Power Wire Sizing and Protection Devices
To correctly size electrical service wiring for a unit, find the
appropriate calculations listed below. Each type of unit has
its own set of calculations for MCA (Minimum Circuit
Ampacity), MOP (Maximum Overcurrent Protection), and RDE (Recommended Dual Element fuse size). Read the
load definitions that follow and then find the appropriate
set of calculations based on unit type.
Note: Set 1 is for cooling only and cooling with gas heat...

Page 82

Installation
82RT-SVX24K-EN
Table 23. Electrical service sizing data—motors
Condenser Fan Motors
Nominal  Tons  No. of Fans 460 V 575 V 380 V
FLA FLA FLA
90, 105 6 16.2 13.2 15
120, 130,  150 8 21.6 17.6 20
100 2 11.8 N/A N/A
118, 128,  140, 162 2 11.8 N/A N/A
Supply Fan Motors
Motor 
Horsepow er 460 V 575 V 380 V
FLA FLA FLA
15 18.5 15.1 24
20 24.7 19.6 29
25 3124.5 38
30 36.6 29.2 47
40 49.0 3954
50 60.5 4868
60 71.5 57.2 81
75 9072103
100 115 92N/A
Exhaust/Return Fan Motors
Motor 
Horsepow er 460 V...

Page 83

Installation
RT-SVX24K-EN83
Field Installed Control Wiring
The Rooftop Module (RTM) must have a mode input in
order to operate the rooftop unit. The flexibility of having
several system modes depends upon the type of sensor
and/or remote panel selected to interface with the RTM. An
overall layout of the various control options available, with
the required number of conductors for each device, is
illustrated beginning with Figure 57, p. 89.
Note: All field wiring must conform to NEC guidelines as
well as...

Page 84

Installation
84RT-SVX24K-EN
c. Must not pass between buildings.
Constant Volume System Controls
Remote Panel w/o NSB—BAYSENS110*
This electronic sensor features four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto) with four system status LEDs. It is a manual or automatic changeover control with dual setpoint
capability. It can be used with a remote zone sensor
BAYSENS077*. Refer to Table 34, p. 87for the
Temperature vs. Resistance coefficient.
Constant Volume Zone...

Page 85

Installation
RT-SVX24K-EN85
Remote Minimum Position Potentiometer
(BAYSTAT023*)
The remote minimum position potentiometer is used on
units with an economizer. It allows the operator to
remotely set the economizer minimum position (which
controls the amount of outside air entering the unit). Use
the installation instructions that shipped with the
potentiometer to install it, and the appropriate illustrations
beginning with Figure 57, p. 89to connect it to the unit.
Single Zone Variable Air Volume & Rapid...

Page 86

Installation
86RT-SVX24K-EN
– OA Dampers - Closed; Return Damper - Open
– Heat - All heat stages off; Mod Heat output at 0 VDC
– Occupied/Unoccupied/VAV box output - Energized
– VOM Relay - Energized (if so equipped)
– Preheat Output - Off
– Return Fan - Off; Exhaust Dampers - Closed (if so
equipped)
– Return VFD - Min (if so equipped)
Ventilation Override Module (VOM)
Important: The ventilation override system should not
be used to signal the presence of smoke
caused by a fire, as it is not intended...

Page 87

Installation
RT-SVX24K-EN87
– Heat - All heat stages off; Mod Heat output at 0 VDC
– Occupied/Unoccupied/VAV box output - Energized
– VOM Relay - Energized
– Preheat Output - Off
– Return Fan - On; Exhaust Dampers - Open (if so
equipped)
– Return VFD - Max (if so equipped)
– OA Bypass Dampers - Open (if so equipped)
– Exhaust Bypass Dampers - Open (if so equipped)
5. PURGE with duct pressure control sequence “E”
This sequence can be used when supply air control is required
 for smoke control.
– Supply...

Page 88

Installation
88RT-SVX24K-EN
heating operation is limited to either 50% or 100%.
Demand limit can be initiated by a toggle switch closure,
a time clock, or an ICS
TMcontrol output. These contacts
must be rated for 12 ma @ 24 VDC minimum.
Outside Air Sensor—BAYSENS016*
This device senses the outdoor air temperature and sends this information in the form of an analog input to the RTM.
Its factory installed on units with an economizer, but can
be field provided/installed and used for informational
purposes...

Page 89

Installation
RT-SVX24K-EN89
Figure 57. Typical field wiring diagram for 90 to 162 ton CV control options 

Page 90

Installation
90RT-SVX24K-EN
Figure 58. Typical ventilation override binary output for 90 to 162 ton CV control options 