Trane Intellipak 2 Service Manual
Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Unit Startup RT-SVX24K-EN111 internally connected for clockwise rotation with the incoming power supply phased as A, B, C. Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following the steps below: [ ] Turn the field supplied disconnect switch that provides power to terminal block or to the unit mounted disconnect switch to the “Off” position. [ ] Connect the phase sequence indicator leads to the terminal block or unit mounted disconnect switch as follows: [ ] Close the disconnect switch or circuit protector switc h that provides the supply power to the unit terminal block or the unit mounted disconnect switch. HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. [ ] Observe the ABC and CBA phase indicator lights on the face of the sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA indicator light glows, open the disconnect switch or circuit protection switch and reverse any two power wires. [ ] Restore the main electrical power and recheck the phasing. If the phasing is correct, open the disconnect switch or circuit protection switch and remove the phase sequence indicator. Voltage Supply and Voltage Imbalance Voltage Supply Electrical power to the unit must meet stringent requirements for the unit to operate properly. Measure each leg (phase-to-phase) of the power supply. Each reading must fall within the utilization range stamped on the unit nameplate. If any of the readings do not fall within the proper tolerances, notify the power company to correct this situation before operating the unit. Voltage Imbalance Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows: % Voltage Imbalance = where; AV (Average Voltage) = V1, V2, V3 = Line Voltage Readings VD = Line Voltage reading that deviates the farthest from the average voltage. Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be: VD (reading farthest from average) = 221 The percentage of Imbalance equals: The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2%, notify the proper agencies to correct the voltage problem before operating this equipment.Phase Sequence Leads Unit Power Terminal Black (phase A) L1 Red (phase B) L2 Yellow (phase C) L3 WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 100xAV VD – AV ---------------- - Vo lt1 Volt2 Volt3 ++ 3 ------------------------------------------------- 211 230 227 ++ 3 ----------------------------------- - 226 A v g= 100 x226 221 – 226 -------------------- - 2.2 pe r c e n t=
Unit Startup 11 2RT-SVX24K-EN Table 37. Service test guide for component operation — part I of II Component Being Tested COMPONENT CONFIGURATION Supply Fan Return Fan Exhaust Fan Condenser Fans Heat Stages Compressor Stage 1231234 COMPRESSOR 90 - 105 Ton 1A OFF OFF OFF ALL OFF OFF OFF OFF ON OFF OFF OFF 1B OFF OFF OFF ALL OFF OFF OFF OFF ON ON OFF OFF 2A OFF OFF OFF ALL OFF OFF OFF OFF OFF OFF ON OFF 2B OFF OFF OFF ALL OFF OFF OFF OFF OFF OFF ON ON120 - 162 Ton 1A OFF OFF OFF 1A-On /1B-Off/1C-Off/1D-Off 2A-Off/2B-Off/2C-Off/2D-Off OFF OFF OFF ON OFF OFF OFF 1B OFF OFF OFF ALL OFF OFF OFF OFF ON ON OFF OFF 2A OFF OFF OFF 1A-Off/1B-Off/1C-Off/1D-Off 2A-On/2B-Off/2C-Off/2D-Off OFF OFF OFF OFF OFF ON OFF 2B OFF OFF OFF ALL OFF OFF OFF OFF OFF OFF ON ON CONDENSER FANS 90 - 105 Ton — Air Cooled 1A OFF OFF OFF 1A-On /1B-Off/1C-Off 2A-Off/2B-Off/2C-Off OFF OFF OFF OFF OFF OFF OFF 1B & 1C OFF OFF OFF 1A-Off/1B-On /1C-On 2A-Off/2B-Off/2C-Off OFF OFF OFF OFF OFF OFF OFF 2A OFF OFF OFF 1A-Off/1B-Off/1C-Off \ 2A-On /2B-Off/2C-Off OFF OFF OFF OFF OFF OFF OFF 2B & 2C OFF OFF OFF 1A-On/1B-Off/1C-Off \ 2A-Off /2B-On /2C-On OFF OFF OFF OFF OFF OFF OFF120 - 150 Ton — Air Cooled 1A OFF OFF OFF 1A-On /1B-Off/1C-Off/1D-Off 2A-Off/2B-Off/2C-Off/2D-Off OFF OFF OFF OFF OFF OFF OFF 1B OFF OFF OFF 1A-Off/1B-On/1C-Off/ 1D-Off 2A-Off/2B-Off/2C-Off/ 2D-Off OFF OFF OFF OFF OFF OFF OFF 1C & 1D OFF OFF OFF 1A-Off/1B-On/1C-On/ 1D-On 2A-Off/2B-Off/2C-Off/ 2D-Off OFF OFF OFF OFF OFF OFF OFF 2A OFF OFF OFF 1A-Off/1B-Off/1C-Off/ 1D-Off 2A-On /2B-Off/2C-Off & 2D-Off OFF OFF OFF OFF OFF OFF OFF 2B & 2C OFF OFF OFF 1A-Off/1B-On/1C-Off/ 1D-Off 2A-Off/2B-On/2C-On/ 2D-Off OFF OFF OFF OFF OFF OFF OFF 2D OFF OFF OFF 1A-Off/1B-On/1C-Off 1D-Off 2A-Off/2B-Off/2C-Off/ 2D-On OFF OFF OFF OFF OFF OFF OFF 100, 118, 128, 140, 162 Ton — Evaporative Condensing 1A OFF OFF OFF 1A 0 -100 % 2A OFF OFF OFF OFF OFF OFF OFF OFF 2A OFF OFF OFF 1A OFF 2A 0 - 100% OFF OFF OFF OFF OFF OFF OFF
Unit Startup RT-SVX24K-EN11 3 SUPPLY FAN ON ON OFF ALL OFF OFF OFF OFF OFF OFF OFF OFF RETURN FAN ON ON N/A ALL OFF OFF OFF OFF OFF OFF OFF OFF EXHAUST FAN OFF N/A ON ALL OFF OFF OFF OFF OFF OFF OFF OFF GAS HEAT (Full Capacity) ON ON OFF ALL OFF ON ON ON OFF OFF OFF OFF STAGE 1 ON ON OFF ALL OFF ON OFF ON OFF OFF OFF OFF STAGE 2 ON ON OFF ALL OFF OFF ON N/A OFF OFF OFF OFF Full Modulating ON ON OFF ALL OFF 10% - 90% OFF OFF OFF OFF ELECTRIC HEAT ON ON OFF ALL OFF ON ON ON OFF OFF OFF OFF Stage 1 ON ON OFF ALL OFF ON OFF OFF OFF OFF OFF OFF Stage 2 ON ON OFF ALL OFF OFF ON OFF OFF OFF OFF OFF Stage 3 ON ON OFF ALL OFF OFF OFF ON OFF OFF OFF OFF HYDRONIC HEAT OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF OUTSIDE AIR DAMPERS OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF EXHAUST DAMPERS OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF EVAP COND Sump Pump OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF Sump Heater OFF OFF OFF ALL OFF 100% Select OFF OFF OFF OFF Table 37. Service test guide for component operation — part I of II (continued) Component Being Tested COMPONENT CONFIGURATION Supply Fan Return Fan Exhaust Fan Condenser Fans Heat Stages Compressor Stage 1231234
Unit Startup 11 4RT-SVX24K-EN Table 38. Service test guide for component operation — part II of II Component Being Tested Component Configuration Occ Unocc Relay Sump Pump Sump Heater Econo Damper Exhaust Damper VFD Output COMPRESSOR 90 - 105 Ton 1A Closed Closed 0%Default OFFOFF 1B Closed Closed 0%Default OFFOFF 2A Closed Closed 0%Default OFFOFF 2B Closed Closed 0%Default OFFOFF 120 - 162 Ton 1A Closed Closed 0%Default OFFOFF 1B Closed Closed 0%Default OFFOFF 2A Closed Closed 0%Default OFFOFF 2B Closed Closed 0%Default OFFOFF CONDENSER FANS 90 - 105 Ton — Air Cooled 1A Closed Closed 0%Default OFFOFF 1B & 1C ClosedClosed 0%Default OFFOFF 2A Closed Closed 0%Default OFFOFF 2B & 2C ClosedClosed 0%Default OFFOFF 120 - 150 Ton — Air Cooled 1A Closed Closed 0%Default OFFOFF 1B Closed Closed 0%Default OFFOFF 1C & 1D ClosedClosed 0%Default OFFOFF 2A Closed Closed 0%Default OFFOFF 2B & 2C ClosedClosed 0%Default OFFOFF 2D Closed Closed 0%Default OFFOFF 100, 118, 128, 140, 162 Ton — Evaporative Cooled 1A Closed Closed 0%Default OFFOFF 2A Closed Closed 0%Default OFFOFF SUPPLY FAN ClosedClosed 100%Unocc OFFOFF RETURN FAN ClosedClosed 100%Default OFFOFF EXHAUST FAN ClosedClosed 100%Default OFFOFF GAS HEAT (Full Capacity) Closed Closed 100%Unocc OFFOFF Stage 1 ClosedClosed 100%Unocc OFFOFF Stage 2 ClosedClosed 100%Unocc OFFOFF Full Modulating ClosedClosed 100%Unocc OFFOFF ELECTRIC HEAT ClosedClosed 100%Unocc OFFOFF Stage 1 ClosedClosed 100%Unocc OFFOFF Stage 2 ClosedClosed 100%Unocc OFFOFF Stage 3 ClosedClosed 100%Unocc OFFOFF HYDRONIC HEAT ClosedClosed 100%Default OFFOFF OUTSIDE AIR DAMPERS Closed Closed 100%Default OFFOFF EXHAUST DAMPERS ClosedClosed 100%Default OFFOFF EVAP COND Sump Pump ClosedClosed 100%Default ONOFF Sump Heater ClosedClosed 100%Default OFFON
Unit Startup RT-SVX24K-EN11 5 Service Testing—Evaporative Condenser Components From the Compressor and Condenser Service Menu screens—Head Pressure Control: AUTO or Head Pressure Control: MANUAL 1. Select: Head Pressure Control: MANUAL Note: All outputs, Sump Control, Fan Stage Control and Fan speed Control (per circuit where specified), will be available for ON/OFF, OPEN/CLOSED, 0-100% manual settings considering the stipulations in Table 39 : Notes: 1. Sump Freeze Protection is active during AUTO but is inactive in service test modes (Head Pressure Control set to MANUAL). 2. Water Treatment Drain Request will be ignored in Service Test. Verifying Proper Fan Rotation Note: Fans controlled by VFD will run in the correct direction even if phasing is incorrect. 1. Ensure that the “System” selection switch at the remote panel is in the “Off” position and the “Fan” selection switch for constant volume units is in the “Auto” position. (VAV and SZVAV units do not utilize a “Fan” selection input.) 2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal block 1TB1 or the unit mounted disconnect switch 1S14. 3. Turn the 115 volt control circuit switch 1S2 and the 24 v olt control circuit switch 1S3 to the “On” position. 4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for applications for the SERVICE TEST screens and programming instructions. 5. Use Table37, p.11 2to program the unit Fans for operation by scrolling through the displays. All of the F ans (Supply, Exhaust, and Condenser fans) can be programmed to be “On”, if desired. Refer to Figure69, p.11 6for the condenser fan locations and the Human Interface designator. 6. Once the configuration for the Fans is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after theTEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 7. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fans will begin to operate. 8. Check the supply fan and the exhaust fans (if equipped) for proper rotation. The direction of rotation is indicated by an arrow on the fan housings. Check the condenser fans for clockwise rotation when viewed from the top. Table 39. Service test guide component operation— ev aporative condenser COMPONENT BEING TESTED Requirements (ON) Requirements (OFF) Compressors Sump minimum level switch must be closed for a minimum of five minutes No Requirements Sump Pump Sump minimum level switch must be closed for a minimum of five minutes No Requirements Condenser Fans No Requirements No Requirements Fill Valve Solenoid No Requirements No Requirements Drain Valve Actuator No Requirements No Requirements Sump Heater No Requirements No Requirements WARNING Rotating Components! During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury.
Unit Startup 11 6RT-SVX24K-EN If all of the fans are rotating backwards; a. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. b. Open the field supplied disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the open position while working at the unit. c. Interchange any two of the field connected main power wires at the unit terminal block or the factory mounted disconnect switch. Note: Interchanging “Load” side power wires at the fan contactors will only affect the individual fan rotation. Ensure that the voltage phase sequence at the main terminal block or the factory mounted disconnect switch is ABC as outlined in the “Electrical Phasing” section. If some of the fans are rotating backwards; a. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. b. Open the field supplied disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the open position while working at the unit. c. Interchange any two of the fan motor leads at the contactor for each fan that is rotating backwards.WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. Figure 69. Air-cooled (90-150 tons)/evaporative (100-162 tons) condenser fan locations with human interface designator 2B92B11 2B102B12 2B14 2B15 2B13 2B16 2B9 1K9 01K1 01B2 2B11 1K10 4K1 21B2 11K1 31B2 21K1 41B2 2B15 1K12 2B16 1K1 Condenser Fan Motor Designator Condenser Fan contactor Designator 120 TON 130 TON 150 TON 2B5 2B6 2B5 1K4* *1K1 6B2 Condenser Fan Motor Designator Condenser Fan contactor Designator 100 TON 118 TON 128 TON 140 TON 162 TON *Note: 2B5 and 2B6 are initiated with operation of 1K4 and 1K1 compressor contactors.
Unit Startup RT-SVX24K-EN11 7 System Airflow Measurements Constant Volume Systems 1. Ensure that the “System” selection switch at the remote panel is in the “Off” position and the “Fan” selection switch for constant volume units is in the “Auto” position. 2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal block or the unit mounted disconnect switch. HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. 3. Turn the 115 volt control circuit switch and the 24 volt control circuit switch to the “On” position. 4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for CV applications for the SERVICE TEST screens and programming instructions. 5. Use Table37, p.11 2to program the Supply Fan for operation by scrolling through the displays. 6. Once the configuration for the Fan is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the +key to designate the delay before the test is to start. This service test will begin after theTEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 7. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fans will begin to operate. 8. With the system in the SERVICE MODE and the supply fan rotating in the proper direction, measure the amperage at the supply fan contactors. If the amperage exceeds the motor nameplate value, the static pressure is less than design and the airflow is too high. If the amperage is below the motor nameplate value, static pressure may be too high and CFM may be too low. To determine the actual CFM (± 5%); a. Measure the actual fan RPM b. Calculate the Theoretical BHP Actual Motor Amps X Motor HP Motor Nameplate Amps c. Plot this data onto the appropriate Fan Performance Curve beginning with Figure 62, p. 100. Where the two points intersect, read straight down to the CFM line. Use this data to assist in calculating a new fan drive if the CFM is not at design specifications. An alternate method with less accuracy is to measure the static pressure drop across the evaporator coil.This can be accomplished by; a. drilling a small hole through the unit casing on eachside of the coil. Note: Coil damage can occur if care is not taken when drilling holes in this area. b. Measure the difference between the pressures at both locations. c. Plot this value onto the appropriate pressure drop curve beginning with Figure 71, p. 120. Use the data in Table 40, p. 127 (Component Static Pressure Drops) to assist in calculating a new fan drive if the CFM is not at design specifications. d. Plug the holes after the proper CFM has been established. 9. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. Variable Air Volume Systems 1. Ensure that the “System” selection switch at theremote panel is in the “Off” position. 2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal block or the unit mounted disconnect switch. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Unit Startup 11 8RT-SVX24K-EN HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. 3. Turn the 115 volt control circuit switch and the 24 volt control circuit switch to the “On” position. 4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the appropriate Programming Manual for VAV applications for the SERVICE TEST screens and programming instructions. Use T able 37, p. 112 to program the following system components for operation by scrolling through the displays: Supply Fan, Variable Frequency Drive (100% Output, if applicable), RTM Occ/Unocc Output (Unoccupied) 5. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the +key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 6. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fan will begin to operate. 7. With the VFD at 100% and the supply fan operating at full airflow capability, measure the amperage at the supply fan contactors. If the amperage exceeds the motor nameplate value, the static pressure is less than design and the airflow is too high. If the amperage is below the motor nameplate value, static pressure may be too high and CFM may be too low.To determine the actual CFM (± 5%); a. Measure the actual fan RPM b. Calculate the Theoretical BHP Actual Motor Amps X Motor HP Motor Nameplate Amps c. Plot this data onto the appropriate Fan Performance Curve beginning with Figure 62, p. 100. Where the two points intersect, read straight down to the CFM line. Use this data to assist in calculating a new fan drive if the CFM is not at design specifications. An alternate method with less accuracy is to measure the static pressure drop across the evaporator coil.This can be accomplished by: a. drilling a small hole through the unit casing on eachside of the coil. Note: Coil damage can occur if care is not taken when drilling holes in this area. b. Measure the difference between the pressures at both locations. c. Plot this value onto the appropriate pressure drop curve beginning with Figure 71, p. 120. Use the data in Table 40, p. 127 (Component Static Pressure Drops) to assist in calculating a new fan drive if the CFM is not at design specifications. d. Plug the holes after the proper CFM has been established. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. 8. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. Exhaust Airflow Measurement (Optional) 1. Close the disconnect switch or circuit protectorswitch that provides the supply power to the units terminal block or the unit mounted disconnect switch. HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. 2. Turn the 115 volt control circuit switch and the 24 volt control circuit switch to the “On” position. 3. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Unit Startup RT-SVX24K-EN11 9 key to display the first service screen. Refer to the latest edition of the appropriate programming manual for applications for the SERVICE TEST screens and programming instructions. 4. Use Table37, p.11 2to program the following system components for operation by scrolling through the displays: Exhaust Fan, Exhaust Dampers (100% Open, if applicable), Outside air dampers (100% Open), Variable Frequency Drive (100%, if applicable), RTM Occ/Unocc Output (Default) 5. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the +key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 6. Press the TEST START key to start the test. Remember that the delay designated in step 5 must elapse before the fans will begin to operate. 7. With the exhaust dampers open and the exhaust fan operating at full airflow capability, measure the amperage at the exhaust fan contactor. If the amperage exceeds the motor nameplate value, the static pressure is less than design and airflow is too high. If the amperage is below the motor nameplate value, static pressure may be too high and CFM may be too low. To determine the actual CFM (± 5%); a. Measure the actual fan RPM b. Calculate the Theoretical BHP Actual Motor Amps X Motor HP Motor Nameplate Amps Use appropriate figures beginning with Figure 71, p. 120 to calculate a new fan drive if the CFM is not at design specifications. 8. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. TRAQ™ Sensor Airflow Measurement (Optional with all units equipped with an economizer) 1. Open the Human Interface access door, located in theunit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for applications for the SERVICE TEST screens and programming instructions. 2. Use Table37, p.11 2to program the following system components for Economizer operation by scrolling through the displays; Supply Fan (On) Outside air dampers (Selected % Open) Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied) Outside Air CFM Setpoint Outside Air Pre-Heater Operation (if applicable) 3. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the +key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 4. Press the TEST START key to start the test. Remember that the delay designated in step 3 must elapse before the fans will begin to operate. 5. With the unit operating in the “TEST MODE”, the amount of outside air flowing through the TRAQ sensor can be viewed by switching to the “STATUS MENU” screen “OA CFM. 6. Scroll to the “ECONOMIZER ENABLE/ECONOMIZER POSITION” screen by pressing the “NEXT” key and read the corresponding damper opening percentage (%). 7. Press the STOP key at the Human Interface Module in the unit control panel to stop the unit operation. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Unit Startup 120RT-SVX24K-EN Performance Data Supply Fan with or without Variable Frequency Drive Figure 70. Supply fan performance LOW CFM — 90/100 tons, 25” supply fan Figure 71. Supply fan performance STANDARD CFM — 90/100 and 105/118 tons, 36” supply fan