Page 71
Installation RT-SVX24K-EN71 Table 16. Sizing natural gas pipe mains and branches Gas Supply Pipe Run (ft) Gas Input (Cubic Feet/Hour)* 1¼ Pipe 1½ Pipe 2 Pipe 2½ Pipe 3 Pipe4 Pipe 10 1050 1600 3050 4800 8500 17500 20 730 1100 2100 3300 5900 12000 30 590 890 1650 2700 4700 9700 40 500 760 1450 2300 4100 8300 50 440 670 1270 2000 3600 7400 60 400 610 1150 1850 3250 6800 70 370 560 1050 1700 3000 6200 80 350 530 990 1600 2800 5800 90 320 490 930 1500 2600 5400 100 305 460 870 1400 2500 5100 125 275 410...
Page 72
Installation 72RT-SVX24K-EN Flue Assembly Installation 1. Locate the collapsed flue assembly in the compartment above the gas heat controls by removing the panel screws. The assembly is secured by screws up through the roof of the gas controls compartment roof. 2. Separate the pieces of the collapsed assembly. 3. Then assemble the stack as shown in Figure48. 4. Insert the tube on the flue assembly into the hole located in the vertical support for the heat section. 5. Butt both tube sections together and...
Page 73
Installation RT-SVX24K-EN73 Figure 49. Gas heat piping penetration locations K 17 8 11 5 8 W D 2.5M & 1.8M (W=16 1/8in, D=14 11/16in) 1.1M, 0.8M (W=9 15/16in, D=9 12/16in) H C 2119 20 7 16 B Horizontal gas pipe inlet Pipe type: Black pipe, sch 40 Condensate drain outlet Pipe type: cpvc Hole at the base Ø3 Unit end plane Edge of mist eliminatorTop View Side View
Page 74
Installation 74RT-SVX24K-EN General Coil Piping and Connection Recommendations Proper installation, piping, and trapping is necessary to ensure satisfactory coil operation and to prevent operational damage: Support all piping independently of the coils. Provide swing joints or flexible fittings on all connections that are adjacent to heating coils to absorb thermal expansion and contraction strains. Install factory supplied control valves (valves ship separately). Note: The contractor is responsible...
Page 75
Installation RT-SVX24K-EN75 After completing the piping connections, seal around pipe from inner panel to outer panel. Hot Water Heat Units Hot water heating coils are factory installed inside the heater section of the unit. Once the unit is set into place, the hot water piping and the factory provided three way modulating valve must be installed. The valve can be installed inside the heat section or near the unit. If the valve is installed in a remote location, use field supplied wiring to extend the...
Page 76
Installation 76RT-SVX24K-EN 7. Install a “Gate” type valve in the supply branch line as close as possible to the steam main and upstream of any other device. 8. Install a “Gate” type valve in the return branch line as close as possible to the condensate return main and downstream of any other device. 9. Install a strainer as close as possible to the inlet of the control valve and steam trap(s). 10. Steam trap selection should be based on the maximum possible condensate flow and the recommended load...
Page 78
Installation 78RT-SVX24K-EN Disconnect Switch w/External Handle Units come equipped with a factory mounted disconnect switch with an externally mounted handle.This allows the operator to disconnect power from the unit without having to open the control panel door. The handle locations and its three positions are shown below; “ON” - Indicates that the disconnect switch is closed,allowing the main power supply to be applied at the unit. “OFF” - Indicates that the disconnect switch is open, interrupting the...
Page 79
Installation RT-SVX24K-EN79 Main Unit Power Wiring Figure 56, p. 80lists the field connection wire ranges for both the main power terminal block and the optional main power disconnect switch. The electrical tables beginning with Table 22, p. 81 list the component electrical data.The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate. Refer to the “Power...
Page 80
Installation 80RT-SVX24K-EN Figure 55. Typical field power wiring Figure 56.Customer connection wire range Note:Non-fused disconnect switch size is calculated by selecting the size greater than or equal to 1.15 X (sum of unit loads). See unit literature for unit load values. (See following page for circuit breaker sizing)