Home > Siemens > Communications System > Siemens Saturn Iie Epabx General Description Manual

Siemens Saturn Iie Epabx General Description Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Siemens Saturn Iie Epabx General Description Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 428 Siemens manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							SATURN IIE EPABX 
    Maintenance and Troubleshooting 
    - 
    A30808-X5130-DllO-l-8920 
    Issue 1, May 1986 
    Table 4.05 Allowable Voltage Ranges 
    MODULE/OUTPUT NOMINAL VOLTAGE 
    VOLTAGE RANGE CONNECTOR-PIN 
    LTUPS 
    l + 5Vdc 
    + 4.9 tp + 5.2 Jl-2, -3, -12, -13 
    (if system is equipped + 12Vdc 
    +11.3 to +12.7 Jl-1, -11 
    with LTU shelf(s)) -12Vdc -11.3 to -12.7 Jl-5, -15 
    - 5Vdc - 4.9 to - 5.2 Jl-4, -14 
    PSU - 5Vdc - 4.9 to - 5.2 JlO-1 
    + 5Vdc 
    l * * + 4.9 to f 5.2 J9-1, -2, -3, 
    :4; Jll-1, -2; 
    J6-3 
    + 12Vdc +11.3 to -1-12.7 JlO-10, -11; 
    Jll-4, -5; 
    J6-6 
    -12Vdc -11.3 to -12.7 JlO-12 
    MSM 
    l (+5MEM/+5B) + 5Vdc l * + 4.9 to + 5.3 JlO-3 
    RGEN 
    9OVac (RMS) @ 20Hz 75.0 to 100.0 (Not directly measurable) 
    RACIRMW 9OVac (RMS) @ 20Hz See Figure 2.12 J7-6 to Basic Shelf, J7-7 
    (for 2 seconds) to LTU Shelf 1: J8-7 to 
    +97Vdc (for 1 second) LTU Shelf 2: J8-8 to 
    alternating 
    LTU Shelf 3’ 
    -48PS0 
    -488 
    -48Vdc -43.0 to -53.0 J2-1 
    -48P -48Vdc -43.0 to -53.0 J2-3 
    -48PSl * (if an Expansion 
    Cabinet is included) 
    -488 -48Vdc -43.0 to -53.0 J2-1 
    -48P -48Vdc -43.0 to -53.0 
    J2-3 
    * Optional. 
    l * If optional MSM is installed, PSU +5 Vdc output must be adjusted to 50 millivolts below +5MEM/+5B output provided 
    by MSM (with memory PCBs installed). Adjustment (+5 V ADJUST) is accessible through PSU front panel (refer to 
    Figure 2.01). 
    (a) Replace the fuse. (c) Replace the fuse again. 
    (b) If the fuse blows again, replace the PSU. (If op- 
    tional MSM is installed, adjust PSU +SVdc out- 
    put versus MSM output as specified in Table 
    4.05.) 
    4. If an RAC fuse has blown, 
    NOTE: If it is known or believed that a previous 
    event or or action by the craftsperson may 
    have caused a transient fault condition 
    which caused the fuse to blow, proceed to 
    step (a) below; otherwise proceed to step 
    (b) below. (1) If the fuse does not blow, a subscriber line 
    module (SLMA-0, SLMA-S, or SLAl6 PCB) 
    is at fault. Reinsert the subscriber line mod- 
    ules in the shelf, one at-a-time and recheck 
    the fuse after each module is inserted. If the 
    fuse blows after reinserting a module, the 
    module is defective. Replace the module. 
    (2) If the fuse blows again, the most probable 
    location of the fault is the PSU. Replace the 
    PSU. (If optional MSM is installed, adjust 
    PSU +SVdc output versus MSM output as 
    specified in Table 4.05.) 
    (a) Replace the fuse. If the fuse blows again, pro- 5. 
    ceed to step (b) below. If a circuit breaker has tripped to the off (down) po- 
    sition, 
    (b) Remove all subscriber line modules (SLMA-0, 
    SLMA-S, or SLA16 PCBs) in the associated 
    shelf. Do not remove the PIMD, SLMD, DTMF, 
    trunk (TMBA-2, TMBA-4, TMBM, or TMIE 
    PCBs) or common control (CE PCBs) modules 
    in the shelf. (a) Switch the circuit breaker to the on (up) position. 
    (1) If the circuit breaker does not trip to off im- 
    mediately, continue to observe it for a period 
    of time to determine that it remains on. 
    Also, check system for proper performance 
    4-19  
    						
    							A30808-X5130-DIIO-l-8920 
    Issue 1, May 1986  SATURN IIE EPABX 
    Maintenance and Troubleshootrng 
    (b) If the circuit breaker trips off (down) again, 
    switch it on again. 
    (1) If the circuit breaker does not trip to off im- 
    mediately, continue to observe it for a peri- 
    od of time to determine that it remains on. 
    Also, check system for proper performance. 
    (2) If the circuit breaker trips off again, replace 
    the associated power supply as indicated 
    below: 
    BASIC PS circuit breaker: replace the PSU. 
    (If optional MSM is installed, adjust PSU 
    +SVdc output versus MSM output as 
    specified in Table 4.05.) 
    LTUPSO circuit breaker: replace the LTUPS 
    on LTU Shelf 1. 
    LTUPSl circuit breaker: replace the LTUPS 
    on LTU Shelf 2 in the Expansion Cabinet. 
    LTUPS2 circuit breaker: replace the LTUPS 
    on LTU Shelf 3 in the Expansion Cabinet. 
    -48PSO circuit breaker: replace -48PSO. 
    -48PSl circuit breaker: replace -48PSl. 
    (3) If the circuit breaker trips off again, the most 
    probable location of the fault is the PSU. 
    Replace the PSU. (If optional MSM is in- 
    stalled, adjust PSU +SVdc output versus 
    MSM output as specified in Table 4.05.) 
    b. If the fuses and circuit breakers are normal but all LEDs 
    on the cabinet(s) are extinguished (i.e., no calls are be- 
    ing processed), perform the following voltage checks: 
    1. Check the ac input voltage to the Basic Cabinet: 
    (a) Connect one lead of the DVM to pin 1 and the 
    other lead to pin 3 of connector Pl (connected 
    to Jl) on the rear panel of the PSU (refer to Figure 
    4.00). Be careful not to damage the connector 
    housing or contacts. 
    (b) If ac voltage is measured, replace the PSU. (If 
    optional MSM is installed, adjust PSU +5Vdc 
    output versus MSM output as specified in Table 
    4.05.) 
    (c) If no ac voltage is measured, check the ac vol- 
    tage at the ac power source outlet. 
    (1) If no ac voltage is measured, commercial 
    power is not being supplied to the SATURN 
    System. 
    (2) If the ac voltage is correct at the ac power 
    source outlet, check power cable and con- 
    nections in cabinet junction box (refer to 
    Figure 4.01). 
    2. To check the ac input to a particular -48PS module, 
    (a) Connect one DVM lead to pin 1 and the other 
    lead to pin 2 of the plug mated to connector Jl 
    4-20 on the -48PS module (refer to Figure 4.01). Be 
    careful not to damage the plug housing or 
    contacts. 
    (b) If no ac voltage is measured, replace the PSU. 
    (If optional MSM is installed, adjust PSU +5Vdc 
    output versus MSM output as specified in Table 
    4.05.) 
    3. Check the dc output voltages from the PSU (+5V, 
    SV, +12V and -12V) appearing at connectors J47 and 
    J48 on the Basic Shelf backplane (refer to Figure 
    4.02). For each voltage shown in Figure 4.02, con- 
    nect the common (-) DVM lead to the ground bus- 
    bar and insert the positive (+) DVM lead into the 
    associated wire slot of the wiring harness plug. Be 
    careful not to damage the plug housing or contacts. 
    (a) If only one output voltage from the PSU to the 
    Basic Shelf backplane is low (refer to Table 4.05 
    for the acceptable voltage ranges), suspect that 
    excessive current load on that output is causing 
    current foldback protection to be in effect. This 
    may be due to a short circuit or partial short cir- 
    cuit in a PCB installed in the Basic Shelf or the 
    PSU may be defective. To isolate the fault, pro- 
    ceed as follows: 
    (1) 
    (2) 
    (3) Remove all PCBs in the Basic Shelf and 
    recheck the incorrect voltage. 
    If the voltage remains low, replace the PSU. 
    (If optional MSM is installed, adjust PSU 
    +5Vdc output versus MSM output as speci- 
    fied in Table 4.05.) 
    If the voltage returns to normal after remov- 
    ing all PCBs in the Basic Shelf, a PCB is 
    probably at fault. Reinsert the PCBs in the 
    shelf, one at-a-time and recheck the voltage 
    after each PC8 is inserted. If the incorrect 
    voltage reading returns after inserting a PCB, 
    the PCB is defective. Replace the PCB. 
    (b) If all PSU output voltages are low as measured 
    at the Basic Shelf, the PSU may have ex- 
    perienced an overvoltage condition at its output 
    which caused the overvoltage protection circuitry 
    to latch the PSU into a shut down mode. This 
    may be due to a short,circuit or partial short cir- 
    cuit between two output voltages. When a short 
    circuit is cleared, it is necessary to switch the 
    BASIC PS circuit breaker on the PSU to off 
    (down), then on (up) again, to clear the latched 
    shut down condition. To isolate the faulty equip- 
    ment proceed as follows: 
    (1) Remove all PCBs from the Basic Shelf 
    (2) Switch the associated BASIC PS circuit 
    breaker on the PSU to off (down), then on 
    (up) again. Check the PSU output voltages 
    once again at the Basic Shelf. If the voltages 
    remain low, replace the PSU. flf ootional 
    MSM is installed, adjust PSU +5Vdcbutput 
    versus MSM output as specified in Table 
    4.05)  
    						
    							SATURN IIE EPABX 
    A30808-X5130-DllO-l-8920 
    Maintenance and Troubleshooting 
    Issue 1, May 1986 
    Jg,(I, j-J11w
    						
    							SATURN IIE EPABX 
    A30808-X5130-DllO-l-8920 
    Maintenance and Troubleshooting 
    issue 1, May 1986 
    I J2/P2 
    Pin 
    1 -48Vdc (-488) 
    2 Ground 
    3 -48Vdc (-48P) 
    4 Ground Jl/Pl 
    Junction LINE-AC IN 
    LINE AC IN 
    Pin 
    Box (AC%@ IN) 
    (AC#l IN) 
    1 AC Line 
    Note 2 
    2 AC Neutral 
    3 AC Ground 
      -48PSo 
    Note 1 PSU J2 
    Notes: 
    1. When -48PSl is installed, voltages on connectors Jl and J2 are the same as 
    those on -48PSfi.  
    2. Second AC input is required only when expansion cabinet is used and -48$PSl 
    is installed. Jumper plug at PSU J2 is removed and second AC source is connected 
    to J2. 
    Figure 4.01 -48PSO Module Power Connections 
    4-22  
    						
    							SATURN IIE EPABX 
    Maintenance and Troubleshooting A30808-X5130-DllO-l-6920 
    Issue 1, May 1986 
    (3) If the voltages return to normal after remov- 
    ing all the PCBs, a PCB has probably short- 
    ed. Reinsert the PCBs in the shelf, one at 
    a time, and recheck the the PSU output vol- 
    tages at the Basic Shelf after each PCB is 
    inserted. If the low voltage readings return 
    after inserting a PCB, the PCB is defective. 
    Replace the PCB. 
    (c) If all output voltages from the PSU are zero and 
    ac is applied to the input, switch off all PSU cir- 
    cuit breakers and replace the PSU. (If optional 
    MSM is installed, adjust PSU +SVdc output ver- 
    sus MSM output as specified in Table 4.05.) 
    c. If PSU circuit breakers and fuses are normal and the sys- 
    tem is processing some calls (i.e., status indicators on 
    the CIOP PCB are decrementing), check appropriate vol- 
    tages for the shelf or shelves experiencing problems. If 
    problems appear to be in the Basic Shelf, check dc in- 
    put voltages to the shelf. If problems appear to be in an 
    LTU shelf, check the ac input voltage to the shelf LTUPS 
    then check the dc output voltages provided by the 
    LTUPS. 
    To check the ac input to a particular LTUPS, 
    1. Connect one lead of the DVM to pin 1 and the other 
    lead to pin 2 of the LTUPS ac input connector on 
    the raceway (refer to Figure 4.03). Be careful not to 
    damage the connector housing or contacts. 
    2. If no ac voltage is measured, replace the PSU. (If 
    optional MSM is installed, adjust PSU +5Vdc out- 
    put versus MSM output as specified in Table 4.05.) 
    d. If the ac input voltage to the LTUPS is correct, check the 
    dc output voltages from the associated LTUPS module. 
    The LTUPS output voltages can be checked at connec- 
    tor Jl on the LTUPS and at connectors J42, J43, and 
    J44 on the LTU shelf backplane. To check the output vol- 
    tages, refer to Figure 4.03 for the location of the connec- 
    tor on the rear of the LTUPS and Figure 4.04 for the 
    locations of connectors J42, J43, and J44 on the LTU 
    shelf backplane. For each voltage indicated in Figures 
    4.03 and 4.04, connect the common (-) DVM lead to the 
    ground busbar and insert the positive (+) DVM lead in 
    the associated wire slot of the connector. Be careful not 
    to damage the connector housings or contacts. 
    1. If only one output voltage is low (refer to Table 4.05), 
    suspect that excessive current load on that output 
    is causing current foldback protection to be in effect. 
    This may be due to a short circuit or partial short 
    circuit within a PCB installed in the shelf, or the 
    LTUPS module may be at fault. To isolate the faulty 
    equipment proceed as follows: NOTE: If the +5Vdc is low, the voltage can be in- 
    creased by turning the +5 V ADJUST 
    potentiometer on the front of the LTUPS 
    clockwise. 
    (4 
    (b) 
    w 
    2. Remove all PCBs in the LTU shelf and check the 
    voltage again. 
    If the voltage is still low, replace the LTUPS 
    module. 
    If the voltage returns to normal after removing 
    all the PCBs, a PCB has probably shorted. 
    Reinsert the PCBs into the shelf, one at a time. 
    Check whether the low voltage returns after in- 
    serting each PCB. If the low voltage returns af- 
    ter inserting a PCB, the PCB is defective. 
    Replace the PCB. 
    If all output voltages from the LTUPS module are 
    low, suspect that the LTUPS module has ex- 
    perienced an overvoltage condition at its output 
    which has caused the overvoltage protection cir- 
    cuitry to latch the LTUPS into a shut down mode. 
    This may be due to a short circuit or partial short 
    circuit between two output voltages. When the 
    short circuit is cleared, it will be necessary to switch 
    the associated LTU shelf input circuit breaker OFF 
    and then ON to clear the “latched shut down con- 
    dition.” 
    (a) Remove all PCBs in the LTU shelf. 
    (b) Switch the LTU circuit breaker on the PSU mod- 
    ule off and then ON to determine if the shut 
    down condition is cleared. 
    (c) Check the LTUPS output voltages again. 
    (1) If the voltages are still low, replace the 
    LTUPS module. 
    (2) If the voltages return to normal after remov- 
    ing all the PCBs, the latched shut down 
    condition has cleared, indicating that a 
    PCB has probably shorted. To determine 
    which PCB(s) is defective, reinsert the 
    PCBs into the shelf, one at a time. After in- 
    serting each PCB, again check the output 
    voltages of the LTUPS module. If the low 
    voltages return after inserting a PCB, the 
    PCB is defective. Replace the PCB. 
    (3) If all output voltages from the LTUPS mod- 
    ule are zero and there is ac input to the 
    module, replace the LTUPS module. 
    4-23  
    						
    							A30808-X5130-DllO-l-8920 
    Issue 1, May 1986 
    El 
    +5Vdc 
    J46IP46 
    Pin 
    1 RAC/RMW 
    2 Ground 
    3 -48Vdc 
    (-48P) 
    J47IP47 
    Pin 
    1 -5Vdc 
    2 -48Vdc 
    (-488) 
    3 Ground 
    4 Ground 
    E2 
    + 5Vdc 
    J48lP48 
    Pin 
    1 -12Vdc - 
    2 +12Vdc 
    3 +12Vdc 
    4 Ground 
    5 +5Vdc (a5B) 
    ’ E3 
    -i- 5Vdc 
    ’ E4 
    +5Vdc 
    Figure 4.02 Basic Shelf Backplane Power Connections  
    						
    							I 
    SATURN IIE EPABX 
    Maintenance and Troubleshooting A30808-X5130-DllO-l-8920 
    Issue 1, May 1986 
    Raceway 
    PI 
    Pin 
    1 AC Line 
    2 AC Corn1 
    3 GND nor 
    Jl 
    Pin 
    Pin Pin 
    1 +12v 6 RET 11 +12v 
    2 +5v 7 RET 12 +5v 
    3 +5v 8 Keying Plug 13 +5V 
    4 -5v 9 RET 14 -5v 
    5 -12V 10 RET 15 -12v 
    Figure 4.03 LTUPS Module Power Connections 
    4-25  
    						
    							SATURN IIE EPABX 
    Maintenance and Trouhleshootlng 
    J42 
    Pin 
    1 -k5v 
    2 RING 
    S GND 
    4 -48P 
    5 -5v 
    J43 
    Pin 
    1 GND 
    2 -488 
    3 +5v 
    4 +12v 
    5 -12v 
    ’ J44 
    Pin 
    1 GND 
    2 +5v 
    3 +5v 
    4 GND AC (+-5Vdc) 
    (RAC/RMV 
    (Ground) 
    (Ground) 
    (-48Vdc) 
    (+SVdc) 
    (Ground) 
    V) ! 
    Figure 4.04 LTU Shelf Backplane Power Connections 
    4-16  
    						
    							I 
    _-. 
    SATURN IIE EPABX 
    Maintenance and Troubleshooting 
    4.07 Single-Line Telephone Related Failures. Step-by-step 
    instructions for troubleshooting the single-line telephone (SLT) 
    (i.e., 500-or 2500-type analog instrument) are provided below: 
    a. If the SLT is completely inoperative (i.e., no talk battery), 
    1. Using the SERVICE CMU Procedure, check serv- 
    ice state of the circuit serving this SLT 
    (a) If in-service, continue with step 2. 
    (b) If out-of-service-craft, return the circuit to the 
    in-service state (Table 4-10) and verify opera- 
    tion. Continue with step 2 if the SLT remains 
    inoperative. 
    (c) If out-of-service - automatic, attempt to return 
    the circuit to the in-service state (Table 4-10). 
    (1) If circuit returns to the in-service state and 
    the failure clears, the problem was tran- 
    sient. If transient problems recur on the 
    same circuit, continue with step 2. 
    (2) If the circuit remains in the out-of-service 
    - automatic state, continue with step 2. 
    2. Using the ALMDATA CMU Procedure, check the 
    Failure History Memory for system alarm mes- 
    sages. The corrective repair procedures for system 
    alarm messages are provided in Table 4.02. 
    3. If more than one SLT fails at the same time, 
    (a) If all affected SLTs are assigned to the same sub- 
    scriber line module (SLMA-C, SLMA-S, or %A16 
    PCB) replace the subscriber line module. 
    (b) Replace the SMXTG PCB 
    4. If only one SLT fails, 
    (4 Check the line with a test set or replace the SLT 
    with a known good SLT. If the problem disap- 
    pears, replace the faulty SLT. 
    UN Replace the associated subscriber line mod- 
    ule (SLMA-0, SLMA-S, or %A16 PCB). 
    (4 Replace the SMXTG PCB. 
    b. If the SLT rings continuously, 
    1. Replace the associated subscriber line module 
    (SLMA-0, SLMA-S, or SLAl6 PCB). 
    c. If dial tone cannot be heard, 
    1. Using the SERVICE CMU Procedure, check serv- 
    ice state of the circuit serving this SLT. 
    (a) If in-service, continue with step 2. 
    (b) If out-of-service - craft, return the circuit to the 
    in-service state (Table 4-lo), and verify opera- 
    tion. Continue with step 2 if the SLT remains 
    inoperative. A30808-X5130-DllO-l-8920 
    Issue 1. May 1986 
    (c) If out-of-service - automatic, attempt to return 
    the circuit to the in-service state (Table 4-10). 
    (1) If circuit returns to the in-service state and 
    the failure clears, the problem was tran- 
    sient. If transient problems recur on the 
    same circuit, continue with step 2. 
    (2) If the circuit remains in the out-of-service 
    - automatic state, continue with step 2. 
    2. Using the ALMDATA CMU Procedure, check the 
    Failure History Memory for system alarm mes- 
    sages. The corrective repair procedures for system 
    alarm messages are provided in Table 4.02. 
    3. If dial tone cannot be heard at more than one SLT, 
    (4 
    04 
    (cl If all affected SLTs are assigned to the same 
    subscriber line module (SLMA-0, SLMA-S, or 
    SLA16 PCB), replace the associated subscriber 
    line module. 
    Perform the Tone Generator Test (Table 4.06). 
    If the Tone Generator Test passes but the failure 
    still persists, replace the associated SMXTG 
    PCB. 
    4. If dial tone cannot be heard on one SLT only, 
    (a) Check line.with a test set or replace the SLT 
    with a known g,ood SLT. If the problem disap- 
    pears, replace the faulty SLT. 
    (b) Replace the associated subscriber line mod- 
    ule (SLMA-0, SLMA-S, or SLAl6) PCB. 
    d. If dial tone is distorted or at a low level, 
    1. 
    2. If dial tone is distorted or at a low level on only one 
    SLT, replace the SLT with a known good SLT. 
    If dial tone is distorted or at a low level on more 
    than one SLT. 
    (a) 
    (b) 
    (cl Perform the Tone Generator Test (Table 4.06). 
    If the Tone Generator Test passes but the failure 
    still persists, replace the associated PSC PCB 
    and recheck dial tone. (PSCO for Basic Cabi- 
    net; PSCl for Expansion Cabinet, if applicable.) 
    If failure persists, reinsert original PSC PCB 
    and replace the MCA PCB. 
    e. If the SLT dial pad is suspected of being faulty, per- 
    form the DTMF Dial Pad Test (Table 4.12). 
    f. If the SLT fails to ring, 
    1. Using the SERVICE CMU Procedure, check serv- 
    ice state of the circuit serving this SLT, 
    (a) If in-service, continue with step 2. 
    (b) If out-of-service-craft, return the circuit to the 
    4-27  
    						
    							SATURN IIE EPABX 
    Maintenance and Troubleshooting 
    I ’ 
    A30808-X5130-DllO-l-8920 
    Issue 1, May 1986 
    in-service state (Table 4-lo), and verify opera- 
    tion. Continue with step 2 if the SLT remains 
    inoperative. 
    (c) If out-of-service - automatic, attempt to return 
    the circuit to the in-service state (Table 4-10). 
    (1) If circuit returns to the in-service state and 
    the failure clears, the problem was tran- 
    sient. If transient problems recur on the 
    same circuit, continue with step 2. 
    (2) If the circuit remains in the out-of-service 
    - automatic state, continue with step 2. 
    2. Using the ALMDATA CMU Procedure, check the 
    Failure History Memory for system alarm mes- 
    sages. The corrective repair procedures for system 
    alarm messages are provided in Table 4.02. 
    3. Perform the Station Line Test (Table 4.13) to verify 
    ringing capability. 
    4. Verify that the problem is not due to the activation 
    of a SATURN feature (e.g., Do Not Disturb, Call For- 
    warding, etc.). 
    5. Replace the SLT with a known good SLT. If the 
    problem is corrected, replace the faulty SLT. 
    6. Replace the associated subscriber line module 
    (SLMA-0, SLMA-S, or SLA16) PCB. 
    4.08 Attendant Console Related Failures. Step-by-step in- 
    structions for troubleshooting the attendant console are 
    provided below: 
    a. If the console is completely inoperative (i.e., no dial 
    tone, no audible alerting, no functioning buttons and 
    LED indicators), 
    1. Using the SERVICE CMU Procedure, check serv- 
    ice state of the circuit serving this console. 
    (a) If in-service, continue with step 2. 
    (b) If out-of-service - craft, return the circuit to the 
    in-service state (Table 4-10) and verify opera- 
    tion. Continue with step 2 if the console re- 
    mains inoperative. 
    (c) If out-of-service - automatic, attempt to return 
    the circuit to the in-service state (Table 4-10). 
    (1) If circuit returns to the in-service state and 
    the failure clears, the problem was tran- 
    sient. If transient problems recur on the 
    same circuit, continue with step 2. 
    (2) If the circuit remains in the out-of-service 
    - automatic state, continue with step 2. 
    2. Using the ALMDATA CMU Procedure, check the 
    Failure History Memory for system alarm mes- 
    sages. The corrective repair procedures for system 
    alarm messages are provided in Table 4.02. 
    3. Verify that the line cord is properly seated in the modular jacks. One end of the line cord plugs into 
    the rear base of the console and the other end con- 
    nects to the modular connecting block. Also insure 
    that the handset cord is properly seated in the 
    handset console jacks. 
    4. Replace the associated PIMD PCB. 
    5. Replace the console with a known good console. 
    If the problem is corrected, replace the faulty 
    console. 
    b. If static is heard in the handset, 
    1. Replace the handset. 
    2. Replace the handset coiled cord. 
    3. Replace the associated PIMD PCB. 
    4. Replace the console with a known good console. 
    If the problem is corrected, replace the faulty 
    console. 
    c. If the console is not operating properly (i.e., nonfunc- 
    tioning LED(s), button(s), alphanumeric display, audi- 
    ble alerting device, etc.): 
    1. Perform the Attendant Console Test (refer to Table 
    4.14). 
    2. If theAttendant Console Test passes but the failure 
    persists, 
    (a) Replace the associated PIMD PCB. 
    (b) Replace the console with a known good con- 
    sole. If the problem is corrected, replace the 
    faulty console. 
    (c) Replace the SMXTG PCB. 
    4.09 Siemens Digital Telephone (SDT) Related Failures. 
    Step-by-step instructions for troubleshooting SDTs are provid- 
    ed below: 
    a. If the SDT is completely dead (i.e., no dial tone, no au- 
    dible alerting, no functioning buttons and LED indi- 
    cators), 
    1. Using the SERVICE CMU Procedure, check serv- 
    ice state of the circuit serving this SDT. 
    (a) If in-service, continue with step 2. 
    (b) If out-of-service - craft, return the circuit to the 
    in-service state (Table 4-10) and verifv opera- 
    tion. Continue with step 2 ‘if the SDT iemains 
    inoperative. 
    (c) If out-of-service - automatic, attempt to return 
    the circuit to the in-service state (Table 4-10). 
    (1) If circuit returns to the in-service state and 
    the failure clears, the problem was tran- 
    sient. If transient problems recur on the 
    same circuit, continue with step 2. 
    4-28  
    						
    All Siemens manuals Comments (0)

    Related Manuals for Siemens Saturn Iie Epabx General Description Manual