Page 91
Installation RT-SVX24K-EN91 Figure 59. Typical field wiring diagram for 90 to 162 ton VAV control options
Page 92
Installation 92RT-SVX24K-EN Figure 60. Typical field wiring diagram notes for 90 to 162 ton VAV and CV control options
Page 93
Installation RT-SVX24K-EN93 Figure 61. Typical GBAS analog input wiring diagram for 90 to 162 ton CV and VAV control options Note:See Figure 64, p. 101
Page 94
Installation 94RT-SVX24K-EN Table 35. GBAS voltage vs. setpoint SetpointGBAS 0-5 VDCGBAS 0-10 VDCValid Range Occ Zone Cooling Setpoint(CV only)0.5 to 4.5 VDC0.5 to 9.5 VDC50 to 90°F Unocc Zone Cooling Setpoint 0.5 to 4.5 VDC 0.5 to 9.5 VDC 50 to 90°F Occ Zone Heating Setpoint(CV only)0.5 to 4.5 VDC0.5 to 9.5 VDC50 to 90°F Unocc Zone Heating Setpoint 0.5 to 4.5 VDC 0.5 to 9.5 VDC 50 to 90°F SA Cooling Setpoint (VAV only)0.5 to 4.5 VDC0.5 to 9.5 VDC40 to 90°F SA Cooling Setpoint (SZVAV only) 0.5 to 4.5 VDC...
Page 95
Installation Checklist RT-SVX24K-EN95 Installation Checklist General Checklist (applies to all units) Unit checked for shipping damage and material shortage Verify that the installation location of the unit will provide the required clearance for proper operation Roof curb assembled and installed Roof curb level and square Ductwork secured to curb, or unit Corners of duct adapters sealed on units with horizontal supply or return Horizontal supply or return ductwork is self supporting Pitch...
Page 96
Installation Checklist 96RT-SVX24K-EN Using 0.75 x 24 threaded rod pull and secure evaporator section and outside air section together Using .375 bolts, nuts and washers pull and secure the roof rails together Installed roof splice plate Added bullwrap to electrical wiring between evaporator and outside air section Connected power and control wiring between evaporator and outside air section Gasket applied and side panels installed on unit split Butyl tape applied on top of unit split along roof...
Page 97
Installation Checklist RT-SVX24K-EN97 Energy Recovery Wheel Verify that the wheel turns freely though a full rotation Confirm that all wheel segments are fully engaged in the wheel frame and that the segment retainers are completely fastened Confirm the seal adjustment and proper belt tracking on the wheel rim
Page 98
98RT-SVX24K-EN Unit Startup Sequence of Operation Cooling Sequence of Operation Time delays are built into the controls to increase reliability and performance by protecting the compressors and maximizing unit efficiency. SZVAV Cooling Sequence of Operation Single Zone VAV units will be equipped with a VFD controlled supply fan which will be controlled via the 0- 10VDC RTM VFD output and the RTM Supply Fan output. With the RTM Supply Fan output energized and the RTM VFD output at 0Vdc the fan speed...
Page 99
Unit Startup RT-SVX24K-EN99 Low Ambient Compressor Operation Certain applications require compressor operation at lower ambient conditions than standard units. Low ambient compressor operation is a factory configured option that allows units to operate down to -10°F by extending the low ambient compressor lockout setpoint range. Standard configuration units are limited to a minimum low ambient compressor lockout setpoint of 40° F. In conditions below 40°F the low-pressure cutout (LPC) switch can open in...
Page 100
Unit Startup 10 0RT-SVX24K-EN The drain control can be configured via the Human Interface, and by the drain actuator installation, to hold or drain water on power loss; the default is set to drain. Periodic purge is a cyclic opening of the drain to remove debris and buildup from the sump and add additional fresh water to the sump. Periodic purge has an adjustable interval from the setup menu on the Human Interface with a range of 1-12 hours or can be set to disabled - the default position if periodic...