Home > Trane > Air Conditioner > Trane Intellipak 2 Service Manual

Trane Intellipak 2 Service Manual

Here you can view all the pages of manual Trane Intellipak 2 Service Manual. The Trane manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.

Page 41

Dimensional Data
RT-SVX24K-EN41
Tonnage Blank 
Section Gas 
Heat Supply Opening
X4 (One or  Two-Piece  Models) X4 
(Three- Piece 
Models) Y4 W4 H2
90-105/100-118 None None 351  3/16 370  7/16 10 10/16 54 12/16 84 15/16
90-105/100-118  4 ft None 399  6/16 418 11/16 10 10/16 54 12/16 84 15/16
90-105/100-118 8 ft None 447 10/16 466 14/16 10 10/16 54 12/16 84 15/16
120-150/128-162 None None 415 15/16 441  6/16 10 10/16 54 12/16 84 15/16
120-150/128-162 4 ft None 464  2/16 489 10/16 10 10/16 54 12/16 84...

Page 42

Dimensional Data
42RT-SVX24K-EN
Figure 13. Evaporative condenser water connection locations
RIGHT SIDE VIEW  

Page 43

Dimensional Data
RT-SVX24K-EN43
Figure 14. Electrical entry details (in.)
16
603
4
711
4
76 1
4
81 1
4
46 1
16
48 1
16
61 3
444
Ø3 5
8
Ø1 116Ø78
6
5
165 5
16
Marine lights
customer supplied 
power service 
entrance Unit power External customer 
connection points
Outside edge of 
base rail 
51 5
8
53 11
16
31 11
16
Ø1 12
Bottom View  

Page 44

44RT-SVX24K-EN
Weights
Notes:
 1.Weights shown for air-cooled units include the following features: standard coils, 0-25% outs\
ide air, throwaway filters, low CF M supply fan, minimum 
motor sizes, constant volume, 460 XL, No heat. Weights shown for Evaporative condensing units include high-capacity evaporator coil and the weight 
of the extra structure associated with a two piece unit.
 2. Weights shown represent approximate operating weights and have a + 5% accuracy. To calculate weight for a specific...

Page 45

Weights
RT-SVX24K-EN45
Exhaust VFD (60-100 hp)- 295 - 295 - 295 - 295 - 295
Exhaust Fan Motor - 7.5 hp - 160160 - 160 - 160 - 160
Exhaust Fan Motor - 10 hp - 181 - 181 - 181 - 181 - 181
Exhaust Fan Motor - 15 hp - 206 - 206 - 206 - 206 - 206
Exhaust Fan Motor - 20 hp - 206 - 206 - 206 - 206 - 206
Exhaust Fan Motor - 25 hp - 358 - 358 - 358 - 358 - 358
Exhaust Fan Motor - 30 hp - 413 - 413 - 413 - 413 - 413
Exhaust Fan Motor - 40 hp - 495 - 495 - 495 - 495 - 495
Exhaust Fan Motor - 50 hp - 604 - 604 - 604...

Page 46

Weights
46RT-SVX24K-EN
Cabinet
Cabinet- 8097 - 8315 - 9473 - 9473 - 9473
Cabinet - 4 Blank Section - 935 - 935 - 901 - 901 - 901
Cabinet - 8 Blank Section - 1709 - 1709 - 1682 - 1682 - 1682
Control Box - Main
Control Box - Main - 519 - 519 - 519 - 519 - 519
Convenience Outlet - 36 - 36 - 36 - 36 - 36
Low Ambient VFD - 57 - 57 - 57 - 57 - 57
2/3 Piece Unit Adder
2 Piece Adder- 406 - 406 - 406 - 406 - 406
3 Piece Adder - 1157 - 1157 - 1236 - 1236 - 1236
Air-Cooled Condenser
Total Weight of Condenser...

Page 47

RT-SVX24K-EN47
Installation
Roof Curb and Ductwork
The roof curbs for units consist of two main components;
a pedestal to support the unit condenser section and a “full
perimeter” enclosure to support the unit air handler
section.
Before installing any roof curb, verify;
1. That it is the correct curb for the unit,
2. That it includes the necessary gaskets and hardware
3. That the purposed installation location provides the required
 clearance for proper operation.
4. ensure that the curb is level and...

Page 48

Installation
48RT-SVX24K-EN
Figure 16. Pitch pocket location
B1
B2
B3
A2
B1
B2
B3
A1
Pitch Pocket
Pitch PocketRoof Curb
1Pc Roof Curb
2Pc
Table 15. Pitch pocket dimensions (in.)
One-Piece Two/Three-
Piece One, Two, or Three-Piece
Tonnages A1 A2 B1 B2 B3
90113.8 129.9±1 68.875 73.875 78.875
105 131.8 147.9±1 68.875 73.875 78.875
120,130,150 140.8 156.9±1 68.875 73.875 78.875
100,118,128,14 0,162 N/A 135.0±1 68.875 73.875 78.875
Figure 17. Ductwork conversion 

Page 49

Installation
RT-SVX24K-EN49
Field Converting Horizontal Ductwork
(Supply or Return) from Right to the Left
Side
To field convert horizontal ductwork from right side to the
left, follow this procedure:
1. Remove Panel 2 from end of unit
2. Remove the Door and Door header from the left side.
3. Assemble Door header and Door removed from the left side
 in the empty location on the end wall.
4. Remove Panel 1 and Post from the left side. Remove g
 askets from the base rail flange at the bottom.
5. Remove the...

Page 50

Installation
50RT-SVX24K-EN
Figure 18. Ductwork conversion 
Start reading Trane Intellipak 2 Service Manual