Page 41
Dimensional Data RT-SVX24K-EN41 Tonnage Blank Section Gas Heat Supply Opening X4 (One or Two-Piece Models) X4 (Three- Piece Models) Y4 W4 H2 90-105/100-118 None None 351 3/16 370 7/16 10 10/16 54 12/16 84 15/16 90-105/100-118 4 ft None 399 6/16 418 11/16 10 10/16 54 12/16 84 15/16 90-105/100-118 8 ft None 447 10/16 466 14/16 10 10/16 54 12/16 84 15/16 120-150/128-162 None None 415 15/16 441 6/16 10 10/16 54 12/16 84 15/16 120-150/128-162 4 ft None 464 2/16 489 10/16 10 10/16 54 12/16 84...
Page 42
Dimensional Data 42RT-SVX24K-EN Figure 13. Evaporative condenser water connection locations RIGHT SIDE VIEW
Page 43
Dimensional Data RT-SVX24K-EN43 Figure 14. Electrical entry details (in.) 16 603 4 711 4 76 1 4 81 1 4 46 1 16 48 1 16 61 3 444 Ø3 5 8 Ø1 116Ø78 6 5 165 5 16 Marine lights customer supplied power service entrance Unit power External customer connection points Outside edge of base rail 51 5 8 53 11 16 31 11 16 Ø1 12 Bottom View
Page 44
44RT-SVX24K-EN Weights Notes: 1.Weights shown for air-cooled units include the following features: standard coils, 0-25% outs\ ide air, throwaway filters, low CF M supply fan, minimum motor sizes, constant volume, 460 XL, No heat. Weights shown for Evaporative condensing units include high-capacity evaporator coil and the weight of the extra structure associated with a two piece unit. 2. Weights shown represent approximate operating weights and have a + 5% accuracy. To calculate weight for a specific...
Page 45
Weights RT-SVX24K-EN45 Exhaust VFD (60-100 hp)- 295 - 295 - 295 - 295 - 295 Exhaust Fan Motor - 7.5 hp - 160160 - 160 - 160 - 160 Exhaust Fan Motor - 10 hp - 181 - 181 - 181 - 181 - 181 Exhaust Fan Motor - 15 hp - 206 - 206 - 206 - 206 - 206 Exhaust Fan Motor - 20 hp - 206 - 206 - 206 - 206 - 206 Exhaust Fan Motor - 25 hp - 358 - 358 - 358 - 358 - 358 Exhaust Fan Motor - 30 hp - 413 - 413 - 413 - 413 - 413 Exhaust Fan Motor - 40 hp - 495 - 495 - 495 - 495 - 495 Exhaust Fan Motor - 50 hp - 604 - 604 - 604...
Page 46
Weights 46RT-SVX24K-EN Cabinet Cabinet- 8097 - 8315 - 9473 - 9473 - 9473 Cabinet - 4 Blank Section - 935 - 935 - 901 - 901 - 901 Cabinet - 8 Blank Section - 1709 - 1709 - 1682 - 1682 - 1682 Control Box - Main Control Box - Main - 519 - 519 - 519 - 519 - 519 Convenience Outlet - 36 - 36 - 36 - 36 - 36 Low Ambient VFD - 57 - 57 - 57 - 57 - 57 2/3 Piece Unit Adder 2 Piece Adder- 406 - 406 - 406 - 406 - 406 3 Piece Adder - 1157 - 1157 - 1236 - 1236 - 1236 Air-Cooled Condenser Total Weight of Condenser...
Page 47
RT-SVX24K-EN47 Installation Roof Curb and Ductwork The roof curbs for units consist of two main components; a pedestal to support the unit condenser section and a “full perimeter” enclosure to support the unit air handler section. Before installing any roof curb, verify; 1. That it is the correct curb for the unit, 2. That it includes the necessary gaskets and hardware 3. That the purposed installation location provides the required clearance for proper operation. 4. ensure that the curb is level and...
Page 48
Installation 48RT-SVX24K-EN Figure 16. Pitch pocket location B1 B2 B3 A2 B1 B2 B3 A1 Pitch Pocket Pitch PocketRoof Curb 1Pc Roof Curb 2Pc Table 15. Pitch pocket dimensions (in.) One-Piece Two/Three- Piece One, Two, or Three-Piece Tonnages A1 A2 B1 B2 B3 90113.8 129.9±1 68.875 73.875 78.875 105 131.8 147.9±1 68.875 73.875 78.875 120,130,150 140.8 156.9±1 68.875 73.875 78.875 100,118,128,14 0,162 N/A 135.0±1 68.875 73.875 78.875 Figure 17. Ductwork conversion
Page 49
Installation RT-SVX24K-EN49 Field Converting Horizontal Ductwork (Supply or Return) from Right to the Left Side To field convert horizontal ductwork from right side to the left, follow this procedure: 1. Remove Panel 2 from end of unit 2. Remove the Door and Door header from the left side. 3. Assemble Door header and Door removed from the left side in the empty location on the end wall. 4. Remove Panel 1 and Post from the left side. Remove g askets from the base rail flange at the bottom. 5. Remove the...