Page 141
Unit Startup RT-SVX24K-EN141 Figure 94. Operating pressure curve (all comp. and cond. fans per ckt. on)—90 tons high capacity Figure 95. Operating pressure curve (all comp. and cond. fans per ckt. on)—105 tons standard capacity
Page 142
Unit Startup 142RT-SVX24K-EN Figure 96. Operating pressure curve (all comp. and cond. fans per ckt. on)—105 tons high capacity Figure 97. Operating pressure curve (all comp. and cond. fans per ckt. on)—120 tons standard capacity
Page 143
Unit Startup RT-SVX24K-EN143 Figure 98. Operating pressure curve (all comp. and cond. fans per ckt. on)—120 tons high capacity Figure 99. Operating pressure curve (all comp. and cond. fans per ckt. on)—130 tons standard capacity
Page 144
Unit Startup 144RT-SVX24K-EN Note:Due to the variable speed fans on evaporative condenser units, typical operating pressure curves are not relevant. If operating pressures at certain conditions are needed, contact a local Trane sales representative. Figure 100. Operating pressure curve (all comp. and cond. fans per ckt. on)—130 tons high capacity Figure 101. Operating pressure curve (all comp. and cond. fans per ckt. on)—150 tons standard capacity
Page 145
Unit Startup RT-SVX24K-EN145 Components Standard Unit without Energy Recovery Wheel Economizer Damper Adjustment Exhaust Air Dampers Verify that the exhaust dampers (if equipped) close tightly when the unit is off. Adjust the damper linkage as necessary to ensure proper closure. An access panel is provided under each damper assembly. Outside Air & Return Air Damper Operation The outside air and return air damper linkage is accessible from the filter section of the unit. The damper linkage connecting the...
Page 146
Unit Startup 146RT-SVX24K-EN measure the return static pressure at the location determined in step 1. 9. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation. 10. Open the field supplied main power disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the “Open” position while working on the dampers. Note: Gravity will cause the damper to close. Support or secure the damper blades while removing the actuator to prevent unexpected...
Page 147
Unit Startup RT-SVX24K-EN147 Figure 103. Outside air and return air economizer assembly (w/TRAQ™ dampers) TRAQ Damper Linkage Top view Jackshaft TRAQ damper
Page 148
Unit Startup 148RT-SVX24K-EN Standard Unit with Energy Recovery Wheel Economizer Damper Adjustment - ERW units Outside & Return Air Damper Operation The outside air and return air damper actuators are accessible through from the filter section of the unit. The outside air and return air dampers have individual actuators that are linked electronically. The actuators are preset to 0 degrees from the factory. Refer to Table 44, p. 150 for the appropriate actuator position for the unit and operating airflow...
Page 149
Unit Startup RT-SVX24K-EN149 6. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec. screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice. 7. Press the TEST START key to start the test. Rememberthat the delay designated in step 6 must elapse before the fan...
Page 150
Unit Startup 150RT-SVX24K-EN Table 44. Standard units with ERW — field measured plenum pressureLow CFM ERW — 90-162 Tons 90/100 Ton Low CFM ERW - Field measured plenum pressure (inches wc) OA Actuator Reading [Degrees] RA Actuator Reading [Degrees] 60 50 40 30 20 10 0 10 20 30 35 40 45 50 CFM Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T E/T 16000 1.29 — 0.87 1.52 0.71 1.05 0.64 0.84 0.60 0.64 0.58 0.63 0.46 0.45 0.43 0.41 0.38 0.35 0.32 0.20 20000 1.99 — 1.34...