Page 181
Service and Maintenance RT-SVX24K-EN181 Fan Belt Adjustment The supply fan belts and optional exhaust fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length. When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base. Once the new belts are...
Page 182
Service and Maintenance 182RT-SVX24K-EN 2. Set the large O-ring on the belt tension gauge at the deflection value determined in Step 1b. 3. Set the small O-ring at zero on the force scale of the g auge plunger. 4. Place the large end of the gauge at the center of the belt span; then depress the gauge plunger until the large O- ring is even with the top of the next belt—-or even with a straightedge placed across the fan and motor sheaves. See Table59, p. 183. 5. Remove the belt tension gauge. The small...
Page 183
Service and Maintenance RT-SVX24K-EN183 Scroll Compressor Replacement The compressor manifold system was purposely designed to provide proper oil return to each compressors. The refrigerant manifold system must not be modified in any way. Note: Altering the compressor manifold piping may cause oil return problems and compressor failure. Should a compressor replacement become necessary and a suction line filter drier is to be installed, install it a minimum of 18 inches upstream of the oil separator tee....
Page 184
Service and Maintenance 184RT-SVX24K-EN VFD Programming Parameters Units shipped with an optional variable frequency drive (VFD) are preset and run tested at the factory. If a problem with a VFD occurs, ensure that the programmed parameters listed inTable 60, p. 185have been set before replacing the drive. Note: Check to make sure that parameter 1-23 is set to 60 Hz.To check parameter 1-23 press the [Main Menu] button (press [Back] button if the main menu does not display), use the [▼] button to scroll...
Page 185
Service and Maintenance RT-SVX24K-EN185 g. Ensure parameter 14-22 Operation Mode has reverted back to “Normal Operation”. Notes: Item 5 resets the drive to the default factory settings. The program parameters listed in Table 60, p. 185will need to be verified or changed as described in Item 3 and 4. Some of the parameters listed in the Table are motor specific. Due to various motors and efficiencies available, use only the values stamped on the specific motor nameplate. Do not use the Unit nameplate...
Page 186
Service and Maintenance 186RT-SVX24K-EN [ ] Verify that all damper linkages move freely; lubricate with white grease, if necessary. [ ] Check supply fan motor bearings; repair or replace the motor as necessary. [ ] Check the fan shaft bearings for wear. Replace the bearings as necessary. [ ] Lubricate the supply fan shaft bearings with a lithium based grease. Refer to Table57, p.181for recommended greases. Note: The bearings are manufactured using a special synthetic lithium based grease designed...
Page 187
Service and Maintenance RT-SVX24K-EN187 [ ] Open the main gas valve and apply power to the unit heating section; then initiate a “Heat” test using the startup procedure described in “Gas Furnace Startup”. [ ] Verify that the ignition system operates properly. Air-Cooled Coil Cleaning Regular coil maintenance, including annual cleaning enhances the unit operating efficiency by minimizing: – compressor head pressure and amperage draw; – water carryover; – fan brake horsepower; and, – static pressure...
Page 188
Service and Maintenance 188RT-SVX24K-EN c. Spray the solution perpendicular (at 90 degrees) to the coil face. d. For evaporator and reheat coils, maintain a minimum clearance of 6 between the sprayer nozzle and the coil. For microchannel condenser coils, optimum clearance between the sprayer nozzle and the microchannel coil is 1-3”. 6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. For evaporator and reheat coils, allow the cleaning solution to stand on the...
Page 189
Service and Maintenance RT-SVX24K-EN189 different times of the year. The sump water clarity should be checked periodically. The evaporative condenser has several design features to reduce the possibility of biological growth in the sump. These features include: air inlets constructed to eliminate direct sunlight in the sump The sump flush sequence replenishes the sump with fresh water 1 to 12 times per day depending on the flush setting The copper tubing in the coils is a natural biocide Important:...
Page 190
Service and Maintenance 19 0RT-SVX24K-EN Final Process Record the unit data in the blanks provided. Table 61. Evaporative Condenser Models—Maintenance and Troubleshooting Maintenance Schedule Component Action Frequency Comments Fan Motor None Required Non-grease bearings Sump Pump Inspect / Clean 1 – 2 times per year Clean inlet openings to pump Sump Inspect / Clean 1 – 2 times per year depending on water hardness and unit run time Sump can be drained and hosed out using hose bib...