Turn the screw clockwise to increase
    the
     gas pressure or counterclockwise to decrease the
    gas pressure. Note:
    Do
    not adjust the combustion air damper while
    the furnace is operating at low-fire.
    4. Check the carbon dioxide levels after each adjustment.
    5. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the system operation.
    Figure 116. Natural gas combustion curve (ratio of oxygen to carbon dioxide in percent)
    0 1
    2 3 4
    5
    6 7 8
    9
    10
    11 12 13
    14
    15 16 17
    18
    012345 6789101112131415161718192021
    Percent Oxygen
    Percent Carbon Dioxide
    Curve       Fuel
       A     =    1,000 BTU per c u. ft.
                     of Natural Gas.
    A
    Table 48. Recommended manifold pressures and CO2levels during furnace operation
    2-STAGE MODULATING
    MBH FIRING 
    RATES % CO2
    NAT GAS MANIF 
    PRESS  “W.C. % CO2
    PROPANE MANIF 
    PRESS  “W.C. MBH FIRING 
    RATE  % CO2
    NAT GAS MANIF 
    PRESS “W.C. % CO2
    PROPANE MANIF 
    PRESS “W.C.
    850 100% 8.0-9.0 3.0-3.5 9.0-10.0 3.0-3.5 850 100% 8.0-9.0 3.0- 3.5 7.8-8.4 1.7-2.2
    510 60%  5.0 -7.0 0.8-0.95 5.0-7.0 1.5-3.0 85 10%  5.0 -7.0 0.8- 0.9.5 2.0-3.0 .1-.2
    1100 100% 8.0-9.0 3.0-3.3 9.0-10.0 3.0-3.3 1100 100% 7.0-9.0 .8-.9 8.5-9.5 .5-.75 550 50%  5.0 -7.0 0.8-0.95 5.0-7.0 0.8-0.95 55 5% 1.5-3.0 .05-1.0 1.5-2.5 .02-.04
    1800 100% 7.0- 8.0 1.5- 1.8 N/A N/A 1800 100% 7.0-9.0 1.5- 1.8 N/A N/A 900 50% 5.0- 7.0 0.5- 0.7 N/A N/A 90 5% 1.5-3.0 .05-1.0 N/A N/A
    2500 100% 7.5- 8.5 2.0- 2.5 N/A N/A 2500 100% 7.0-9.0 2.0- 2.5 N/A N/A
    1250 50% 5.0- 7.0 0.5-  0.7 N/A N/A 125 5% 1.5-3.0 .05-1.0 N/A N/A 
    						
    							Unit Startup
    RT-SVX24K-EN169
    Full Modulating Gas Furnace
    Full Modulating gas heaters are available for the 850, 1100,
    1800, 2500 MBH heater sizes.
    – The firing rate of the 850 MBH modulating heatercan vary from 10% to 100% of the 850 MBH.
    – The firing rate of the 1100, 1800 and 2500 MBH can vary from 5% to 100% of its nameplate value.
    Heat Exchanger
    The heat exchanger drum, tubes and front and rearheaders are constructed from stainless steel alloys.
    Unit Control
    The unit is controlled by a supply air temperature sensorlocated in the supply air stream for VAV units. CV units
    have two sensors, one located in the supply air stream and
    the zone sensor. The temperature sensor signal is sent to
    the Heat module of the IntelliPak™ II Unit Control. The
    control signal from the Heat Module signal is directly
    proportional 0-10 VDC. The higher the voltage signal, the
    lower the call for heat. The 0-10 VDC signal controls the air damper actuator
    which is mounted on the end of the air damper shaft. As
    the actuator rotates clockwise, more combustion air
    passes through the combustion air blower. In turn, the gas
    butterfly valve opens more through a directly connected
    linkage, resulting in a higher rate of firing.
    1. Use Table 37, p. 112 to program the following system
    components for operation by scrolling through the
    Human Interface displays;
    Gas Heat
    Supply Fan (On)
    Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied)
    High Fire (90%)
    Turn the 115 volt control circuit switch 4S24 located in the heater control panel to the “On” position.
    Open the manual gas valve, located in the gas heat
    section.
    2. Once the configuration for the appropriate heating system is complete, press the NEXT key until the LCD
    displays the “Start test in __Sec.” screen. Press the +
    key to designate the delay before the test is to start.
    This service test will begin after theTEST START key is pressed and the delay designated in this step has
    elapsed. Press the ENTER key to confirm this choice.
    3. Press the TEST START key to start the test. Remember that
     the delay designated in step 2 must elapse before
    the system will begin to operate.
    4. Once the system has started, check the appearance of the flame through the sight glass provided on the front
    of the heat exchanger. In appearance, a normal flame
    has a clearly defined shape, and is primarily (75%) blue
    in color with an orange tip.
    5. Check the inlet gas pressure at the modulating gas valve.
     The inlet pressure should be 6 to 8 w.c.
    6. Use a carbon dioxide analyzer and measure the percentage
     of carbon dioxide in the flue gas. Refer to
    the illustration in Figure11 7, p .169. Take several
    samples to assure that an accurate reading is obtained.
    The
     C0
    2level should fall in the ranges shown in the
    guide values Table48, p. 168
    Figure 117. Flue gas carbon dioxide and oxygen
    measurements
    Figure 118. High/low pressure regulator
    WARNING
    Rotating Components!
    During installation, testing, servicing and
    troubleshooting of this product it may be necessary to
    work with live and exposed rotating components. Have
    a qualified or licensed service individual who has been
    properly trained in handling exposed rotating
    components, perform these tasks. Failure to follow all
    safety precautions could result in rotating components
    cutting and slashing technician which could result in
    death or serious injury. 
    						
    							Unit Startup
    170RT-SVX24K-EN
    Note:The burner capacity is controlled by the movement
    of the air damper. This has been preset at the
    factory and normally does not need field
    adjustment. The combustion quality (air/gas) is
    controlled by the setup of the air damper and
    butterfly valve linkage relationship.
    7. Use Table37, p.11 2to program the minimum (5%)
    firing rate. Allow the system to operate for
    appro
     ximately 10 minutes.
    8. Use a carbon dioxide analyzer and measure the percentage
     of carbon dioxide in the flue gas. If the
    measured carbon dioxide level is in the ranges shown
    in the Guide Values Table48, p. 168, no adjustment is
    necessary. Note:
    It
    is normal for the low fire CO2to be lower than the
    high fire.
    9. If the measured carbon dioxide level is below the recommended
     values for low heat, return the burner to
    90% fire rate and repeat step 6, to achieve optimum
    combustion.
    10. Program the burner for 100% operation and recheck the
     CO
    2or O2value.
    11. Check the flue gas values at several intermediate output
     levels. If corrections are necessary;
    – Adjust butterfly linkage
    12. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the system operation.
    Figure 119. Modulating gas regulator 
    						
    All Trane manuals Comments (0)