Unit Startup RT-SVX24K-EN111 internally connected for clockwise rotation with the incoming power supply phased as A, B, C. Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following the steps below: [ ] Turn the field supplied disconnect switch that provides power to terminal block or to the unit mounted disconnect switch to the “Off” position. [ ] Connect the...
Page 112
Unit Startup 11 2RT-SVX24K-EN Table 37. Service test guide for component operation — part I of II Component Being Tested COMPONENT CONFIGURATION Supply Fan Return Fan Exhaust Fan Condenser Fans Heat Stages Compressor Stage 1231234 COMPRESSOR 90 - 105 Ton 1A OFF OFF OFF ALL OFF OFF OFF OFF ON OFF OFF OFF 1B OFF OFF OFF ALL OFF OFF OFF OFF ON ON OFF OFF 2A OFF OFF OFF ALL OFF OFF OFF OFF OFF OFF ON OFF 2B OFF OFF OFF ALL OFF OFF OFF OFF OFF OFF ON ON120 - 162 Ton 1A...
Page 113
Unit Startup RT-SVX24K-EN11 3 SUPPLY FAN ON ON OFF ALL OFF OFF OFF OFF OFF OFF OFF OFF RETURN FAN ON ON N/A ALL OFF OFF OFF OFF OFF OFF OFF OFF EXHAUST FAN OFF N/A ON ALL OFF OFF OFF OFF OFF OFF OFF OFF GAS HEAT (Full Capacity) ON ON OFF ALL OFF ON ON ON OFF OFF OFF OFF STAGE 1 ON ON OFF ALL OFF ON OFF ON OFF OFF OFF OFF STAGE 2 ON ON OFF ALL OFF OFF ON N/A OFF OFF OFF OFF Full Modulating ON ON OFF ALL OFF...
Page 114
Unit Startup 11 4RT-SVX24K-EN Table 38. Service test guide for component operation — part II of II Component Being Tested Component Configuration Occ Unocc Relay Sump Pump Sump Heater Econo Damper Exhaust Damper VFD Output COMPRESSOR 90 - 105 Ton 1A Closed Closed 0%Default OFFOFF 1B Closed Closed 0%Default OFFOFF 2A Closed Closed 0%Default OFFOFF 2B Closed Closed 0%Default OFFOFF 120 - 162 Ton 1A Closed Closed 0%Default OFFOFF 1B Closed Closed 0%Default OFFOFF 2A Closed Closed 0%Default OFFOFF 2B Closed...
Page 115
Unit Startup RT-SVX24K-EN11 5 Service Testing—Evaporative Condenser Components From the Compressor and Condenser Service Menu screens—Head Pressure Control: AUTO or Head Pressure Control: MANUAL 1. Select: Head Pressure Control: MANUAL Note: All outputs, Sump Control, Fan Stage Control and Fan speed Control (per circuit where specified), will be available for ON/OFF, OPEN/CLOSED, 0-100% manual settings considering the stipulations in Table 39 : Notes: 1. Sump Freeze Protection is active during AUTO but...
Page 116
Unit Startup 11 6RT-SVX24K-EN If all of the fans are rotating backwards; a. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. b. Open the field supplied disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the open position while working at the unit. c. Interchange any two of the field connected main power wires at the unit terminal block or the factory mounted disconnect switch. Note: Interchanging “Load” side power wires at...
Page 117
Unit Startup RT-SVX24K-EN11 7 System Airflow Measurements Constant Volume Systems 1. Ensure that the “System” selection switch at the remote panel is in the “Off” position and the “Fan” selection switch for constant volume units is in the “Auto” position. 2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal block or the unit mounted disconnect switch. HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. 3. Turn the 115 volt...
Page 118
Unit Startup 11 8RT-SVX24K-EN HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR UNIT DISCONNECT SWITCH. 3. Turn the 115 volt control circuit switch and the 24 volt control circuit switch to the “On” position. 4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the appropriate Programming Manual for VAV applications for the SERVICE TEST screens and programming instructions. Use T able 37,...
Page 119
Unit Startup RT-SVX24K-EN11 9 key to display the first service screen. Refer to the latest edition of the appropriate programming manual for applications for the SERVICE TEST screens and programming instructions. 4. Use Table37, p.11 2to program the following system components for operation by scrolling through the displays: Exhaust Fan, Exhaust Dampers (100% Open, if applicable), Outside air dampers (100% Open), Variable Frequency Drive (100%, if applicable), RTM Occ/Unocc Output (Default) 5. Once the...
Page 120
Unit Startup 120RT-SVX24K-EN Performance Data Supply Fan with or without Variable Frequency Drive Figure 70. Supply fan performance LOW CFM — 90/100 tons, 25” supply fan Figure 71. Supply fan performance STANDARD CFM — 90/100 and 105/118 tons, 36” supply fan