Home > Trane > Air Conditioner > Trane Intellipak 2 Service Manual

Trane Intellipak 2 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Unit Startup
    RT-SVX24K-EN171
    Final Unit Checkout
    After completing all of the checkout and startup
    procedures outlined in the previous sections (i.e.,
    operating the unit in each of its Modes through all
    available stages of cooling and heating), perform these
    final checks before leaving the unit:
    [ ] Close the disconnect switch or circuit protector
    switch that provides the supply power to the unit
    terminal block or the unit mounted disconnect switch.
    HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
    UNIT DISCONNECT SWITCH. [ ] Turn the 115 volt control circuit switch “Off”.
    [ ] Turn the 24 volt control circuit switch to the “On”
    position.
    [ ] At the Human Interface Module, press the “SETUP”
    key. The LCD screen will display various preset
    “parameters of operation” based on the unit type, size, and the installed options. Compare the factory preset
    information to the specified application requirements.
    If adjustments are required, follow the step-by-step instructions provided in the appropriate programming
    manual for CV or VAV applications.
    [ ] Program the Night Setback (NSB) panel (if
    applicable) for proper unoccupied operation. Refer to
    the programming instructions for the specific panel.
    [ ] Verify that the Remote panel “System” selection
    switch, “Fan” selection switch, and “Zone
    Temperature” settings for constant volume systems are correct.
    [ ] Verify that the Remote panel “System” selection
    switch and the “Supply Air Temperature” settings for
    variable air volume systems are correct.
    [ ] Inspect the unit for misplaced tools, hardware, and
    debris.
    [ ] Turn the 115 volt control circuit switch “On”.
    [ ] Press the “AUTO” key at the Human Interface
    Module to begin system operation. The system will
    start automatically once the dampers modulate and a
    request for either heating or cooling has been given.
    [ ] Verify that all exterior panels including the control
    panel doors and condenser grilles are secured in place.
    Multi-piece Unit—Trane Startup
    Once the IntelliPak II multi-piece unit has been installed, all
    shipped with items have been installed, all utilities and
    drain pipes have been connected, the refrigeration piping
    has been reconnected and refrigerant charge has been
    adequately distributed throughout the system, and all
    ductwork has been attached to the unit,Trane will provide
    unit startup.
    Trane startup of multi-piece units will review the overall unit for exterior damage (dents, bends, missing panels,
    doors work properly), verify that the unit interior is free
    from debris/obstructions, ensure that the panels and
    doors are secured properly and verify that all wiring
    connections are tight.
    The overall installation will be reviewed to ensure the unit clearances are adequate to avoid air recirculation and all
    unit drain lines and traps are properly installed.
    The unit main power will be reviewed to ensure the unit is properly grounded, the main power feed wire gauge is
    adequately sized, the correct voltage is supplied to unit
    and electric heaters, and the incoming voltage is phase
    balanced. Verification will be performed to ensure that all
    field installed control wiring is applied to the correct
    terminals, all automation and remote controls installed/
    wired and control wiring for CV, SZVAV and VAV controls
    is completed.
    The refrigeration system will be reviewed to ensure the coil fins are straightened, the removal of shipping
    hardware and plastic covers for compressors, proper oil
    level in the compressors, crankcase heaters have been
    operational for at least 12 hours time prior toTrane startup
    being performed. The proper compressor voltage and
    amperage, correct position of service valves prior to
    Figure 120. 850-1100 MBH
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury. 
    						
    							Unit Startup
    172RT-SVX24K-EN
    startup and proper system subcooling and superheat will
    be verified.
    The unit fans will be checked to ensure that the condenser fan blade set-screws to the motor shaft are tight, that the
    hold down bolts and channels from fan sections have been
    removed, proper adjustment of fan section spring
    isolators, proper fan belts tension, adequate fan bearings
    grease, alignment of fan sheaves, adequate tightness of
    supply and exhaust fan pulley bolts, proper fan rotation,
    and proper fan motor amperage.
    A check will be made to ensure both piping to the condenser and air handler side of the system have been
    completed and interconnecting refrigerant tubing has
    been evacuated by the contractor prior to Trane
    performing the startup. All damper linkages will be
    checked for proper adjustment, and proper damper
    operation and outside air pressure sensors verified.
    Units equipped with electric heaters will be checked to
    ensure that the heating system matches the unit
    nameplate and for correct voltage supply to the heaters.
    Units equipped with gas heaters will be checked to ensure
    that the flue assembly is secure and properly installed,
    sufficient gas pressure exists according to pipe size, no
    leaks exist in gas supply line, the gas heat piping includes
    a drip leg, condensate line and the combustion air CO2 and
    O2 levels are normal. Units equipped with hot water heat will be checked to
    ensure that the hot water pipes are properly routed, sized
    and leak free; for the presence of swing joints or flexible
    connectors next to the hot water coil; proper gate valve
    installation in the supply and return branch line; proper
    three way modulating valve installation, and proper coil
    venting will be verified.
    Units equipped with steam heat will be checked to ensure
    that the hot water pipes are properly routed, sized and leak
    free; proper swing check vacuum breaker installation;
    proper 2-way modulating valve installation; proper steam
    trap installation.
    Units equipped with energy recovery wheels will be
    checked to ensure proper rotation and operation of the
    wheel. The service test guide will be used to check proper
    component operation.
    Finally, the program set points for proper unit operation
    will be validated through human interface module. Once
    the IntelliPak II multi-piece unit has been started, a
    communication will be provided of startup activities and
    the associated operating log. 
    						
    							Unit Startup
    RT-SVX24K-EN173
    Table 49. Trane startup checklist
    Important: This checklist is not intended as a substitution for the contractor’s installation instruction.
    This checklist is intended to be a guide for the Trane technician just prior to unit startup. Many of the recommended checks and actions could expose the technician to electrical and mechanical hazards. Refer to the appropriate sections
    in the this manual for appropriate procedures, component specifications and safety instructions.
    Job Name Serial #
    Job Location Model #
    Sales Order # Ship Date
    Unit DL # (special units) Date
    Starting Sales Office Technician
    Important: Except where noted, it is implied that theTrane technician is to use this checklist for inspection/verification
    of prior tasks completed by the general contractor at installation. Use the line item content to also record
    the associated values onto the Trane unitary packaged equipment log.
    Complete
    1. Crankcase heaters working for 8 hours prior to arrival of Trane technician performing startup
    2. Correct voltage supplied to unit and electric heaters
    3. Unit exterior inspected
    4. Disconnect all power, Unit interior free from debris/obstructions etc.
    5. Open all access doors to verify all open and close fully without any binding
    6. All wiring connections tight
    7. Unit properly grounded
    8. Copper power wiring meets sizing requirement
    9. All field control wiring for CV, SZVAV or VAV controls completed
    10. All automation and remote controls installed/wired
    11. Unit clearances adequate for service and to avoid air recirculation etc.
    12. All unit drain lines and traps proper
    13. All coil fins inspected and straightened
    14. Shipping hardware for compressors removed
    15. Hold down bolts and channels from fan sections removed
    16. Fan section spring isolators checked/adjusted
    17. Damper linkages tight/adjusted
    18. Rail connector splice brackets installed on low side base rail
    Where applicable: Evaporative condenser
    19. Verify incoming water pressure is between 35-60psig, dynamic pressure (measured with valve open) for min flow rate of 30 GPM
    20. Verify fan shipping brackets between fans and mist eliminators above spray distribution system have been removed
    21. Verify water treatment system has been installed and approved - discontinue start-up if proof of active water treatment does not exist
    Continued on next page
    22. Verify conductivity controller calibration has been documented
    23. Verify conductivity controller min and max setpoints have been setup
    24. Verify all water and drain connections are complete
    25. Verify the sump fills to within 1 of the overflow
    26. Verify drain valve is set to drain during power loss or hold during power loss per job specification
    Where applicable: Electric Heat
    27. Electric heat circuits have continuity
    Where applicable: Gas Heat
    28. Gas heat piping includes drip leg previously installed by controlling contractor
    29. Gas heat flue assembly fully installed 
    						
    							Unit Startup
    174RT-SVX24K-EN
    30. Gas heat condensate line + heat tape installed where applicable
    Where applicable: HW/Steam Heat
    31. Modulating valve and actuator (HW and Steam) installed/wired
    32. Steam heat swing check vacuum breakers installed per IOM direction
    33. Steam heat condensate trap provided
    34. O/A pressure sensor installed and piped
    35. High side to low side piping to be completed prior to Trane technician arriving for startup
    36. Space sensor and pneumatic tubing installed properly
    Complete
    37. Compressor discharge service valves, oil valves and liquid lines valves open/back seated (excludes Schrader valves)
    38. Compressor oil levels (½ -¾ high in glass) proper
    39. Verify power wires are connected in the high voltage power box
    40. Verify field installed control wiring landed on correct terminals
    41. All fan belts tensioned and bearings greased
    42. Heat wheel rotates freely by hand
    43. Reenergize power. Phase sequence (A-B-C) proper for compressor rotation
    44. Incoming voltage balanced
    45. All panels/doors secured prior to startup
    Start unit
    46. Service test guide used to operate unit components
    47. Fan amperages within nameplate specs
    48. Verify system airflow
    49. Dampers open and close properly
    50. Adjust outside air damper travel
    51. On evaporative condenser models: Verify the sump fills to within 1.5” below the overflow, which is within the slot on the max float
    bracket (see Figure 114, p. 164 )
    52. Compressor operation normal and within amperage rating
    53. Superheat (14-18°F) and subcooling (14-22°F) normal for air-cooled units
    54. Electric, hot water and steam heating operation checked
    55. Gas heating startup sequence of operation per IOM has been followed
    56. Gas heat operation has been verified with combustion analyzer
    57. Incoming gas pressure does not drop below 7 water column when burner is on high fire
    58. Operating log completed
    Table 49. Trane startup checklist (continued) 
    						
    							RT-SVX24K-EN175
    Service and Maintenance
    WARNING
    Hazardous Voltage and Exposure to
    Ultraviolet Radiation!
    This product contains components that emit high- intensity ultraviolet (UV-C) radiation which can be
    harmful to unprotected eyes and skin. To avoid injury,
    disconnect all electrical power, including remote
    disconnects, and make sure the UV lights are off before
    servicing. Follow proper lockout/tagout procedures to
    ensure the power can not be inadvertently energized.
    Failure to disconnect power before servicing could
    result in burns or electrocution which could result in
    death or serious injury.
    Trane does not recommend field installation of ultraviolet lights in its equipment for the intended
    purpose of improving indoor air quality. High intensity
    C-band ultraviolet light is known to severely damage
    polymer (plastic) materials and poses a personal safety
    risk to anyone exposed to the light without proper
    personal protective equipment. Polymer materials
    commonly found in HVAC equipment that could be
    susceptible include insulation on electrical wiring, fan
    belts, thermal insulation, various fasteners and
    bushings. Degradation of these materials can result in
    serious damage to the equipment.
    Trane accepts no responsibility for the performance or operation of our equipment in which ultraviolet devices
    were installed outside of the Trane factory or its
    approved suppliers.
    Table 50. Control Settings and Time Delays
    Control Description Elec. DesignationContacts Open Contacts Closed
    Combustion Airflow Switch   
    (Gas Heat Only) 4S25see note 10.1 - 0.25 wc rise in press diff
    Supply Airflow Switch   
    (Gas Heat Only) 4S380.03 - 0.12 wc  0.15 + 0.05 wc rise in press diff
    Freezestat   
    (Hydronic Heat Only) 4S12(N.O.) Auto Reset 40 F
    Gas Heat Units
    Prepurge Timer: Honeywell 4U18internal timing function 2 Stage 850/1100 MBH 60—seconds/
    All other configurations—30 seconds
    Sequencing Time Delay Relay 4DL6N.C. - timed to close 60 seconds 
    + 20%
    Notes: The combustion airflow switch (4S25) differential is 0.02 - 0.08 wc\
    . 
    						
    							Service and Maintenance
    176RT-SVX24K-EN
    Table 51. Gas Heat—High Limit
    UNIT
    TONS 2500 MBH HIGH LIMIT 
    CONTACTS CONTACTS
    FAN SIZE  (IN) CONFIG. OPEN CLOSE
    120-162 40 DF 195 155
    40 HZ 240 200
    32 DF & HORZ 220 180
     1800 MBH HIGH LIMIT 
     120-162
    32 &40 DF 240 200
    32 &40 HZ 220 180
    90-118 32 DF & HZ 240 200
    36 DF & HZ 240 200
    36 HZ 240 310
    25 DF 240 200
    25 HZ 220 180
     1100 MBH HIGH LIMIT 
     120-162
    32 DF 240 200
    32 HZ 200 160
    40 DF & HZ 240 200
    90-118 32 DF 240 200
    32 HZ 200 160
    25 &36 DF & HZ 220 180
    850 MBH HIGH LIMIT 
     90-118 25 &36 DF & HZ 240 200
    Table 52. Electric Heat—Selection Limits
    TonsIndoor Fan 
    Option Electric Heat Option Supply 
    Discharge Linear Limit - 
    Open Temp. Fan Fail Limit - 
    Open Temp.
    120-162 Ton High (40) High (300 kW) Downflow 185F185F
    Hz (right) 185F185F
    Low (140 kW) Downflow 150F185F
    Hz (right) 150F185F
    Low (32) High (300 kW) Downflow 205F185F
    Hz (right) 185F185F
    Low (140 kW) Downflow 150F185F
    Hz (right) 150F185F
    105/118 Ton High (36) High (262.5 kW) Downflow 195F155F
    Hz (right) 195F155F
    Low (90 kW) Downflow150F175F
    Hz (right) 150F175F
    Low (32) High (262.5 kW) Downflow 225F185F
    Hz (right) 205F185F
    Low (90 kW) Downflow150F175F
    Hz (right) 150F175F
    90/105 Ton High (36) High (262.5 kW) Downflow 195F155F
    Hz (right) 195F155F
    Low (90 kW) Downflow150F175F 
    						
    							Service and Maintenance
    RT-SVX24K-EN177
    Hz (right)150F175F
    Low (25) High (262.5 kW) Downflow 215F155F
    Hz (right) 235F155F
    Low (90 kW) Downflow150F175F
    Hz (right) 150F175F
    Table 52. Electric Heat—Selection Limits
    Table 53. Compressor Circuit Breaker Electrical Characteristics
    460V 575V380V
    Unit Size Compressor 
    Designator Compressor 
    Size Must 
    Hold Must 
    Trip Must 
    Hold Must 
    Trip Must 
    Hold Must 
    Trip
    90/105 1A, 2A CSHN250 41.5 47.7 33.2 38.2 41.4 47.6
    1B, 2B CSHN250 41.5 47.7 33.2 38.2 41.4 47.6
    105/118 1A, 2A CSHN250 41.5 47.7 33.2 38.2 41.4 47.6 1B, 2B CSHN315 54.4 62.6 43.6 50.1 54.3 62.4
    120/128 1A, 2A CSHN315 57.7 66.4 46.3 53.2 57.3 66 1B, 2B CSHN315 54.4 62.6 43.6 50.1 54.3 62.4
    130/140 1A, 2A CSHN315 57.7 66.4 46.3 53.2 57.3 66 1B, 2B CSHN374 63.4 72.9 50.0 57.5 63.3 72.8
    150/162 1A, 2A CSHN374 66.7 76.7 52.7 60.6 66.4 76.3 1B, 2B CSHN374 63.4 72.9 50.0 57.5 63.3 72.8 
    						
    							Service and Maintenance
    178RT-SVX24K-EN
    Note:**See fuse replacement table on VFD panel for VFD
    power fuses (F40, F41, F42).
    Table 54. Unit Internal Fuse Replacement Data & VFD
    Factory Settings 
    						
    							Service and Maintenance
    RT-SVX24K-EN179
    Table 55. Filter Data
    Filters
    Unit 
    Model  (AC/ EC) Standard 2 High Eff 
    Throwaways 90-95% Bag Filters 
    with Prefilters 90-95% Cartridge Filters 
    with Prefilters 90-95% Low Pressure Drop 
    Cartridge Filters
    Qty Size of 
    Each Face 
    Area 
    (ft2) Pre-filters Bag Filters Prefilters Cartridge Filters Prefilters Low PD Filters
    Qty Size Qty Size Face 
    Area 
    (ft2) Qty Size Qty Size Face 
    Area 
    (ft2) Qty Size Qty Size  Face 
    Area 
    (ft2)
    90/100 21 20x24x2
    8021 20x24x2 21 20x24x19
    8021 20x24x2 21 20x24x12
    8021 20x24x2 21 20x24x12
    80
    5 15x24x2 5 12x24x2 5 12x24x19 5 12x24x2 5 12x24x12 5 12x24x2 5 12x24x12
    105/ 118 21 20x24x2
    8021 20x24x2 21 20x24x19
    8021 20x24x2 21 20x24x12
    8021 20x24x2 21 20x24x12
    80
    5 15x24x2 5 12x24x2 5 12x24x19 5 12x24x2 5 12x24x125 12x24x2 5 12x24x12
    120/ 128 28 20x24x2 93 21 20x24x2 21 20x24x19
    8021 20x24x2 21 20x24x12
    8021 20x24x2 21 20x24x12
    80
    5 12x24x2 5 12x24x19 5 12x24x2 5 12x24x125 12x24x2 5 12x24x12
    130/ 140 28 20x24x2 93 21 20x24x2 21 20x24x19
    8021 20x24x2 21 20x24x12
    8021 20x24x2 21 20x24x12
    80
    5 12x24x2 5 12x24x19 5 12x24x2 5 12x24x125 12x24x2 5 12x24x12
    150/ 162 28 20x24x2 93 21 20x24x2 21 20x24x19
    8021 20x24x2 21 20x24x12
    8021 20x24x2 21 20x24x12
    80
    5 12x24x2 5 12x24x19 5 12x24x2 5 12x24x125 12x24x2 5 12x24x12 
    						
    							Service and Maintenance
    180RT-SVX24K-EN
    Table 56. Final Filter Data
    Final Filters
    Unit Model  (AC/EC) 90-95% Low Pressure Drop Cartridge Filters 90-95% Bag Filters with Prefilters 90-95% Cartridge Filters with Prefilters
    Pre-filters Low PD Cartridge Filters Prefilters Bag Filters Prefilters Cartridge Filters
    Qty Size Qty Size Face Area (ft2) Qty Size Qty  Size Face Area (ft2) Qty Size Qty Size  Face Area (ft2)
    90/100 15 24x24x4 15 24x24x12 74 15 24x24x2 15 24x24x19 74 15 24x24x2 15 24x24x12 74
    7 12x24x4 7 12x24x12 7 12x24x2 7 12x24x19 7 12x24x2 7 12x24x12
    105/118 15 24x24x4 15 24x24x12 74 15 24x24x2 15 24x24x19 74 15 24x24x2 15 24x24x12 74
    7 12x24x4 7 12x24x12 7 12x24x2 7 12x24x19 7 12x24x2 7 12x24x12
    120/128 15 24x24x4 15 24x24x12 74 15 24x24x2 15 24x24x19 74 15 24x24x2 15 24x24x12 74
    7 12x24x4 7 12x24x12 7 12x24x2 7 12x24x19 7 12x24x2 7 12x24x12
    130/140 15 24x24x4 15 24x24x12 74 15 24x24x2 15 24x24x19 74 15 24x24x2 15 24x24x12 74
    7 12x24x4 7 12x24x12 7 12x24x2 7 12x24x19 7 12x24x2 7 12x24x12
    150/162 15 24x24x4 15 24x24x12 74 15 24x24x2 15 24x24x19 74 15 24x24x2 15 24x24x12 74
    7 12x24x4 7 12x24x12 7 12x24x2 7 12x24x19 7 12x24x2 7 12x24x12Unit Model  (AC/EC) 90-95% High Temp Cartridge Filters 
    with Prefilters HEPA Filters with Prefilters High Temp HEPA Filters with Prefilters
    Pre-filters High Temp Cartridge Filters Prefilters HEPA Filters Prefilters High HEPA Temp Filters
    Qty Size Qty Size Face Area (ft
    2) Qty Size Qty  Size Face Area (ft
    2) Qty Size Qty Size  Face Area (ft
    2)
    90/100 15 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    74
    7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12
    105/118 15 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    74
    7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12
    120/128 15 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    74
    7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12
    130/140 15 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    74
    7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12
    150/162 15 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    7415 24x24x2 15 24x24x12
    74
    7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12 7 12x24x2 7 12x24x12 
    						
    All Trane manuals Comments (0)