D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 81 Bosch Security Systems | 1/04 | 47775E 4.1.1 Point Responses Applications for Point Responses 9, D, and E: Combine Point Responses 9, D, and E with Perimeter point types to create more flexible 24-hour protection. Unlike 24-hour points, a faulted Perimeter point with a Point Response of D and E displays at the command center when arming. Like a 24- hour point, a point programmed this way can generate alarms whether the area is armed or disarmed....
Page 82
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 82 Bosch Security Systems | 1/04 | 47775E P## Pt Response Default:See Program Record Sheet Selection:0 to F Controlled (Non-24-Hour Points) Point Response 0123456789ABCDEF Armed OpenIIIIDDIIDIIIIIT Armed ShortIIIIIIDDDIIIIII Disarmed OpenTT TIITIT Disarmed ShortTT T ITI I 24-Hour Points Point Response 0123456789ABCDEF Open ITIT ITSTS S Short I I T T I T T S S S Key: I = Instant alarm D = Delayed alarm T = Trouble S = Supervisory Blank =...
Page 83
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 83 Bosch Security Systems | 1/04 | 47775E P## Entry Delay Default:See Program Record Sheet Selection:5 seconds to 600 seconds Use this option to enter the amount of entry delay time that a user has after faulting a Controlled point ( P## Type 1, 2, 3) with a delayed response (D) ( P## Pt Response) of 4, 5, 6, 7, or 8. DISARM NOW displays for the duration of the time programmed when the point is faulted in the delay condition. 0101 0101 0101Beginning...
Page 84
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 84 Bosch Security Systems | 1/04 | 47775E If the point restores and the fire alarm is not silenced from the command center, the fire alarm output continues until Fire Bell time expires. If the point does not restore, the fire alarm output continues even after bell time expires.\ Use this option for fire applications to meet the requirement that audible alarms cannot be silenced until the fault condition clears or the Fire Bell time expires. P##...
Page 85
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 85 Bosch Security Systems | 1/04 | 47775E P## Buzz On Fault Default:Blank Selection:Blank, 1 to 3 Selection Operation for Controlled Points (Point Types 1, 2, and 3)Operation for 24-hour Points (Point Type 0) Blank The point only generates a buzz at the command center if it goes into the trouble condition indicated in the P## Point Response.Same 1 The point generates a Buzz Until Restore at the command center for any fault condition while the point...
Page 86
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 86 Bosch Security Systems | 1/04 | 47775E P## RlyResp Type Default:See Program Record Sheet Selection:Blank, 1 to 2 Blank Point state does not affect the operation of the corresponding relay. 1 Relay Follow Point: The relay corresponding with this point activates when the point is faulted to any off normal condition. The relay automatically resets when the point is returned to normal. 2 Relay Latches: The relay corresponding with this point latches...
Page 87
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 87 Bosch Security Systems | 1/04 | 47775E *Restoral Reports are still transmitted if the alarm, trouble, or bypass (by Sked, RAM, or Swinger bypass) condition occurred when the area disarmed, and the point restored. Allows a controlled point (P## Type 1, 2, 3), to report Alarms, Troubles, and Restoral Reports only when the area is disarmed. This prompt does not affect local annunciation. Local While Armed suppresses all reports from 24-hour points....
Page 88
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 88 Bosch Security Systems | 1/04 | 47775E P## Bypassable Default:No Selection:Yes or No Yes This point can be bypassed and force armed. No This point cannot be bypassed or force armed from the command center or RAM. However, it can be force armed by automatic arming at the end of the Closing Window (see the A# Auto Close prompt in Section 2.9.5 Open/Close Options) or by a Sked programmed to arm the area. Use this option to allow this point to be...
Page 89
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 89 Bosch Security Systems | 1/04 | 47775E P## Defer BP Report Default:No Selection:Yes or No Yes Send a Point Bypass Report with the Closing Report instead of a Command Bypass Report when a user bypasses the point. No Do not defer Bypass Reports. Use this option to prevent (P## Type 0 to F) points that are bypassed by the user (COMMAND BYPASS) from occurring until the area is armed. Once the area is armed, the bypassed points and any point being...
Page 90
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 90 Bosch Security Systems | 1/04 | 47775E P## Fire Point Default:No Selection:Yes or No Yes This point is a Fire point. No This point is not a Fire point. Use this option to make a 24-hour point a Fire point. This option makes this point the highest priority event in the control panel when an alarm occurs for both reporting and displaying on the command center. Characteristics of a Fire Point Reporting: When a group of events occur, the control...
All Bosch manuals