Page 61
Installation RT-SVX24K-EN61 Complete Tubing and Wiring Connections as follows: Air-Cooled Tubing Connection One piece Air Cooled units are shipped with refrigerant throughout the entire tubing assemblies. Two and three piece Air-Cooled low side and condenser sections are shipped with a Nitrogen holding charge. All service valves are shipped in an open position. Additional interconnecting tubes (approx. 15-20” in length) will be supplied with the unit. Note: Field charging of 2 and 3 piece air-cooled...
Page 62
Installation 62RT-SVX24K-EN If the rise exceeds this, there is either still moisture in the system or a leak is present. 10. Charge the system per the unit nameplate field c harge.Do not add refrigerant in the suction line at this time to prevent excessive refrigerant in the low side prior to compressor startup. 11. At the liquid line angle valve add as much R-410A LIQ UID as possible. Depending on conditions, it could not be possible to add more than 60% of the field charge. This will be adequate for...
Page 63
Installation RT-SVX24K-EN63 Electric Heat Wiring Connection Important:For units with electric heat, complete tubing connections AFTER completing wiring connections. See “Tubing Connections” section. 1. Cut and remove wire ties which hold the electric control wires together, remove the shield bracket. Leave the armaflex on the hole with the control wires. 2. Cut the lowest wire tie which holds the electric heatpower wires to the vertical post on the high side. 3. Route the power wires one by one in to the...
Page 64
Installation 64RT-SVX24K-EN General Unit Requirements The checklist below is a summary of the steps required to successfully install a Commercial rooftop unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instructions called out in the applicable sections of this manual. [ ] Check the unit for shipping damage and material shortage; file a freight claim and notify Trane office. [ ] Verify that the...
Page 65
Installation RT-SVX24K-EN65 Rigging the Unit [ ] Set the unit onto the curb; check for levelness. [ ] Ensure unit-to-curb seal is tight and without buckles or cracks. [ ] Install and connect condensate drain lines to each evaporator drain connection. [ ] Remove the shipping hardware from each compressor assembly. [ ] Remove the shipping hold-down bolts and shipping channels from the supply and exhaust fans with spring isolators. [ ] Check all supply and exhaust fan spring isolators for proper...
Page 66
Installation 66RT-SVX24K-EN connections. Refer to Detail A inFigure 12, p. 25for the location of these drain connections. A condensate trap must be installed due to the drain connection being on the “negative pressure” side of the fan. Install the P-Traps at the unit using the guidelines in Figure 41. Pitch the drain lines at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a possible double- trap condition which could...
Page 67
Installation RT-SVX24K-EN67 6. Use screw gun to unscrew the two screws that hold the fan shipping bracket. The bracket should drop down but still remain engaged with a hook on the bracket. 7. Go to the other side of the unit and follow the procedure for inlet louver and door removal (see steps1-6 ). 8. Hold the bracket with one hand and remove remaining two screws. 9. Remove the bracket and all the removed screws from the unit. Important: Mak e sure there are no screws remaining in the coil area....
Page 68
Installation 68RT-SVX24K-EN O/A Sensor and Tubing Installation An Outside Air Pressure Sensor is shipped with all units designed to operate on variable air volume applications or constant volume units with 100% modulating exhaust w/ Statitrac. On VAV systems, a duct pressure transducer and the outside air sensor is used to control the discharge duct static pressure to within a customer-specified parameter. On CV & VAV units equipped with 100% modulating exhaust w/Statitrac, a space pressure transducer...
Page 69
Installation RT-SVX24K-EN69 Evaporative-Cooled Condenser Make-up Water and Drain Line Installation Make-up Water and Drain Lines Water Supply Source The supply line should be designed to provide a minimum supply of water within customary domestic supply pressures, 35 to 60 psig; dynamic pressure (measured with the valve open) which will allow approximately 30 GPM to enter the sump through the makeup water valve, when the sump is empty. The unit uses about 2-4 GPM. Attach a hand valve at the inlet for...
Page 70
Installation 70RT-SVX24K-EN Make Up Water Solenoid Valve This valve is controlled by the UCM based on water level in the sump, as well as whether a call for mechanical cooling exists. During low ambient temperatures, the solenoid valve will be de-energized preventing water from further filling sump.The sump drain valve opens to empty sump of water. Operation can be extended to 10 deg by providing an optional sump heater. Drain Valve The drain valve is shipped to “drain during power loss conditions”. If...