Trane Intellipak 2 Service Manual
Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Unit Startup RT-SVX24K-EN161 8. Tighten the set screw to the drive shaft. 9. Stretch the belt over the pulley and engage it in the groo ve. Compressor Startup 1. Ensure that the “System” selection switch at theremote panel is in the “Off” position. 2. Before closing the disconnect switch, ensure that the compressor discharge service valve and the liquid line service valve for each circuit is back seated. 3. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal block or the unit mounted disconnect switch to allow the crankcase heater to operate a minimum of 8 hours before continuing. 4. Turn the 115 volt control circuit switch and the 24 volt control circuit switch to the “On” position. 5. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the applications programming guide for applications for the SERVICE TEST screens and programming instructions. 6. Use Table37, p.11 2to program the following system components for operation by scrolling through the displays; Compressors Compressor 1A (On) Compressor 1B (Off) Compressor 2A(Off) Compressor 2B (Off) Condenser Fans 1. Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. See Figure 115, p. 165 for the various compressor locations. 2. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 3. Press the TEST START key to start the test. Remember that the delay designated in step 8 must elapse before the system will begin to operate. 4. Once each compressor or compressor pair has started, verify that the rotation is correct. If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed. Check the electrical phasing at the load side of the compressor contactor. If the phasing is correct, before condemning the compressor, interchange any two leads to check the internal motor phasing. If the compressor runs backward for an extended period (15 to 30 minutes), the motor winding can over heat and cause the motor winding thermostats to open. This will cause a “compressor trip” diagnostic and stop the compressor. 5. Press the STOP key at the Human Interface Module in the unit control panel to stop the compressor operation. 6. Repeat steps 5 through 11 for each compressor stage and the appropriate condenser fans. Refrigerant Charging 1. Attach a set of service gauges onto the suction anddischarge gauge ports for each circuit. See Figure 115, p. 165 for the various compressor locations. 2. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the applications programming guide for CV or VAV applications for the SERVICETEST screens and programming instructions. NOTICE: Compressors Failure! Unit must be powered and crankcase heaters energized at least 8 hours BEFORE compressors are started. This will protect the compressors from premature failure. CAUTION Compressor Damage! Do not allow liquid refrigerant to enter the suction line. Excessive liquid accumulation in the liquid lines could result in compressor damage. COMPRESSOR SERVICE VALVES MUST BE FULLY OPENED BEFORE STARTUP (SUCTION, DISCHARGE, LIQUID LINE, AND OIL LINE). WARNING Rotating Components! The following procedure involves working with rotating components. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury.
Unit Startup 162RT-SVX24K-EN 3. UseTable37, p.11 2to program the following system components for the number 1 refrigeration circuit by scrolling through the displays; Supply Fan (On) VFD (100%, if applicable) OCC/UNOCC Relay (Unoccupied for VAV units) All Compressors for each circuit (On) Condenser Fans for each circuit (On) 4. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 5. Press the TEST START key to start the test. Remember that the delay designated in step 4 must elapse before the system will begin to operate. 6. After all of the compressors and condenser fans for the number 1 circuit have been operating for approximately 30 minutes, observe the operating pressures. Use the appropriate pressure curve beginning with Figure84, p.136to determine the proper operating pressures. For superheat and subcooling guidelines, refer to “Thermostatic Expansion Valves and Charging by Subcooling” at the end of this section. Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all Federal, State and local laws. 7. Verify that the oil level in each compressor is correct. The oil level may be down to the bottom of the sightglass but should never be above the sightglass. 8. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation. 9. Repeat steps 1 through 8 for the number 2 refrigeration circuit. 10. After shutting the system off, check the compressor oil appearance. Discoloration of the oil indicates that an abnormal condition has occurred. If the oil is dark and smells burnt, it has overheated because: the compressor is operating at extremely high condensing temperatures; high superheat; a compressor mechanical failure; or, occurrence of a motor burnout. If the oil is black and contains metal flakes, a mechanical failure has occurred. This symptom is often accompanied by a high compressor amperage draw. If a motor burnout is suspected, use an acid test kit to check the condition of the oil. Test results will indicate an acid level exceeding 0.05 mg KOH/g if a burnout occurred. The scroll compressor uses Trane OIL00079 (one quart container) or OIL00080 (one gallon container) without substitution. The appropriate oil charge for CSHN250 and CSHN315 scroll compressors is 14.2 pints. For CSHN374 scroll compressor, use 15.2 pints. Compressor Crankcase Heaters Each scroll compressor is equipped with a 160-watt crankcase heater. Compressor Operational Sounds Because of the scroll compressor design, it emits a higher frequency tone (sound) than a reciprocating compressor. It is designed to accommodate liquids, both oil and refrigerant, without causing compressor damage. The following discussion describes some of the operational sounds that differentiate it from those typically associated with a reciprocating compressor. These sounds do not affect the operation or reliability of the compressor. At Shutdown When a Scroll compressor shuts down, the gas within thescroll expands and causes momentary reverse rotation until the discharge check valve closes. This results in a “flutter” type sound. At Low Ambient Startup When the compressor starts up under low ambient conditions, the initial flow rate of the compressor is low due to the low condensing pressure. This causes a low differential across the thermal expansion valve that limits its capacity. Under these conditions, it is not unusual to hear the compressor rattle until the suction pressure climbs and the flow rate increases. Note: Evaporative Condensers ordered with sump heaters will have low ambient down to 10 deg as standard WARNING Rotating Components! The following procedure involves working with rotating components. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury.
Unit Startup RT-SVX24K-EN163 Evaporative Condenser Startup Important:Water treatment by a qualified water treatment expert is required to ensure proper equipment life and product performance. Dolphin Water Care™ is an option offered by Trane that is NOT a subsitute for regular water treatment by a qualified water treatment professional. If a water treatment system is not operating on the unit, do not proceed. Startup for evaporative and air-cooled condensers is initially the same. In addition, the following is required for evaporative condensers prior to startup: All water and drain connections must be checked and verified Evaporative condensers will ship with a fan support c hannel to reduce damage caused by vibration during shipment. The shipping support brackets must be removed prior to unit startup. See “To remove shipping brackets,” p. 163and Figure 113, p.164for removal instructions. Verify that inlet water pressure is 35-60 PSIG, dynamic pressure (measured with the valve open) Verify that drain valve is set to drain during power loss or hold during power loss per job specification Upon a call for cooling, the sump will fill with water. V erify that the sump fills to a level within the slot on the max float bracket as shown in Figure114, p.164. To remove shipping brackets Important: Remove fan shipping brackets before startup. Failure to remove brackets could result in fan damage. Evaporative condensers are shipped with fan shipping brackets to reduce damage caused by vibration during shipment. The fan shipping brackets must be removed prior to unit startup. To remove the shipping brackets start from the side opposite to the drain actuator: 1. Loosen the screw for the bracket that holds the inlet louvers below the door side. 2. Remove inlet louvers and set to the side. Note: S ervice technician may need to step on the horizontal surface of FRP coated base. Step with care. 3. Unscrew the bolt in the middle of the door. Keep the bolt in a safe place. 4. Lift one door with handle until it touches the top. S wivel bottom of door to remove it from the door opening and set it to the side. 5. Slide and remove the middle mist eliminator section so that the shipping bracket is visible. 6. Use screw gun to unscrew the two screws that hold the fan shipping bracket. The bracket should drop down but still remain engaged with a hook on the bracket. 7. Go to the other side of the unit and follow the procedure for inlet louver and door removal (see steps1-6 ). 8. Hold the bracket with one hand and remove remaining two screws. 9. Remove the bracket and all the removed screws from the unit. Important: Mak e sure there are no screws remaining in the coil area. 10. Reinstall inlet louvers, mist eliminators and louvers. 11. Check that the direction of arrow on the inlet louver is cor rect
Unit Startup 164RT-SVX24K-EN Figure 113. Fan shipping bracket removal Mist Eliminator Fan Shipping Bracket ScrewsFan Shipping Bracket Access Doors Inlet Louvers Actuator Side Figure 114. Float bracket setting Fill sump so float shuts off when water is within these slots
Unit Startup RT-SVX24K-EN165 Thermostatic Expansion Valves The reliability and performance of the refrigeration system is heavily dependent upon proper expansion valve adjustment.Therefore, the importance of maintaining the proper superheat cannot be over emphasized. On air-cooled units, the expansion valves shipped installed were factory set to control between 14-18°F at the ARI full load rating conditions (approximately 45°/125°F saturated suction/discharge). On evaporative condenser units, the expansion valves shipped installed were factory set to control between 18-22°F at the ARI full load rating conditions (approximately 45°/105°F saturated suction/ discharge). At part load, expect lower superheat. Systems operating with lower superheat could cause serious compressor damage due to refrigerant floodback. Pressure curves, included in the IOM, are based on outdoor ambient between 65° & 105°F, relative humidity above 40 percent. Measuring the operating pressures can be meaningless outside of these ranges. Measuring Superheat 1. Measure the suction pressure at the suction line gauge access port located near the compressor. 2. Using a Refrigerant/Temperature chart, convert thepressure reading to a corresponding saturated vapor temperature. 3. Measure the suction line temperature as close to the expansion valve bulb, as possible. Use a thermocouple type probe for an accurate reading. 4. Subtract the saturated vapor temperature obtained in step 2 from the actual suction line temperature obtained in step 3. The difference between the two temperatures is known as “superheat”. When adjusting superheat, recheck the system subcooling before shutting the system “Off”. Note: If unit includes the modulating reheat dehumidification option, adjust superheat only in the cooling mode of operation. Charging by Subcooling The outdoor ambient temperature must be between 65 and 105°F and the relative humidity of the air entering the evaporator must be above 40 percent. When the temperatures are outside of these ranges, measuring the operating pressures can be meaningless. Make sure hot gas bypass (if applicable) is not flowing when taking performance measurements. With the unit operating at “Full Circuit Capacity”, acceptable subcooling ranges for air-cooled units is between 14°F to 22°F. For evaporative condenser units, acceptable subcooling range is between 8°F to 14°F. Measuring Subcooling 1. At the liquid line service valve, measure the liquid line pressure. Using a Refrigerant R410A pressure/ temperature chart, convert the pressure reading into the corresponding saturated temperature. 2. Measure the actual liquid line temperature as close to the liquid line service valve as possible. To ensure an accurate reading, clean the line thoroughly where the temperature sensor will be attached. After securing the sensor to the line, insulate the sensor and line to isolate it from the ambient air. Use a thermocouple type probe for an accurate reading. Note: Glass thermometers do not have sufficient contact area to give an accurate reading. 3. Determine the system subcooling by subtracting the actual liquid line temperature (measured in step 2) from the saturated liquid temperature (converted in step 1). Standard Ambient Units The following Table gives the minimum starting temperatures for Standard Ambient Units. Do not start the unit in the cooling mode if the ambient temperature is below the recommended operating temperatures. Figure 115. Compressor locations and staging sequence Table 46. Staging sequence Compressor Staging (Lead) Compressor Staging (Lag) 1A 1B 2A 2B 1A 1B 2A 2B Stage 1 XX Stage 2XXXX Stage 3X XXXXX Stage 4XXXXXXXX K4
Unit Startup 166RT-SVX24K-EN Electric, Steam and Hot Water Startup (Constant Volume & Variable Air Volume Systems) 1. Ensure that the “System” selection switch at the remote panel is in the “Off” position. 2. Close the disconnect switch or circuit protector switchthat provides the supply power to the unit terminal block or the unit mounted disconnect switch. HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. 3. Turn the 115 volt control circuit switch and the 24 volt control circuit switch to the “On” position. 4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for CV or VAV applications for the SERVICETEST screens and programming instructions. 5. Use Table37, p.11 2to program the following system components for operation by scrolling through the Human Interface displays; Electric Heat Supply Fan (On) Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied) Heat Stages1&2(On) Steam or Hot Water Heat Supply Fan (On) Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied) Hydronic Heat Actuator (100% Open) Open the main steam or hot water valve supplying the rooftop heater coils. 6. Once the configuration for the appropriate heating system is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after theTEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 7. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fan will begin to operate. 8. Once the system has started, verify that the electric heat or the hydronic heat system is operating properly by using appropriate service technics; i.e. amperage readings, delta tees, etc. 9. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation. Gas Furnace Startup (Constant Volume and Variable Air Volume Systems) It is important to establish and maintain the appropriate air/fuel mixture to assure that the gas furnace operates safely and efficiently. Since the proper manifold gas pressure for a particular installation will vary due to the specific BTU content of the local gas supply, adjust the burner based on carbon dioxide and oxygen levels. The volume of air supplied by the combustion blower determines the amount of oxygen available for combustion, while the manifold gas pressure establishes fuel input. By measuring the percentage of carbon dioxide produced as a by-product of combustion, the operator can estimate the amount of oxygen used and modify the air volume or the gas pressure to obtain the proper air/fuel ratio. Arriving at the correct air/fuel mixture for a furnace results in rated burner output, limited production of carbon Table 47. Minimum ambient Minimum Starting Ambient Unit Size Standard Ambient with HGBP without HGBP 90-162 4055 Notes: 1. Minimum starting ambients in degrees F and is based on unit operating at min. step of unloading, and unloading and 5 mph wind across condenser WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Do not open the service access doors while the unit is operating. Failure to disconnect power before servicing could result in death or serious injury. WARNING Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury.
Unit Startup RT-SVX24K-EN167 monoxide, and a steady flame that minimizes nuisance shutdowns. Two Stage Gas Furnace High-Fire Adjustment 1. UseTable 37, p. 112 to program the following system components for operation by scrolling through the Human Interface displays; Gas Heat Supply Fan (On) Return Fan (On, if supplied) Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied) Heat Stages1&2(On) Turn the 115 volt control circuit switch 4S24 located in the heater control panel to the “On” position. Open the manual gas valve, located in the gas heat section. 2. Once the configuration for the appropriate heating system is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after theTEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 3. Press the TEST START key to start the test. Remember that the delay designated in step 2 must elapse before the system will begin to operate. 4. Once the system has started, check the appearance of the flame through the sight glass provided on the front of the heat exchanger. In appearance, a normal flame has a clearly defined shape, and is primarily (75%) blue in color with an orange tip. 5. Check the manifold gas pressure by using the manifold pressure port on the gas valve. Refer to Table48, p.168 for the required manifold pressure for high-fire operation. If it needs adjusting, remove the cap covering the high-fire adjustment screw on the gas valve. Refer to Figure118, p.169for the adjustment screw location. Turn the screw clockwise to increase the gas pressure or counterclockwise to decrease the gas pressure. 6. Use a carbon dioxide analyzer and measure the percentage of carbon dioxide in the flue gas. Refer to the illustration in Figure11 7, p .169. Take several samples to assure that an accurate reading is obtained. R efer to Figure116, p.168for the proper carbon dioxide levels. A carbon dioxide level exceeding the listed range indicates incomplete combustion due to inadequate air or excessive gas. Combustion Air Adjustment (O2) 7. Use an oxygen analyzer and measure the percentage of oxygen in the flue gas. Take several samples to assure an accurate reading. Compare the measured oxygen level to the combustion curve in Figure11 6 , p. 168 . The oxygen content of the flue gas should be 4% to 5%. If the oxygen level is outside this range, adjust the combustion air damper to increase or decrease the amount of air entering the combustion chamber. Refer to Figure120, p. 171for the location of the combustion air damper. 8. Recheck the oxygen and carbon dioxide levels after eac h adjustment. After completing the high-fire checkout and adjustment procedure, the low-fire setting may require adjusting. Low-Fire Adjustment (850 & 1100 MBH only) 1. Use the TEST initiation procedures outlined in the previous section to operate the furnace in the low-fire state (1st Stage). 2. Use a carbon dioxide analyzer and measure the percentage of carbon dioxide in the flue gas. Refer to the illustration in Figure116, p.168, Inset A. Take several samples to assure that an accurate reading is obtained. Refer toTable48, p. 168for the proper carbon dioxide levels. If the measured carbon dioxide level is within the listed values, no adjustment is necessary. A carbon dioxide level exceeding the listed range indicates incomplete combustion due to inadequate air or excessive gas. 3. Check the manifold gas pressure by using the manifold pressure port on the gas valve. Refer to Table48, p.168 WARNING Hazardous Gases and Flammable Vapors! Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures and result in a fire. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual. Failure to follow all instructions could result in death or serious injury. WARNING Hazardous Pressures! When using dry nitrogen cylinders for pressurizing units for leak testing, always provide a pressure regulator on the cylinder to prevent excessively high unit pressures. Never pressurize unit above the maximum recommended unit test pressure as specified in applicable unit literature. Failure to properly regulate pressure could result in a violent explosion, which could result in death or serious injury or equipment or property-only-damage.
Unit Startup 168RT-SVX24K-EN for the required manifold pressure during low-fire operation. If it needs adjusting, remove the cap covering the low-fire adjustment screw on the gas valve. Refer toFigure118, p.169for the adjustment screw location. Turn the screw clockwise to increase the gas pressure or counterclockwise to decrease the gas pressure. Note: Do not adjust the combustion air damper while the furnace is operating at low-fire. 4. Check the carbon dioxide levels after each adjustment. 5. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation. Figure 116. Natural gas combustion curve (ratio of oxygen to carbon dioxide in percent) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 012345 6789101112131415161718192021 Percent Oxygen Percent Carbon Dioxide Curve Fuel A = 1,000 BTU per c u. ft. of Natural Gas. A Table 48. Recommended manifold pressures and CO2levels during furnace operation 2-STAGE MODULATING MBH FIRING RATES % CO2 NAT GAS MANIF PRESS “W.C. % CO2 PROPANE MANIF PRESS “W.C. MBH FIRING RATE % CO2 NAT GAS MANIF PRESS “W.C. % CO2 PROPANE MANIF PRESS “W.C. 850 100% 8.0-9.0 3.0-3.5 9.0-10.0 3.0-3.5 850 100% 8.0-9.0 3.0- 3.5 7.8-8.4 1.7-2.2 510 60% 5.0 -7.0 0.8-0.95 5.0-7.0 1.5-3.0 85 10% 5.0 -7.0 0.8- 0.9.5 2.0-3.0 .1-.2 1100 100% 8.0-9.0 3.0-3.3 9.0-10.0 3.0-3.3 1100 100% 7.0-9.0 .8-.9 8.5-9.5 .5-.75 550 50% 5.0 -7.0 0.8-0.95 5.0-7.0 0.8-0.95 55 5% 1.5-3.0 .05-1.0 1.5-2.5 .02-.04 1800 100% 7.0- 8.0 1.5- 1.8 N/A N/A 1800 100% 7.0-9.0 1.5- 1.8 N/A N/A 900 50% 5.0- 7.0 0.5- 0.7 N/A N/A 90 5% 1.5-3.0 .05-1.0 N/A N/A 2500 100% 7.5- 8.5 2.0- 2.5 N/A N/A 2500 100% 7.0-9.0 2.0- 2.5 N/A N/A 1250 50% 5.0- 7.0 0.5- 0.7 N/A N/A 125 5% 1.5-3.0 .05-1.0 N/A N/A
Unit Startup RT-SVX24K-EN169 Full Modulating Gas Furnace Full Modulating gas heaters are available for the 850, 1100, 1800, 2500 MBH heater sizes. – The firing rate of the 850 MBH modulating heatercan vary from 10% to 100% of the 850 MBH. – The firing rate of the 1100, 1800 and 2500 MBH can vary from 5% to 100% of its nameplate value. Heat Exchanger The heat exchanger drum, tubes and front and rearheaders are constructed from stainless steel alloys. Unit Control The unit is controlled by a supply air temperature sensorlocated in the supply air stream for VAV units. CV units have two sensors, one located in the supply air stream and the zone sensor. The temperature sensor signal is sent to the Heat module of the IntelliPak™ II Unit Control. The control signal from the Heat Module signal is directly proportional 0-10 VDC. The higher the voltage signal, the lower the call for heat. The 0-10 VDC signal controls the air damper actuator which is mounted on the end of the air damper shaft. As the actuator rotates clockwise, more combustion air passes through the combustion air blower. In turn, the gas butterfly valve opens more through a directly connected linkage, resulting in a higher rate of firing. 1. Use Table 37, p. 112 to program the following system components for operation by scrolling through the Human Interface displays; Gas Heat Supply Fan (On) Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied) High Fire (90%) Turn the 115 volt control circuit switch 4S24 located in the heater control panel to the “On” position. Open the manual gas valve, located in the gas heat section. 2. Once the configuration for the appropriate heating system is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after theTEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 3. Press the TEST START key to start the test. Remember that the delay designated in step 2 must elapse before the system will begin to operate. 4. Once the system has started, check the appearance of the flame through the sight glass provided on the front of the heat exchanger. In appearance, a normal flame has a clearly defined shape, and is primarily (75%) blue in color with an orange tip. 5. Check the inlet gas pressure at the modulating gas valve. The inlet pressure should be 6 to 8 w.c. 6. Use a carbon dioxide analyzer and measure the percentage of carbon dioxide in the flue gas. Refer to the illustration in Figure11 7, p .169. Take several samples to assure that an accurate reading is obtained. The C0 2level should fall in the ranges shown in the guide values Table48, p. 168 Figure 117. Flue gas carbon dioxide and oxygen measurements Figure 118. High/low pressure regulator WARNING Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury.
Unit Startup 170RT-SVX24K-EN Note:The burner capacity is controlled by the movement of the air damper. This has been preset at the factory and normally does not need field adjustment. The combustion quality (air/gas) is controlled by the setup of the air damper and butterfly valve linkage relationship. 7. Use Table37, p.11 2to program the minimum (5%) firing rate. Allow the system to operate for appro ximately 10 minutes. 8. Use a carbon dioxide analyzer and measure the percentage of carbon dioxide in the flue gas. If the measured carbon dioxide level is in the ranges shown in the Guide Values Table48, p. 168, no adjustment is necessary. Note: It is normal for the low fire CO2to be lower than the high fire. 9. If the measured carbon dioxide level is below the recommended values for low heat, return the burner to 90% fire rate and repeat step 6, to achieve optimum combustion. 10. Program the burner for 100% operation and recheck the CO 2or O2value. 11. Check the flue gas values at several intermediate output levels. If corrections are necessary; – Adjust butterfly linkage 12. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation. Figure 119. Modulating gas regulator