Home > Siemens > Communications System > Siemens Saturn Iie Epabx General Description Manual

Siemens Saturn Iie Epabx General Description Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Siemens Saturn Iie Epabx General Description Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 428 Siemens manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							SATURN IIE EPABX 
    Maintenance and Troubleshooting 
    Figure 2.08 is a block diagram which shows the ac power in- 
    put to the Power System Unit and ac power distribution to 
    the various system power supplies via the PSU circuit break- 
    er panel. All circuit breakers and fuses are mounted on the 
    PSU front panel. (Refer to Figure 2.01.) Figure 2.09 shows the 
    layout of input/output connectors and terminals on the rear 
    panel of the PSU. Table 2.00 lists the designations and func- 
    tions of these connectors and terminals. 
    Figure 2.10 is a block diagram showing the fusing of -48 volt 
    outputs from the -48PS module(s). As shown, these -48 volt 
    outputs are supplied to the Basic and LTU Shelves and the 
    Ring Generator (RGEN) module. Also shown is the fusing of 
    the RAClRMW (ringing signal) output of the Control Logic 
    Board which is distributed to the Basic and LTU Shelves. 
    The function and consequences of a failure of each of these 
    modules is described below: 
    a. Power System Unit (PSU). The PSU performs a num- 
    ber of major functions in the SATURN IIE System. It A30808-X5130-DllO-l-8920 
    Issue 1, May 1986 
    provides (1) dc voltages necessary for operation of the 
    Lineflrunk and Common Equipment PCBs in the Basic 
    Shelf and Floppy Disk Drives FDDO and FDDl, (2) ac 
    distribution-to and circuit breaker protection on the ac 
    inputs of all system power supplies, (3) -48Vdc distri- 
    bution and fuse protection on the -48PS outputs to the 
    Basic Shelf and optional LTU Shelf(s), (4) it generates 
    and provides synchronization of the ringing 
    (RACIRMW) signal and provides fuse protection and 
    distribution of the ringing signal to the Basic Shelf and 
    optional LTU Shelf(s), (5) it provides-fuse, voltage, and 
    alarm detection and monitoring, and (6) failure trans- 
    fer control and major and minor alarm indications when 
    a failure or alarm condition is detected. In addition to 
    the above, the PSU provides mounting facilities and 
    power input to the optional Memory Support Module 
    (MSM) when it is provided in the system. The various 
    circuits and components that make up the PSU are list- 
    ed and described below. Refer to Figure 2.11 for a block 
    diagram of the PSU. . , 
    2-16  
    						
    							SATURN IIE EPABX 
    Maintenance and Troubleshooting A30808-X5130-DllO-l-8920 
    Issue 1, May 1986 
    LINE 
    AC IN 
    (AC #O 
    IN 
    LINE 
    AC IN 
    (AC #1 -- 
    W 
    l * 
    J5 s ,.I LTUPSl l 
    I P/O LTU SHELF 2 
    (EXPANSION CABINET) 
    LTIlPS2 l I P/O LTU SHELF 3 
    (EXPANSION CABINET)  P/O LTU SHELF 1 
    (BASIC CABINET) 
    / Jl 
    + -48PSl l 
    l 
    OPTIONAL DEPENDING UPON CUSTOMER/ 
    SYSTEM REQUIREMENTS. 
    l * SECOND AC INPUT IS REQUIRED WHEN 
    EXPANSION CABINET IS USED. JUMPER 
    PLUG AT J2 IS REMOVED AND SECOND 
    AC SOURCE IS WIRED TO J2. (REQUIRED WHEN 
    EXPANSION CABINET 
    IS USED) 
    Figure 2.08 Block Diagram of AC Input to Power Supply Assemblies and Modules 
    2-17 
    .  
    						
    							SATURN IIE EPABX 
    Maintenance and Troubleshooting A30808-X5130-DllO-l-8920 
    Issue 1, May 1986 
    Ftgure 2.09 Layout of Connectors and Terminals on PSU Rear Panel 
    . 7-18  
    						
    							SATURN IIE EPABX 
    Maintenance and Troubleshooting A30808-X5130-DllO-l-8920 
    Issue 1, May 1986 
    PSU 
    -mm---- 
    rP/O CIRCUIT j 
    I BREAKER , 
    * OPTIONAL DEPENDING UPON CUSTOMER/ 
    SYSTEM RECIUIREMENTS J& TO BASIC SHELF 
    I (BASIC CABINET) 
    b TO LTU SHELF 
    1 * 
    : (BASIC CABINET) 
    TO LTU SHELF 2 * 
    (EXPANSION CABINET) 
    & TO LTU SHELF 3 * 
    (EXPANSION CABINET) 
    J7 TO BASIC SHELF 
    I (BASIC CABINET) 
    &, TO LTU SHELF 1 * 
    (BASIC CABINET) 
    TO LTU SHELF 2 * 
    (EXPANSION CABINET) 
    & TO LTU SHELF 3 ’ ; 
    (EXPANSION CABINET) ! 
    !?+ TO BASIC SHELF 
    ’ (BASIC CABINET) 
    & TO LTU SHELF 1 * 
    (BASIC CABINET) ; 
    J& TO LTU SHELF 2 * 
    I (EXPANSION CABINET) 
    & TO LTU SHELF 3 * 
    (EXPANSION CABINET) 
    Figure 2.10 Fusing of -48 Volt Outputs from -48PS0 and -48PSl 
    2-19  
    						
    							SATURN IIE EPABX 
    Maintenance and Troubleshooting 
    Table 2.00 Functions of Connectors and Terminals on PSU Rear Panel 
    DESIGNATION FUNCTION 
    Note: Refer to Figure 2.09. _ - 
    Jl AC power input (AC#O IN) for distribution to PSU Power Supply Board, LTU Shelf power supplies, 
    and -48PS0 if system consists of Basic Cabinet only 
    J2 AC power input (AC#l IN) to -48PS0 and -48PSl in systems consisting of Basic and Expansion 
    Cabinets. Otherwise, provides jumper plug connection for routing ac power to -48PS0 via PSU 
    Circuit Breaker Panel 
    J3 
    J4 
    J5 
    J6 AC power to LTUPSO in LTU Shelf 1 
    AC power to -48PS0 and -48PSl 
    AC power to LTUPSl (LTU Shelf 2) and LTUPS2 (LTU Shelf 3) in Expansion Cabinet 
    -488 and -48P inputs from -48PS0 and -48PSl; +5V and +12V distribution to FDDP (not 
    equipped at this time) 
    J7 
    J8 
    J9 
    JlO 
    Jll 
    J12 -488, -48R and RAClRMW distribution to Basic and LTU 1 Shelves in Basic Cabinet 
    -48B, -48P, and RAClRMW distribution to LTU Shelves 2 and 3 in Expansion Cabinet 
    +5V distribution to Basic Shelf (busbar lug connections) 
    -5V, +5VB, -12V, and +12V distribution to Basic Shelf 
    +5V and +12V distribution to FDDO and FDDl 
    SYNR+, FUSA+, BATPOK-, and VFAlLc to Basic Shelf. ERING-, MINALM+, and MAJALM+, 
    from Basic Shelf. 
    J13 Failure Transfer Control, Major and Minor Alarm Status, and Maintenance Telephone to MDF 
    J14 DC. GND (busbar lug connections) 
    J15 EXT FUSE ALM (external fuse alarm input; disabled when jumper is installed) 
    J16 MSMlLCL jumper for +5V memory power I 
    - . . 
    2-20  
    						
    							SATURN IIE EPABX 
    Maintenance and Troubleshooting 
    I 
    - 
    A30808-X5130-DllO-l-6920 
    Issue 1, May 1986 
    1. Front Panel Fuses, Controls, and Indicators. The 
    following are mounted on or visible through open- 
    ings in the PSU front panel: 
    l Fuses for all -48Vdc and ringing (RACIRMW) 
    voltages to the Basic and optional LTU Shelves 
    (part of Circuit Breaker Panel) 
    l Circuit breakers for ac inputs to all system pow- 
    er supplies (part of Circuit Breaker Panel) 
    l MAJOR (red) and MINOR (yellow) alarm 
    (ALARMS) indicators (part of Control Logic 
    Board) 
    l FAILURE TRANSFER switch and associated 
    ACTIVE (red) and INHIBIT (yellow) indicators 
    (part of Control Logic Board) 
    l MTCE PHONE (maintenance telephone) jack 
    (part of Control Logic Board) 
    0 BATTERY TEST pushbutton switch and as- 
    sociated ON BATTERY POWER (red) and Eat- 
    tery Test (green) indicators (part of MSM) 
    0 
    +5 V ADJUST potentiometer (part of Basic 
    Power Supply Board) 
    (a) Fuses. All -48 volt inputs and RAClRMW inputs 
    to the LTU and Basic Shelves are fused as 
    shown in Figure 2.10. 
    Failure of a fuse to blow under fusing current 
    conditions is very unlikely. To ensure proper 
    protection, always replace a blown fuse with 
    one of the correct value (refer to Figure 2.10). 
    (b) Circuit Breakers. All system power supply mod- 
    ules, including the Basic Power Supply Board 
    in the PSU, are protected at their input by a cir- 
    cuit breaker as shown in Figure 2.08. 
    The remaining PSU controls and indicators are 
    discussed below in text covering the individu- 
    al PSU modules. 
    2. Basic Power Supply Board. The PSU Basic Pow- 
    er Supply Board (refer to Figure 2.11) is a switch- 
    ing power supply which provides +SVdc, -5Vdc, 
    +12Vdc, and -12Vdc for operation of line/trunk unit 
    and common equipment PCBs in the Basic Shelf, 
    the FDDs, and the Control Logic Board and option- 
    al MSM in the PSU. 
    Failures in the Basic Power Supply Board could af- 
    fect operation of the complete system or, selectively, 
    certain types of line/trunk units or common equip- 
    ment PCBs in the Basic Shelf, voltage and fuse 
    alarm monitoring, SYNR+ and RAClRMW gener- 
    ating, and failure transfer circuits on the Control 
    Loaic Board. the MSM in the PSU. and the FDDs. 
    Altrhough the PSU provides the dc voltages neces- 
    sary to operate the floppy disk drive motors, cir- 
    cuits in the CIOP control the voltages. The floppy 
    disk drive select circuit in the CIOP switches dc 
    to the motors of floppy disk drives FDDO and FDDl 
    using the MOTORONO- and MOTORONI- signals, respectively. A failure in this circuitry could prevent 
    switching of dc to a motor or cause dc to be 
    switched to a.motor when it should be switched off. 
    The inability to switch either motor on may be due 
    either to a disconnected power cable between the 
    PSU and the FDD (PSlJ.Jll and FDD J2) or a dis- 
    connected control cable-between the Basic Shelf 
    (J63 for FDDO; J62 for FDDl) and the FDD signal 
    connector, Jl. 
    In the event of a failure in the Basic Power Supply 
    Board, the PSU should be replaced. 
    3. Ring Generator (RGEN) Module. The RGEN mod- 
    ule in the PSU generates the ringing ac voltage 
    (RAC) used in the SATURN IIE System. This voi- 
    tage has a nominal 20H2, 90 volts RMS sinusoi- 
    dal waveform. The RGEN module has a rated 
    output power of 25 Watts and is powered from 
    -48VP via fuse F5 (RGEN) on the PSU front panel. 
    The output voltage (RAC) is routed to the Control 
    Logic Board where it is interleaved with the Ring 
    Message Waitinq signal (RMW) to form the 
    RAClRMW signal, The RA&RMW signal is dis- 
    tributed to the Basic and LTU Shelves via RAC 
    fuses FlO through F13 on the PSU front panel. 
    In the event of a failure in the Ring Generator Mod- 
    ule, the PSU should be replaced. 
    4. Cbntrol Logic Board. The Control Logic Board con- 
    tains circuits and components which perform the 
    following functions. 
    . 
    0 
    . 
    Fuse Alarm Detection 
    Ring Synchronization (SYNR+) Signal 
    Generation 
    Ringing AC/Ring 
    Message Waiting 
    (RACIRMW) Signal Generation 
    Voltage and Alarm Monitoring 
    Failure Transfer Control 
    Failure Transfer and Alarm Output Relays 
    Major and Minor Alarm Indicators 
    Maintenance Telephone Jack 
    (a) Fuse Alarm Detect Circuit. The fuse alarm de- 
    tect circuit monitors each fuse and, upon sens- 
    ing a blown fuse condition, sends a Fuse Alarm 
    signal (FUSA+) to the Controller/Input-Output 
    Processor (CIOP) PCB. A fuse alarm will cause 
    a minor alarm condition in the SATURN IIE Sys- 
    tem; however, the location of the blown fuse 
    must be determined by a visual check of the 
    fuses on the front panel of the PSU. These 
    fuses are “grasshopper” type fuses in which 
    a spring wire indicates by its position away from 
    normal that the fuse has blown. (The spring 
    wire also provides the alarm contact.) If used, 
    a fuse alarm may also be provided through the 
    external fuse alarm connections (EXT FUSE 
    ALM, J15) on the rear panel of the PSU. Nor- 
    mally closed external relay contacts are wired 
    to the terminals and, when these contacts 
    open, a fuse alarm (FUSA+) output will be sent 
    to the CIOI? The EXT FUSE ALM terminals are 
    jumpered at the factory to disable the function. 
    2-22  
    						
    							SATURN IIE EPABX 
    Maintenance and Troubleshooting 
    A failure in the fuse alarm detect circuit may 
    cause spurious fuse alarm (FUSA+) signals or 
    prevent a fuse alarm signal, depending on the 
    nature of the fault. A spurious fuse alarm may 
    occur due to a disconnected cable from J12 of 
    the PSU module to the basic shelf as well as 
    a fault in the CIOP PCB. 
    If a fuse is blown but no fuse alarm is indicat- 
    ed, the fault could be in the fuse alarm detect 
    circuit in the PSU Control Logic Board or cir- 
    cuits in the CIOP PCB. 
    If the Fuse Alarm Detect Circuit on the Control 
    Logic Board fails, replace the PSU. 
    (b) Ring Synchronization Signal (SYNR+) Circuit. 
    The SYNR+ signal is used in the SLMA-0, 
    SLMA-S. and .%A16 PCBs to control the oper- 
    ation and release of the ring relays. The 
    SYNR+ sianal is routed from the PSU to the 
    SMXTG PCB in the Basic Shelf. It is buffered 
    in the SMXTG PCB and then distributed to 
    each line/trunk group on the Basic and 
    LTU shelves. Loss of the SYNR+ signal will gener- 
    ate an alarm signal and light the ALMO LED 
    on the affected LTUC PCB. Refer to Table 4.03. 
    (c) Ringing AC/Ring Message Waiting 
    (RACIRMW) Signal Circuit. The RAC signal 
    from the PSU RGEN module and the ERING- 
    signal from the CIOP PCB are used in the 
    generation of the RAClRMW signal in the PSU 
    Control Logic Board. 
    The RAClRMW signal consists of 2-second in- 
    tervals of RAC signal interleaved with l-second 
    intervals of RMW signal. The transitions from 
    RAC to RMW and from RMW to RAC are con- 
    trolled by the ERING- signal. 
    The RAC signal is nominally 90 Vat RMS 20Hz 
    and the RMW signal is nominally 97 Vdc. The 
    RAClRMVV signal consists of two interleaved 
    phases as shown in Figure 2.12. 
    During the RAC signal intervals, telephones in 
    the ring mode will ring and the associated mes- 
    sage waiting lamps will flicker. During the RMW 
    signal intervals, telephones in the message 
    waiting mode will have their message waiting 
    lamps lighted steadily. The associated ringer 
    will not sound. 
    Thus telephones will ring with a 2 seconds on, 
    4 seconds off cadence and the message wait- 
    ing lamps will light with a 1 second on, 2 se- 
    conds off cadence. 
    Failure of the RAClRMW circuit on the Control 
    Logic Board may result in improper RAC or 
    RMW signals and/or improper timing of these 
    signals. Such faults may be detected audibty 
    and visually. 
    if the Ringing AC/Ring Message Waiting 
    (RAC/RMW) Circuit on the Control Logic Board 
    03 
    A30808-X5130-DllO-l-6920 
    lssue 1, May 1986 
    fails, replace the PSU. 
    Voltage and Alarm Monitoring Circuit. The vol- 
    tage and alarm monitoring circuit is provided 
    on the Control Logic Board in the PSU. The 
    +12Vdc and and -5Vdc outputs of the PSU Bas- 
    ic Power Supply Board and the -488 output vol- 
    tage from the -48PS module(s) are monitored 
    by the circuit. A loss of one or more of the three 
    voltages causes a voltage failure signal 
    (VFAIL+) to be sent to the SMXTG in the Bas- 
    ic Shelf and results in a minor alarm. 
    The +5Vdc, +5.2Vdc, and -12Vdc voltages are 
    not monitored. The reason for this is that a loss, 
    or low level, of the +5Vdc will affect operation 
    of all line/trunk unit PCBs on the Basic Shelf 
    and will cause generation of a PRESENCE ER- 
    ROR alarm from all of these PCBs to be record- 
    ed in the system’s failure history memory. 
    The toss, or low level, of +52Vdc on the Basic 
    Shelf will cause complete system failure. 
    (However, if an 
    MSM module is installed, the 
    memory will be retained for at least 5 minutes.) 
    The -12Vdc is used on the DTMF and RAUP 
    modules. Therefore, a loss or low level of this 
    voltage on the LTU or Basic Shelves, will be 
    evidenced by misoperation of the RAUP PCB 
    on the Basic Shelf and the DTMF PCBs on 
    other shelves, as applicable. 
    If the Voltage and Alarm Monitoring Circuit on 
    the Control Logic Board fails, replace the PSU. 
    (e) Failure Transfer Control Circuit. With the 
    FAILURE TRANSFER mode select switch on 
    the front of the PSU set to the AUTO position, 
    an active MAJALM+ signal from the CIOP PCB 
    in the Basic shelf will initiate a failure transfer. 
    With the FAILURE TRANSFER mode select 
    switch in the ACTIVE position, failure transfer 
    is initiated regardless of the status of the moni- 
    tored voltages and MAJALM+ signal. 
    With the FAILURE TRANSFER mode select 
    switch in the INHIBIT position, failure transfer 
    is inhibited regardless of the status of the moni- 
    tored voltages and MAJALM+ signal. 
    If the Failure Transfer Control Circuit on the 
    Control Logic Board fails, replace the PSU. 
    (f) Failure Transfer and Alarm Output Relays. 
    Failure transfer/major alarm and minor alarm 
    relays in the PSU Control Logic Card have con- 
    tact sets connected to pins on connector J13 
    on the rear panel of the PSU. 
    Both relays are normally operated. Contact sets 
    of one of the relays are used to control remote 
    failure transfer (PXFER) and provide major 
    alarm (MAJOR) status. A contact set on the 
    other relay provides minor alarm (MINOR) 
    status. 
    I , 
    -. 
    2-23  
    						
    							SATURN HE EPABX 
    Maintenance and Troubleshooting 
    RAC/RMW 
    SIGNAL 
    90 VOLTS RMS, 20 HZ 
    RAC 0 
    RAC 1 
    97 VOLTS DC 
    RMW. 
    TIME SCALE IN SECONDS 
    Figure 2.12 RAClRMW Signals 
    2-24  
    						
    							SATURN IIE EPABX A30808-X5130-DllO-l-8920 
    Maintenance and Troubleshooting issue 1, May 1986 
    Both normally closed and normally open con- 
    tact arrangements are provided for failure trans- 
    fer 
    and .for major alarm and minor alarm 
    outputs to allow use of external equipment 
    responding to either arrangement. Connections 
    are normally made to the MDF for distribution 
    of the failure transfer, major alarm, and minor 
    alarm functions. 
    The relay contacts connected to J13 will give 
    an output status for the various combinations 
    of MAJALM+ and MINALM+ signals as shown 
    in Table 2.01. 
    If a fault is suspected in the Failure Transfer and 
    Alarm Output Relays on the Control Logic 
    Board, replace the PSU. (g) Major and Minor Alarm Indicators. The MAJOR 
    and MINOR ALARMS indicators are visible 
    through openings in the PSU front panel and light 
    when MA.JALM+ and MlNALM+ signals are 
    received from the CIOP Table 2.02 shows alarm 
    indicator states for combinations of MAJALM+ 
    and MINALM+ signals from the CIOP If an 
    alarm indicator is faulty, replace the PSU. 
    (h) Maintenance Telephone (MTCE PHONE) Jack. 
    A standard modular jack is accessible through 
    the front of the PSU for plug-in of a maintenance 
    telephone. The jack is connected to pins on con- 
    nector J13 on the PSU rear panel as indicated 
    in Table 2.01. Connector J13 is wired to the MDF 
    If the jack or interconnecting printed circuit or 
    PSU wiring is faulty, replace the PSU. 
    Table 2.01 Pin Functions at Connector 513 on the PSU 
    J13 PIN 
    1 Ring 
    26 Tip 
    2 Ring 
    27 Tip 
    3 Ring 
    28 Tip 
    31 Tip 
    4 Ring 
    29 Tip PIN LEAD AND RELAY CONTACT STATUS 
    (Not Applicable) 
    (Not Applicable) 
    (Normally Open) 
    (Common) 
    (Normally Closed) 
    (Common) 
    (Normally Closed) 
    (Common) 
    (Normally Open) FUNCTION 
    Maintenance Phone 
    Failure Transfer 
    Major Alarm 
    6 Tip (Normally Open) 
    5 Ring (Common) Minor Alarm 
    30 Tip (Normally Closed) 
    Note: The relay contact status shown in this table applies when both relays are not operated (in accordance with standard 
    convention). However, under normal system operating conditions, both relays are operated. Therefore, under normal 
    system operating conditions, the relay contacts are the reverse of those shown in this table. 
    Table 2.02 Alarm LEDs and Output Status at Connector J13 on the PSU 
    ALARM STATUS LED LIT OUTPUT STATUS (J13) 
    Neither MINALM+ nor None Normal 
    MAJALM + Active 
    MlNALM+ Only Active 
    MAJALM+ Only Active 
    Both MINALM+ and 
    MAJALM-t Active MINOR only 
    MAJOR only 
    MAJOR only Minor Alarm Only 
    Major Alarm, Failure Transfer 
    Major Alarm, Failure Transfer 
    2-25  
    						
    All Siemens manuals Comments (0)

    Related Manuals for Siemens Saturn Iie Epabx General Description Manual