Here you can view all the pages of manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Installation And Test For Single-Carrier Cabinets Manual. The Lucent Technologies manuals for Communications System are available online for free. You can easily download all the documents as PDF.
Page 51
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-33 Connect System Cables 1 Recommended Cable Routing 1. Route the fib er optic c ab le up toward the top of the c ab inet. The exc ess c ab le should b e loop ed and d rap ed from the B25A c able c lamp on the top g round p late in the stac k. See Figure 1-18 . 2. Dress the c ab le b y tie wrap p ing it to the outsid e of...
Page 52
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-34 Connect System Cables 1 Standard Reliability Fiber Connections Connec t and route the fib er op tic c able as shown in the c ab le running list. See Fi g u re 1 - 1 9 for a samp le c ab le routing. Figure 1-19. Connections to Standard Reliability SystemsFigure Notes 1. Control Cab inet 2. Port Cab inet 3. Exp ansion Control...
Page 53
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-35 Connect System Cables 1 High Reliability Fiber Connections Connec t and route the fib er op tic c able as shown in the c ab le running list. See Fi g u re 1 - 2 0 for a samp le c ab le routing. Figure 1-20. Connections to High Reliability SystemsFigure Notes 1. Control Cab inet 2. Duplic ate Control Cab inet 3. Port Cab inet...
Page 54
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-36 Connect System Cables 1 Critical Reliability Fiber Connections Connec t and route the fib er op tic c able as shown in the c ab le running list. See Fi g u re 1 - 2 1 for a samp le c ab le routing. Figure 1-21. Connections to Critical Reliability SystemsFigure Notes 1. Control Cab inet 2. Duplic ate Control Cab inet 3. Port...
Page 55
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-37 Install Earthquake Protection 1 Install Earthquake Protection Earthq uake p rotec tion only installs on Sing le-Carrier Cab inets. Figure 1-22. Front Mounting Angle Location 1. Position the Control Cab inet (J58890L) in the p osition it is to oc c up y when the installation is c omp lete. Be sure the c ab inet is level. 2. Using...
Page 56
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-38 Install Earthquake Protection 1 5. Sec ure the Front Mounting Ang le to the floor using the short hex head bolts provided. 6. Move the c ab inet b ac k into p lac e. 7. At the rear of the c ab inet, remove the two hole plug s from the b ottom of the c ab inet. See Fig ure 1-2 3 . 8. Insert a p enc il or marker throug h the...
Page 57
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-39 Install Earthquake Protection 1 Figure 1-23. Cabinet Earthquake Mounting — Rear View 13. Lay the sup p lied Stiffener on the bottom rear of the c ab inet and alig n with the holes in the b ottom of the c ab inet. See Fig ure 1-2 3 . 14. Slid e a nylon washer onto eac h of the two sup p lied long hex head b olts. 15. Insert...
Page 58
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-40 Install Earthquake Protection 1
Page 59
Install Telecommunications Cabling 2-1 Equipment Room Hardware 2 DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 2 Install Telecommunications Cabling Equipment Room Hardware SYSTIMAX 110-typ e hardware is used for the Main Distrib ution Frame (MDF). 110-typ e hard ware is availab le in two b asic types: the 110A and 110P. The 110A req uires less wall sp ac e than the 110P. The 110P inc lud es horizontal and...
Page 60
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install Telecommunications Cabling 2-2 Equipment Room Hardware 2 Figure 2-1. Example MDF ConnectionsFigure Notes 1. Rear of Port Cab inet 2. Main Distrib ution Frame (MDF) 3. Port Distribution Field (Purp le Field ) 4. Station Distribution Field (White Field) 5. Trunk/Auxiliary Field 6. Purp le Field 7. Yellow Field 8. Green Field9. Satellite Closet 10. Auxiliary Cab...