Here you can view all the pages of manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Installation And Test For Single-Carrier Cabinets Manual. The Lucent Technologies manuals for Communications System are available online for free. You can easily download all the documents as PDF.
Page 21
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-3 Install Single-Carrier Cabinets 1 Refer to the serial numb ers and lettered d esig nation strip s in the Customer Servic e Doc ument (CSD) when stac king the c ab inets. If earthq uake p rotec tion is required, skip to ‘‘Install Earthq uake Protec tion’’ . Return to this sec tion when finished . !CAUTION: System g round ing...
Page 22
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-4 Install Single-Carrier Cabinets 1 Position Cabinets (High or Critical Reliability) One Cabinet Stack (Processor Port Network) Perform this step first for all hig h or c ritic al reliab ility c ab inet installations. 1. Plac e Control Cab inet A (J58890L) on the floor in the p osition d etermined when the room layout was planned....
Page 23
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-5 Approved Grounds 1 Approved Grounds An ap p roved g round is the c losest ac c ep tab le med ium for g rounding the b uild ing entranc e protec tor, entranc e c ab le shield , or sing le-p oint ground of elec tronic telep hony eq uip ment. If more than one typ e of ap proved g round is availab le on the p remises, the g...
Page 24
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-6 Connect Cabinet Grounds 1 APPROVED FLOOR GROUNDS Ap p roved floor g round s are those g rounds on eac h floor of a hig h-rise b uild ing suitab le for c onnec tion to the g round terminal in the riser c loset and to the c ab inet eq uip ment sing le-p oint g round terminal. Ap p roved floor g round s may include the...
Page 25
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-7 Connect Cabinet Grounds 1 Connect DC Power Cabinet Ground Figure 1-1. DC Power Cabinet Grounding 1. At the DC Power Cab inet, c onnec t a 1 AWG (#70) (7 mm 2) g round wire to the GROUND DISCHARGE b ar. See Fi g u re 1 -1 . 2. Route the g round wire out of the c ab inet and terminate it on the ap p roved g round . !CAUTION:...
Page 26
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-8 Connect Cabinet Grounds 1 Connect DC Battery Cabinet Frame Ground Figure 1-2. Frame Ground Wiring Between Power Cabinets 1. Cut a leng th of 6 AWG (#40) (4 mm 2) wire long enoug h to reac h b etween the DC Power Cab inet and the DC Battery Cab inet. See Fi g u re 1 -2 . 2. Crimp a terminal lug on the eac h end of the wire. The...
Page 27
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-9 Connect Cabinet Grounds 1 Connect DC Power Distribution Unit Ground Figure 1-3. DC Power Distribution Unit Ground 1. Measure and c ut a length of 6 AWG (#40) (4 mm 2) wire long enoug h to reac h b etween the GROUND DISCHARGE b ar in the DC Power Cab inet and the GRD c onnec tor on the DC Distrib ution Unit. See Fi g u re 1 -3...
Page 28
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-10 Connect Cabinet Grounds 1 Connect Single-Carrier Cabinet Ground Figure 1-4. Single-Carrier Cabinet Ground 1. Cut a leng th of 6 AWG (#40) (4 mm 2) wire long enoug h to reac h b etween the GROUND DISCHARGE b ar on the DC Power Cab inet and the sing le-p oint g round bloc k on the Control Cab inet (b ottom c ab inet in Fi g u re...
Page 29
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-11 Connect Cabinet Grounds 1 Grounding AC-Powered Cabinets Only !CAUTION: System g round ing shall c omp ly with the general rules for g round ing c ontained in Artic le 250 of the National Elec tric al Cod e (NEC), National Fire Protec tion Ag enc y (NFPA) 70, or the ap p lic ab le c od e at the installation site. NOTE: Before...
Page 30
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-12 Connect Cabinet Grounds 1 Single-Carrier Cabinet Ground Figure 1-5. Typical AC Power and Ground Layout — Rear Figure Notes 1. Cabinet Stac k 1 Control Cab inet A 2. Circ uit Breaker 3. AC Power Rec ep tac le 4. Cabinet Stac k Sing le-Point Ground Bloc k 5. 8-Foot (2.5 Meters) Power Cord 6. National Elec tric al Manufac turers...