Page 61

CHAPTER 3 ND-45492 (E)
Pag e 4 4
Revision 2.0
(14) When the system is a multiple-rack configuration, connect  the PN-BS00 in rack 1 to the PN-BS00 in rack
using BUS cable, as shown in Figure 003-19 and Figure 003-20.
Figure 003-19  BUS Cable
NAP 200-003
Sheet 22/37
Installation of Main Equipment
1 meter  (39 inches)
48-TW-1 CONN CA 

Page 62

ND-45492 (E) CHAPTER 3
Page 45
Revision 2.0
Figure 003-20  Connection of the BUS Cables
NAP 200-003
Sheet 23/37
Installation of Main Equipment
PIM7
PIM6
PIM5
PIM4 PIM3
PIM2
PIM1
PIM0BS01
CN2
CN1
CN2
CN1
CN2
CN1
CN2
CN1BS01
CN2
CN1
CN2
CN1
CN2
CN1
CN2
CN1
48-TW-1 CONN CA
BS01
BS01
BS00BS01
BS01
BS01
48-TW-.07 
CONN CARack 1
Rack 2 

Page 63

CHAPTER 3 ND-45492 (E)
Pag e 4 6
Revision 2.0
2. Wall Mounting Installation
(1) Using four appropriate fasteners (locally provided; see Table 003-1) for the type of wall construction, se-
cure the RACK PARTS as shown in Figure 003-21.  For the wall mounting points, refer to Figure 002-2 in
NAP-200-002.
Note:For the wall-mounting installation, a concrete wall is recommended because the concrete wall is more firm
to mount the PBX than a wooden wall or a plaster board. The plaster board is the most infirm...

Page 64

ND-45492 (E) CHAPTER 3
Page 47
Revision 2.0
Figure 003-21  Screwing the RACK PARTS to a Wall
NAP 200-003
Sheet 25/37
Installation of Main Equipment
350 mm 
(13.8 inch)
350 mm 
(13.8 inch)
250 mm 
(9.8 inch)
ANCHOR (x4/PIM) 
(SEE FIGURE 002-2)
(WALL)382 mm (15.0 inch)
M4 MACHINE SCREW-B (x4/PIM) 
SECURED TO RACK PARTS 
(PROVIDED WITH RACK PARTS)
SCREW-A (x4/PIM) 
SECURING RACK PARTS TO WALL 
(LOCALLY PROVIDED) 
(SEE TABLE 003-1)
M5 MACHINE SCREW-C (x4/PIM) 
(PROVIDED WITH RACK PARTS) 
(SEE FIGURE 003-20)...

Page 65

CHAPTER 3 ND-45492 (E)
Pag e 4 8
Revision 2.0
(2) When mounting the RACK PARTS to a wall, connect all the RACK PARTS to each other, and connect the
BASE to the bottom RACK PARTS using the M5 Machine screws (provided), as shown in Figure 003-21.
Figure 003-22  Connecting the RACK PARTS and the BASE
NAP 200-003
Sheet 26/37
Installation of Main Equipment
(JOINT)
RACK PARTS
M5 MACHINE SCREW-C 
(x2/JOINT AREA) 
(PROVIDED WITH RACK PARTS)
(JOINT)
BASE 

Page 66

ND-45492 (E) CHAPTER 3
Page 49
Revision 2.0
(3) Attach four M4 machine screws (provided) to the RACK PARTS as shown in Figure 003-21.  
For proper mounting of each PIM, approximately 4 mm (0.2 inch) spacing should be provided between the
inner face of the M4 machine screw and the RACK PARTS front channel.  See Figure 003-23.
(4) Align and insert the key hole slots of the rear cover of each PIM to the machine screws secured in step (3).
See Figure 003-23.
Figure 003-23  Mounting the PIM to the RACK PARTS...

Page 67

CHAPTER 3 ND-45492 (E)
Pag e 5 0
Revision 2.0
(5) After hanging each PIM onto the RACK PARTS, tighten each M4 machine screw using a Phillips screw
driver as shown in Figure 003-24.
Figure 003-24  Screwing the PIM to the RACK PARTS
NAP 200-003
Sheet 28/37
Installation of Main Equipment
M4 MACHINE SCREW-B (X4)
PIMRACK PARTS 

Page 68

ND-45492 (E) CHAPTER 3
Page 51
Revision 2.0
(6) Connect the bottom PIM and the BASE, and connect PIMs to each other using 3 bolts (provided), as shown
in Figure 003-6 and Figure 003-7. Then, position the TOP COVER on the top PIM and connect them to-
gether with 4 screws (provided), as shown in Figure 003-8.
(7) Connect the AC CORD-B to the terminals inside the BASE in the same manner as for the Floor Standing
Installation (Refer to Figure 003-11 through Figure 003-13).
(8) When the system is a...

Page 69

CHAPTER 3 ND-45492 (E)
Pag e 5 2
Revision 2.0
3. 19-Inch Rack-Mounting Installation
3.1. Single-PIM Installation
(1) Before mounting the PIM, connect the TOP COVER, BOTTOM COVER and AC CORD-A to the PIM as
shown in Figure 003-25.  The AC CORD-A is pre-installed with the BOTTOM COVER.
Figure 003-25  Connecting the Covers and AC CORD-A to the PIM
NAP 200-003
Sheet 30/37
Installation of Main Equipment
TOP COVER
TO PZ-PW86 PIM
AC CORD-A
BOTTOM COVER
LOCAL CABLE DUCT
PWR CA-A/BUS CABLE DUCT 

Page 70

ND-45492 (E) CHAPTER 3
Page 53
Revision 2.0
(2) Secure the 19” BRACKET to the 19-inch Rack as shown in Figure 003-26.
(3) Mount the PIM on the 19” BRACKET  as shown in Figure 003-26.
Then, secure the PIM to the 19” BRACKET as shown in Figure 003-26.
Figure 003-26  Mounting the PIM to the 19-Inch Rack (1 of 2)
NAP 200-003
Sheet 31/37
Installation of Main Equipment
A
B
C
A
BPIM 19” BRACKET
C
FRONT19” BRACKET19-INCH RACK
PIM BOTTOM COVER 