Here you can view all the pages of manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Installation And Test For Single-Carrier Cabinets Manual. The Lucent Technologies manuals for Communications System are available online for free. You can easily download all the documents as PDF.
Page 61
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-3 Equipment Room Hardware 2 Cross-Connect Fields Eac h Main Distrib ution Frame (MDF) c ontains a trunk/auxiliary field and a d istrib ution field . The trunk/auxiliary field c ontains three c ross-c onnec t areas: 1. The g reen field terminates the network interfac e leads from the Central Offic e (CO) and p rovid es the...
Page 62
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-4 Main Distribution Frame 2 Main Distribution Frame The Main Distrib ution Frame (MDF) is loc ated d irec tly b ehind the c ab inet stac k. Fi g u re 2 - 2 shows a typ ic al Sing le-Carrier Cab inet installation using 110A-typ e terminal bloc ks. Figure 2-2. Typical 110A-Type Terminal Blocks Figure Notes 1. System Cab inets...
Page 63
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-5 Installation Requirements 2 Installation Requirements Off-Premises Circuit Protection Protec tion from hazard ous voltag es and c urrents is req uired for all off-p remises (out of b uild ing ) trunks, lines, and terminal installations. Both over-voltag e p rotec tion (lig htning, p ower ind uc tion, and so forth), and sneak...
Page 64
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-6 Installation Requirements 2 110-Type Hardware The trunk/auxiliary field and the d istrib ution field are mounted on the same wall. Eac h 110P-typ e terminal b loc k is 8.5 inc hes (21.6 c m) wid e. Vertic al p atc h c ord troug hs are 5.31 inc hes (13.4 c m) wid e and horizontal p atc h c ord troug hs are 23 inc hes...
Page 65
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-7 Install Equipment and Cables 2 Install Equipment and Cables Install the Main Distrib ution Frame (MDF), the Cable Slac k Manag er, and the sneak fuse panels. Route the c ab les from the rear of the c ab inet stac k to the MDF via the Cab le Slac k Manag er. See Fi g u re 2 -3 . Figure 2-3. Cable Routing Through Cable Slack...
Page 66
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-8 Install Sneak Fuse Panels 2 Install Sneak Fuse Panels Sneak c urrent p rotec tion is req uired b etween the inc oming RJ21X or RJ2GX network interfac e and the system for b oth trunk and off-p remise c irc uit p ac ks. The Model 507B sneak c urrent fuse panel, or eq uivalent, is rec ommend ed for sneak c urrent p rotec...
Page 67
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-9 Install Sneak Fuse Panels 2 Figure 2-4. Model 507B Sneak Fuse Panel 1. Loc ate the 507B near the network interfac e or the MDF. 2. Hold the p anel ag ainst the mounting surfac e and mark the mounting sc rew loc ations. Drill p ilot holes at the marked loc ations and partially install a loc ally ob tained #12 x 3/4-inc h sc...
Page 68
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-10 Install Sneak Fuse Panels 2 Tab le 2-1 is a p inout of the c ab le wiring and assoc iated fuse numb ers. 6. Sec ure the B25A c ab le to the p anel with the c ap tive sc rew on the connector and a supplied cable tie. Table 2-1. Sneak Fuse Connector Pinout Connector Pin NumbersPair/Fuse Number 26/1 1 27/2 2 28/3 3 29/4 4...
Page 69
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-11 Install Coupled Bonding Conductor 2 Install Coupled Bonding Conductor The Coupled Bonding Cond uc tor (CBC) c onnec ts to the sing le-point g round b loc k and runs ad jac ent to p airs in an assoc iated telec ommunic ations c ab le. See Fig ure 2-5 . The mutual c oup ling b etween the b ond ing c ond uc tor and the p...
Page 70
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-12 Install Coupled Bonding Conductor 2 Figure 2-5. Coupled Bonding Conductor Figure Notes 1. 25-Pair Tip & Ring Cab les to Cabinets 2. Coup led Bond ing Cond uc tor (CBC) Terminal Bloc k 3. Tie Wraps 4. Cab le Shield or Six Sp are Pairs 5. Ground on Carb on Bloc k Protector or Eq ui va l en t 6. Trunk Cab le to Network...