Home > Inter-Tel > Communications System > Inter-Tel Glx Plus Issue 2 Installation And Field Maintenance Manual

Inter-Tel Glx Plus Issue 2 Installation And Field Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Inter-Tel Glx Plus Issue 2 Installation And Field Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 31 Inter-Tel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION & MAINTENANCE TROUBLESHOOTING 
    Issue 2, June 1993 
    TROUBLESHOOTING 
    CONTENTS PAGE 
    1. Introduction ......................................................... 
    2. Troubleshooting Checklist ............................................. 
    3. Troubleshooting Charts ................................................ 
    A. Features ........................................................ 
    B. Intercom ........................................................ 
    C. CO Lines ........................................................ 
    D. Keysets ......................................................... 
    E. Single-Line Sets .................................................. 
    F. System Hardware ................................................ 
    4. Customer Support ................................................... 
    A. Technical Support ................................................ 
    B. Emergency Assistance ............................................. 
    5. Defective Unit Return Policy ........................................... 
    1. INTRODUCTION 
    1.1 This section describes the troubleshooting proce- 
    dures to follow in the event of a system or station instru- 
    ment malfunction. System repair is limited to replacing 
    paa -for example, KSU, Expansion PCB, Accessory 
    Port Module @PM), keysets, etc. 
    2. TROUBLESHOOTING CHECKLIST 
    2.1 Use this troubleshooting checklist before you start 
    the system troubleshooting procedures. It may save you 
    time and possibly eliminate the need for detailed 
    troubleshooting. 
    NOTE: In locations where there is low humidity, static 
    can build up. This often causes small shocks or sparks 
    when metal objects are touched. Although the internal 
    metal components of the system are well insulated, a 
    large static charge could cause an interruption in the sys- 
    tem’s digital signals. If this occurs, the system would 
    perform a reset, which may cause dropped calls or reset 
    features. If the KSU or keysets are located in high-static 
    areas, take precautions to eliminate the static. If prob- 
    lems persist, contact Inter-Tel’s Customer Support De- 
    partment. 
    (1) Is the problem caused by user errors? Use the 
    feature according to the instructions in the FEA- 
    TURES section of the manual. 
    6-l 
    6-l 
    6-3 
    6-3 
    6-3 
    6-3 
    6-3 
    6-4 
    6-4 
    6-19 
    6-19 
    6-19 
    6-19 
    (2) Has the equipment been disconnected? Are the 
    integrated circuits, PCBs, and equipment cables 
    securely seated and connected? Refer to 
    INSTALLATION for more information. 
    (3) Is the RUN LED flashing or unlit? 
    If the RUN LED does not light: 
    Check the AC fuse that is accessible from the 
    right side of the KSU. If open, replace it (2A, 
    25OV, slow-blow). 
    Check the breaker to the isolated, dedicated, 
    AC power source. If tripped, reset it. 
    Connector I7 on the Main Control PCB is not 
    connected properly. Refer to page 2-6 for the 
    location of the connector. 
    If the RUNLED isjlashing: 
    a. There may be insufficient voltage available 
    from the AC power source. Measure the AC 
    voltage. If it is low, contact an electrician. 
    b. If the AC Power is sufficient, there is a prob- 
    lem on the Main Control PCB. Replace the 
    K!W. 
    (4) If the problem involves a programmable feature, 
    place the PRG EN switch in the ON position and 
    check the ERROR LED for an indication of a 
    database error. (The ERROR LED will not flash 
    unless the PRG EN switch is ON.) 
    Page 6-l  
    						
    							TROUBLESHOOTING 
    Issue 2. June 1993 INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION L MAINTENANCE 
    NOTE: If the LED is not flashing, there may still 
    be an error. Place the PWR switch in the OFF 
    position for 10 seconds; then return it to the ON 
    position. (Turning the PWR switch off drops all 
    calls in progress.) If the LED flashes, a software 
    error has occurred. Follow the procedures given 
    below. 
    a. If the ERROR LED is flashing, an error has 
    occurred in the system. Count the number of 
    flashes between-the 3-second pauses. Refer to the chart below to determine the type of 
    error. 
    b. Initializing the system will cause the ER- 
    ROR LED to stop flashing for errors 6 and 7. 
    If you do not wish to initialize and prefer to 
    reprogram the affected area, manually stop 
    the flashing LED by placing the PRG EN 
    switch in the OFF position and then returning 
    it to the ON position. 
    FLASHES RESET INDICATION 
    1 ROM failure: A major system error has occurred. Place the PWR switch in the OFF position for 
    10 seconds, then return it to the ON position. If the flashing does not stop, replace the KSU. 
    6 System/station programming: An error has been detected in one of the database programming 
    areas. Either initialize the database or reprogram the areas that are affected. (User-programmable 
    features such as call forwarding and night ring mode can be corrected by the keyset user or atten- 
    dant.) Possible effects of the error include: 
    l All lines are subject to toll restriction. 
    l No line is programmed for call forward to the public network. 
    l Keyset options are incorrect.* 
    0 Ring-in assignments are incorrect.* 
    l Call forward mode is incorrect.* 
    l CO line restriction is incorrect.+ 
    l Timers, night ring mode, and the system toll restriction option have been returned to default status. 
    *Can affect more than one keyset. 
    7 System/station speed dialing: An error has been detected in one or more system or station speed- 
    dial numbers. The faulty number has been erased and can be reprogrammed by the attendant or the 
    keyset user. 
    8 Self-initialization: The software has performed a self-initialization. The software contains a self- 
    testing feature that will automatically initialize the system when the database is not readable. This 
    normally only occurs when the KSU power switch is first turned on and the PRG EN switch is in 
    the ON position, and before the database back-up battery is enabled. To stop the LED flash, make 
    sure the battery is enabled (paper is removed), and turn the PRG EN switch off, then on again. 
    Page 6-2  
    						
    							INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION & MAINTENANCE TROUBLESHOOTING 
    Issue 2, June 1993 
    3. TROUBLESHOOTING CHARTS 
    3.1 The simplified troubleshooting charts located on 
    the following pages list symptoms, possible causes, and 
    corrective actions for problems. Look up the problem in 
    the appropriate chart and perform the corrective actions 
    in the order given. The troubleshooting procedures for 
    correcting equipment failures have been divided into 
    the following six categories: 
    A. Features 
    B. Intercom Calls 
    C. CO Calls 
    D. Keysets 
    E. Single-Line Sets 
    F. System 
    NOTE: Throughout the troubleshooting section of the 
    manual, there are numerous references to replacing the 
    defective part and returning it for repair. However, 
    before returning any part, proper troubleshootingproce- 
    dures should be used to verify that the part is actually de- 
    fective. For example, if a keyset appears to be defective, 
    swap it with a “known good” keyset presently installed 
    in the system. If the problem follows the suspect keyset, 
    it can be considered defective. For more information on 
    returning defective equipment, refer to page 6-19. 
    Some of the probable causes and corrective actions 
    listed in the troubleshooting charts refer to the Expan- 
    sion PCB and the APM. These are applicable only if the 
    problem occurs at CO line 4, 5, or 6, or at sta- 
    tions18,19,20, or 21. 
    A. FEATURES 
    3.2 If the problem involves system features: 
    (1) Determine if the problem is due to user error. 
    Perform the procedures as described in the FEA- 
    TURES section. 
    (2) If the feature still does not operate properly, pro- 
    ceed to Figure 6-1, Feature Troubleshooting 
    Chart, on page 6-5. 
    3.3 The chart covers the following features: 
    l Cannot place a call on hold. 
    l Last number redial does not work. 
    l Speed-dial memory lost or not working. 
    l Headset enable, do-not-disturb, background music, 
    and call forwarding codes do not work. 
    0 Cannot initiate a conference. 
    0 Cannot initiate a page. 
    l 
    0 
    0 
    B. Call is not forwarded to the public network. Caller 
    hears fast busy signal. 
    Unable to interface with computer call-up device. 
    Call privacy release is inoperative. 
    INTERCOM 
    3.4 If the problem is associated with intercom calls 
    only, refer to Figure 6-2, Intercom Troubleshooting 
    Chart, on page 6-8. The chart covers the following fea- 
    tures: 
    0 
    0 
    C. No intercom dial tone. 
    Cannot place an intercom call. Intercom dial tone is 
    present. 
    CO LINES 
    3.5 If the problem is associated with outside calls 
    only, refer to Figure 6-3, CO Line Troubleshooting 
    Chart, on page 6-9. The chart covers the following fea- 
    tures: 
    0 
    l 
    l 
    l 
    0 
    0 
    l 
    D. CO lines will not ring for incoming calls. 
    CO line rings when a call is not ringing in. 
    Cannot obtain CO dial tone. 
    Cannot place an outgoing call. CO dial tone is pres- 
    ent and intercom works. 
    Other conversations can be heard on the line. 
    Outside call is dropped upon answering or during 
    conversation. 
    CO line is inoperative throughout the system. 
    KEYSETS 
    3.6 If the problem is associated with a single keyset, 
    refer to Figure 6-4, Keyset Troubleshooting Chart, on 
    page 6-11. The chart covers the following features: 
    0 Keyset does not receive intercom calls handsfree. 
    l Speakerphone not operating properly. 
    l Data noise heard through speakerphone or headset. 
    l Keyset has no power. 
    l Keyset squeals on outgoing calls or when receiving a 
    handsfree call from a single-line station. 
    0 Data device connected to keyset not operating prop- 
    erly. 
    0 LRA device connected to keyset not operating prop- 
    erly. 
    Page 6-3  
    						
    							TROUBLESHOOTING 
    Issue 2, June 1993 INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION & MAINTENANCE 
    E. SINGLE-LINE SETS 
    3.7 If the problem is associated with a single-line set, 
    refer to Figure 6-5, Single-Line Set Troubleshooting 
    Chart, on page 6-14. The troubleshooting charts cover 
    the following features: 
    Single-line set is completely inoperative. 
    Single-line set inoperative; talk battery is present. 
    Single-line set inoperative; calls ring in; talk battery 
    is present. 
    Single-line set receives CO’ ring-in, but cannot 
    answer the call. 
    Single-line set drops calls when transferring them or 
    placing them on hold. 
    DTMF digits dialed at single-line set cannot be 
    detected by telco and/or other stations 
    l Intercom call to single-line set rings with CO ring 
    cadence, not intercom ring cadence 
    F. SYSTEM HARDWARE 
    3.8 If the problem appears throughout the system, re- 
    fer to Figure 6-6, System Troubleshooting Chart, on 
    page 6-16. The troubleshooting charts cover the follow- 
    ing features: 
    All stations in the system are inoperative. No LEDs 
    light when a CO line key is pressed. 
    Several keysets are inoperative. No LEDs light 
    when a CO line key is pressed. 
    The single-line sets are inoperative. 
    Music-on-hold is not present when an outside call is 
    placed on hold. 
    Repeated occurrence of dropped calls. 
    RIVEMI present over conversations. 
    _’ 
    Page 6-4  
    						
    							INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION & MAINTENANCE TROUBLESHOOTING Issue 2, June 1993 
    FIGURE 6-l. FEATURE TROUBLESHOOTING CHART 
    PROBABLE CAUSE 
    User error 
    Defective station instrument 
    Defective Expansion PCB or 
    APM 
    Defective Main Control 
    PCB 
    SYMPTOM 
    Last number redial does not 
    vork 
    Speed-dial memory lost or 
    not working 
    PROBABLE CAUSE 
    User error 
    Dialing speed too fast for 
    PBX or central office 
    Defective keyset 
    Defective Expansion PCB or 
    APM 
    Defective Main Control 
    PCB 
    CORRECTIVE ACTION 
    I 
    Refer to page 4-22. 
    I 
    Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or reulace the station instrument. 
    I 
    Replace Expansion PCB or APM. 
    Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    I 
    CORRECTIVE ACTION 
    Refer to page 4-33. 
    Change the memory-dial speed timer to 0.2.. Refer 
    to page 5-11. 
    Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or replace the station instrument. 
    Replace Expansion PCB or APM. 
    Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    I SYMPTOM PROBABLE CAUSE 
    I CORRECTIVE ACTION 
    I 
    User error 
    Dialing speed too fast for 
    PBX or Central Office 
    System error has occurred 
    Defective keyset 
    Defective Main Control 
    PCB Refer to page 4-32. 
    Change the memory-dial speed timer to 0.2. Refer 
    to page 5-11. 
    Check the ERROR LED according to the instruc- 
    tions on page 6-l. 
    Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or replace the station instrument. 
    Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    PROBABLE CAUSE CORRECTIVE ACTION 
    PRG EN switch is in the ON PRG EN switch must be in the OFF position to 
    position enter these feature codes. 
    Page 6-5  
    						
    							TROUBLESHOOTING Issue 2, June 1993 INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION dz MAINTENANCE 
    FIGURE 6-l. FEATURE TROUBLESHOOTING CHART (CONT’D) 
    SYhlPTOM PROBABLE CAUSE 
    Zannot initiate a conference User error 
    Conference circuits are busy 
    Intercom channels are busy 
    Defective station instrument 
    Defective Expansion PCB or 
    CORRECTIVE ACTION 
    I 
    Refer to page 4-30. 
    I 
    There are two conference circuits. When both are 
    busy, the initiating party hears a busy signal. In- 
    side parties are disconnected and outside parties 
    are placed on individual hold. 
    The initiating party must hang up and try again 
    before adding an intercom call to the conference. 
    Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or replace the station instrument. 
    Replace Expansion PCB or APM. 
    Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    SYMPTOM I PROBABLE CAUSE 
    I CORRECTIVE ACTION 
    Cannot initiate a page I User error 
    All stations in the paging Refer to page 4-25, for correct procedures. 
    Reorder tone is heard. Wait several seconds and 
    then attempt to place the page again. 
    Reorder tone is heard if all stations in the zone are 
    in do-not-disturb. 
    I 
    I 
    All stations in the paging 
    zone are in do-not-disturb 
    Another external zone page 
    is being made Reorder tone is heard. Wait several seconds and 
    then attempt to place the page again. Only one 
    external zone 
    page can be made at a time. 
    Reprogram keysets to receive incoming pages (re- 
    fer to page 5-13).  All keysets have keyset op- 
    tion 1 enabled 
    Defective station instrument 
    Defective Expansion PCB or 
    APM - 
    Defective Main Control 
    PCB Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or replace the station instrument. 
    Replace Expansion PCB or APM. 
    Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    Page 6-6  
    						
    							INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION & MAINTENANCE TROUBLESHOOTJNG 
    Issue 2, June 1993 
    FIGURE 6-l. FEATURE TROUBLESHOOTING CHART (CONT’D) 
    SYMPTOM 
    Call is not forwarded to pub- 
    lic network. Caller hears fast 
    busy signal. 
    PROBABLE CAUSE CORRECTIVE ACTION 
    Call is toll-restricted or line If both station instruments are toll-restricted or 
    is restricted 
    restricted from accessing the CO line, the call is 
    restricted. 
    Line is not programmed for A CO line must be programmed as the call for- 
    call forwarding ward to the public network line. Refer to page 
    5-11. 
    Call forward line is busy 
    Forward requests form a 
    loop Caller must hang up and try call again later. 
    If call forward requests form a loop (station instru- 
    merits are forwarded to each other), incoming calls 
    will not be forwarded. 
    Station instrument not pro- 
    grammed correctly Refer to page 4-26 for correct procedure. 
    SYMPTOM 
    Unable to interface with 
    computer call-up device 
    (banking machine, answer- 
    ing machine, auto dialer, 
    etc.) 
    I PROBABLE CAUSE 
    I 
    Equipment being called is 
    defective 
    DTMF digit duration/pause 
    specifications of called 
    equipment is incompatible 
    with GLX-Plus System 
    Defective Expansion PCB or 
    Defective Main Control 
    SYMPTOM 
    I PROBABLE CAUSE 
    Call privacy release inopera- User error 
    .~ 
    Programming error 
    CORRECTIVE ACTION 
    Ensure that the called equipment is functioning 
    correctly. 
    Check with the equipment manufacturer for 
    DTMF digit duration/pause specifications. Adjust 
    memory-dial speed timer. Refer to page 5-11. 
    CO trunk must be designated as DTMF. Refer to 
    page 5-11. 
    Replace Expansion PCB or APM. 
    Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    J 
    CORRECTWE ACTION 
    Keyset user must lift the handset or press the ON/ 
    OFF key before pressing the busy CO line 
    key. 
    Refer to page 4-29 for information on call privacy 
    and privacy release. 
    I 
    Verify that system-wide CO privacy release option 
    is enabled. See page 5-11. 
    I 
    Page 6-7  
    						
    							TROUBLESHOOTING 
    Issue 2, June 1993 INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION & MAINTENANCE 
    FIGURE 6-2. INTERCOM TROUBLESHOOTING CHART 
    NOTE: These symptoms are isolated to one station instrument only. For identical problems involving more than one 
    station instrument, refer to Figure 6-6, System Troubleshooting Chart, on page 6-16. 
    SYMPTOM 
    No intercom dial tone 
    PROBABLE CAUSE 
    Defective station cabling 
    Defective station instrument 
    Defective Expansion PCB or 
    APM 
    Defective Main Control 
    PCB 
    CORRECTIVE ACTION 
    Check cable connections. 
    Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or replace the station instrument. 
    Replace Expansion PCB or APM. 
    Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    SYMPTOM 
    I PROBABLE CAUSE 
    Cannot place intercom call. 
    Intercom dial tone is pres- 
    ent. 
    CORRECTIVE ACTlON 
    I 
    Verify that a valid and equipped intercom number 
    was dialed (10-21). / 
    Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or replace the station instrument. 
    , Replace Expansion PCB or APM. 
    Defective Main Control 
    PCB Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    Page 6-8  
    						
    							INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION & MAINTENANCE TROUBLESHOOTING 
    Issue 2, June 1993 
    FIGURE 6-3. CO LINE TROUBLESHOOTING CHART 
    SWJPTOM PROBABLE CAUSE 
    ZO lines will not ring for in- CO ring duration timer is set 
    :oming calls too long 
    CORRECTIVE ACTION 
    Attach a lineman’s test set to one of the lines at the 
    RJ connector. Place an outgoing call that will ring 
    in on the line with the test set. Check for ring sig- 
    nal. If you hear ring signal, set the timer to a short- 
    er duration. Refer to page 5-11. If you do not hear 
    ring signal, notify the telephone company. (The 
    minimum ringing voltage the system will recog- 
    nize is 40VAC.) 
    SYMPTOM 
    I PROBABLE CAUSE 
    I CORRECTIVE ACTION 
    I 
    CO line rings when a call is CO ring duration timer is set 
    not ringing in (false ring-in) too short 
    SYMPTOM 
    Cannot obtain CO dial tone 
    PROBABLE CAUSE 
    Station has been restricted 
    from CO line(s) for placing 
    calls 
    Central office is not supply- 
    ing dial tone 
    Defective station instrument 
    CO line(s) disconnected 
    Defective Expansion PCB or 
    APM 
    Defective Main Control 
    PCB Noise on the CO line is causing false ring-in. Set 
    the timer to a longer duration. Refer to page 5-11. 
    CORRECTIVE ACTION 
    Check the programming for the station and repro- 
    gram is necessary. Refer to page 5-13. 
    Attach a lineman’s test set to each line at the RJ 
    and check for CO dial tone. If not present, contact 
    the telephone company. 
    Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or replace the station instrument. 
    Check every CO line connection between the RJ 
    and the KSU. 
    Replace Expansion PCB or APM. 
    Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    I SYMPTOM 
    I PROBABLE CAUSE 
    I CORRECTIVE ACTION 
    Cannot place an outside call. CO line uses dial-pulse sig- 
    CO dial tone is present and nal 
    intercom works. 
    Keyset is toll restricted 
    (keyset option 6 enabled) 
    Defective station instrument 
    Defective Expansion PCB or 
    APM 
    Defective Main Control 
    PCB When the system is initialized, all CO lines are 
    designated as DTMP lines. One or more lines can 
    be converted to dial-pulse through programming. 
    See pages 5-10 and 5-11. 
    Check the programming for the keyset and repro- 
    gram if necessary (refer to page 5-13). 
    Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or replace the station instrument. 
    Replace Expansion PCB or APM. 
    Replace KSU or contact Inter-Tel Customer Sup- 
    oort for assistance. 
    Page 6-9  
    						
    							THOUBLESHOOTING 
    Issue 2, June 1993 INTER-TEL PRACTICES 
    GLX-PLUS INSTALLATION & MAINTENANCE 
    FIGURE 6-3. CO LINE TROUBLESHOOTING CHART (CONT’D) 
    SYMPTOM 
    Other conversations can be 
    heard on the line (crosstalk) 
    I 
    PROBABLE CAUSE 
    Defective CO line(s) 
    CO lines miswired 
    Defective Expansion PCB or 
    APM 
    Defective Main Control 
    PCB 
    SYMPTOM 
    I PROBABLE CAUSE 
    Outside call dropped upon 
    answering or during con- 
    versation 
    Database error 
    I IAPM - 
    CORRECTIVE ACTION 
    I 
    Attach a lineman’s test set to each line at the RJ 
    connector and check for cross-talk. If present, con- 
    tact the telephone company. 
    Check every CO line connection between the RJ 
    connector and the KSU. 
    Replace Expansion PCB or APM 
    Replace KSU or contact Inter-Tel Customer Sup 
    oort for assistance. 
    CORRECTIVE ACTION 
    I 
    Pressing a line key after the connection has been 
    made will automatically drop the call in progress 
    and reseize that CO line. 
    The system counts the number of digits dialed 
    when the station instrument is toll restricted. If the 
    user dials more digits than are allowed by toll re- 
    striction, the call will be dropped (even if the call 
    is in progress). 
    Refer to the ERROR LED procedures on page 
    6-l. I 
    Perform GLX-Plus Keyset self-test (see page 
    3-24) and/or replace the station instrument. I 
    Replace Expansion PCB or APM. 
    Replace KSU or contact Inter-Tel Customer 
    SUP- 1 
    port for assistance. I  Defective Main Control 
    PCB 
    SYMPTOM 
    CO line is inoperative 
    throughout the system 
    PROBABLE CAUSE CORRECTIVE ACTION 
    Defective CO line from ten- Attach a lineman’s test set the line at the RJ con- 
    tral office nectar and check for CO dial tone. If not present, 
    contact the telephone company. 
    CO lines miswired Check CO line connections between the RJ and 
    the KSU. 
    All station instruments have Check programming for every station and repro- 
    been restricted from acces- gram if necessary. Refer to page 5-13. 
    sing CO line 
    Defective or missing Expan- Replace or install Expansion PCB or APM. 
    sion PCB or APM 
    Defective Main Control 
    PCB Replace KSU or contact Inter-Tel Customer Sup- 
    port for assistance. 
    Page 6-10  
    						
    All Inter-Tel manuals Comments (0)

    Related Manuals for Inter-Tel Glx Plus Issue 2 Installation And Field Maintenance Manual