Trane Intellipak 2 Service Manual
Here you can view all the pages of manual Trane Intellipak 2 Service Manual. The Trane manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 11
General Information RT-SVX24K-EN11 modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for economizing, mechanical cooling, heating, and ventilation. Refer to the following discussion for an explanation of each module function. Rooftop Module (RTM - Standard on all units) The rooftop Module (RTM) responds to cooling, heating, and ventilation requests by energizing the proper unit components based on information received from other unit modules, sensors, remote...
Page 12
General Information 12RT-SVX24K-EN outside air humidity sensor, and the return air temperature sensor to utilize the lowest possible humidity level when considering economizer operation. In addition, it receives space pressure information which is used to maintain the space pressure to within the setpoint control band. Refer toFigure 1 for the Humidity vs. Voltage input values. Multi Purpose Module MPM (Optional - used with Return Fan Control, Energy Recovery, and Evaporative Condensers) The MPM supports...
Page 13
General Information RT-SVX24K-EN13 Generic Building Automation System Module (GBAS - Optional used with non-Trane building control systems) The Generic Building Automation System (GBAS) module allows a non-Trane building control system to communicate with the rooftop unit and accepts external setpoints in the form of analog inputs for cooling, heating, supply air pressure, and a binary Input for demand limit. Refer to the “Field Installed Control Wiring” section for the input wiring to the GBAS module...
Page 14
General Information 14RT-SVX24K-EN Return Air Temperature Sensor An analog input device used with a return humidity sensor on CV and VAV applications when the comparative enthalpy option is ordered. It monitors the return air temperature and compares it to the outdoor temperature to establish which temperature is best suited to maintain the cooling requirements. It is mounted in the return air section and is connected to the ECEM. Leaving Evaporator Temperature Sensor An analog input device used with CV...
Page 15
General Information RT-SVX24K-EN15 remain off for a minimum of three minutes. If the LP cutout trips four consecutive times during the first three minutes of operation, the compressors on that circuit will be locked out and a manual reset diagnostic is initiated. Saturated Condenser Temperature Sensors Analog input devices used on CV and VAV applications mounted inside a temperature well located on a condenser tube bend. They monitor the saturated refrigerant temperature inside the condenser coil and...
Page 16
General Information 16RT-SVX24K-EN Morning Warm-Up—Zone Heat When a system changes from an unoccupied to an occupied mode, or switches from STOPPED to AUTO, or power is applied to a unit with the MWU option, the heater in the unit or external heat will be brought on if the space temperature is below the MWU setpoint. The heat will remain on until the temperature reaches the MWU setpoint. If the unit is VAV, then the VAV box/unocc relay will continue to stay in the unoccupied position and the VFD output...
Page 17
General Information RT-SVX24K-EN17 g. turn the supply fan “Off” h. closes the outside air damper i. turns “On” the SERVICE light at the Remote Panel j. initiates a “Low Temp Limit” diagnostic to the Human Interface Compressor Circuit Breakers The Scroll Compressors are protected by circuit breakerswhich interrupt the power supply to the compressors if the current exceeds the breakers “must trip” value. During a request for compressor operation, if the Compressor Module detects a problem outside normal...
Page 18
General Information 18RT-SVX24K-EN Space Temperature Averaging Space temperature averaging for Constant Volume applications is accomplished by wiring a number of remote sensors in a series/parallel circuit. The fewest number of sensors required to accomplish space temperature averaging is four. The Space Temperature Averaging with Multiple Sensors figure illustrates a single sensor circuit (Single Zone), four sensors wired in a series/parallel circuit (Four Zone), nine sensors wired in a series/parallel...
Page 19
General Information RT-SVX24K-EN19 Unit Control Modules Unit control modules are microelectronic circuit boards designed to perform specific unit functions. The control modules, through proportional/integral control algorithms, provide the best possible comfort level for the customer. They are mounted in the control panel and are factory wired to their respective internal components. The control modules receive and interpret information from other unit modules, sensors, remote panels, and customer binary...
Page 20
General Information 20RT-SVX24K-EN Single Zone Variable Air Volume (SZVAV) Only The IntelliPak controls platform will support Single Zone VAV as an optional unit control type in order to meetASHRAE 90.1. The basic control will be a hybrid VAV/CV configured unit that provides discharge temperature control to a varying discharge air temperature target setpoint based on the space temperature and/or humidity conditions. Concurrently, the unit will control and optimize the supply fan speed to maintain the...