Page 161

Unit Startup
RT-SVX24K-EN161
8. Tighten the set screw to the drive shaft.
9. Stretch the belt over the pulley and engage it in the
groo
 ve.
Compressor Startup
1. Ensure that the “System” selection switch at theremote panel is in the “Off” position.
2. Before closing the disconnect switch, ensure that the compressor
 discharge service valve and the liquid line
service valve for each circuit is back seated.
3. Close the disconnect switch or circuit protector switch that provides the supply power to the...

Page 162

Unit Startup
162RT-SVX24K-EN
3. UseTable37, p.11 2to program the following system
components for the number 1 refrigeration circuit by
scrolling
 through the displays;
Supply Fan (On)
VFD
 (100%, if applicable)
OCC/UNOCC Relay (Unoccupied for VAV units)
All Compressors for each circuit (On) Condenser Fans for each circuit (On)
4. Once the configuration for the components is complete,
 press the NEXT key until the LCD displays
the “Start test in __Sec.” screen. Press the + key to
designate the delay...

Page 163

Unit Startup
RT-SVX24K-EN163
Evaporative Condenser Startup
Important:Water treatment by a qualified water
treatment expert is required to ensure
proper equipment life and product
performance. Dolphin Water Care™ is an
option offered by Trane that is NOT a
subsitute for regular water treatment by a
qualified water treatment professional. If a
water treatment system is not operating on
the unit, do not proceed.
Startup for evaporative and air-cooled condensers is
initially the same. In addition, the...

Page 164

Unit Startup
164RT-SVX24K-EN
Figure 113. Fan shipping bracket removal
Mist Eliminator
Fan Shipping Bracket ScrewsFan Shipping Bracket
Access Doors
Inlet Louvers
Actuator Side
Figure 114. Float bracket setting
Fill sump so float shuts 
off when water is within these slots 

Page 165

Unit Startup
RT-SVX24K-EN165
Thermostatic Expansion Valves
The reliability and performance of the refrigeration system
is heavily dependent upon proper expansion valve
adjustment.Therefore, the importance of maintaining the
proper superheat cannot be over emphasized.
On air-cooled units, the expansion valves shipped
installed were factory set to control between 14-18°F at the
ARI full load rating conditions (approximately 45°/125°F saturated suction/discharge). On evaporative condenser
units, the...

Page 166

Unit Startup
166RT-SVX24K-EN
Electric, Steam and Hot Water Startup
(Constant Volume & Variable Air Volume
Systems)
1. Ensure that the “System” selection switch at the
remote panel is in the “Off” position.
2. Close the disconnect switch or circuit protector switchthat provides the supply power to the unit terminal
block or the unit mounted disconnect switch.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
UNIT
 DISCONNECT SWITCH.
3. Turn the 115 volt control circuit switch and the 24 volt control
 circuit...

Page 167

Unit Startup
RT-SVX24K-EN167
monoxide, and a steady flame that minimizes nuisance
shutdowns.
Two Stage Gas Furnace
High-Fire Adjustment
1. UseTable 37, p. 112 to program the following system
components for operation by scrolling through the
Human Interface displays;
Gas Heat
Supply Fan (On)
Return Fan (On, if supplied)
Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied)
Heat Stages1&2(On)
Turn the 115 volt control circuit switch 4S24 located in the heater control panel...

Page 168

Unit Startup
168RT-SVX24K-EN
for the required manifold pressure during low-fire
operation. If it needs adjusting, remove the cap
covering the low-fire adjustment screw on the gas
valve. Refer toFigure118, p.169for the adjustment
screw location. Turn the screw clockwise to increase
the
 gas pressure or counterclockwise to decrease the
gas pressure. Note:
Do
not adjust the combustion air damper while
the furnace is operating at low-fire.
4. Check the carbon dioxide levels after each adjustment.
5. Press...

Page 169

Unit Startup
RT-SVX24K-EN169
Full Modulating Gas Furnace
Full Modulating gas heaters are available for the 850, 1100,
1800, 2500 MBH heater sizes.
– The firing rate of the 850 MBH modulating heatercan vary from 10% to 100% of the 850 MBH.
– The firing rate of the 1100, 1800 and 2500 MBH can vary from 5% to 100% of its nameplate value.
Heat Exchanger
The heat exchanger drum, tubes and front and rearheaders are constructed from stainless steel alloys.
Unit Control
The unit is controlled by a supply air...

Page 170

Unit Startup
170RT-SVX24K-EN
Note:The burner capacity is controlled by the movement
of the air damper. This has been preset at the
factory and normally does not need field
adjustment. The combustion quality (air/gas) is
controlled by the setup of the air damper and
butterfly valve linkage relationship.
7. Use Table37, p.11 2to program the minimum (5%)
firing rate. Allow the system to operate for
appro
 ximately 10 minutes.
8. Use a carbon dioxide analyzer and measure the percentage
 of carbon dioxide in...