Page 81

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 81
Bosch Security Systems | 1/04 | 47775E
4.1.1 Point Responses
Applications for Point Responses 9, D,
and E:
Combine Point Responses 9, D, and E with
Perimeter point types to create more flexible
24-hour protection. Unlike 24-hour points, a
faulted Perimeter point with a Point
Response of D and E displays at the
command center when arming. Like a 24-
hour point, a point programmed this way can
generate alarms whether the area is armed
or disarmed....

Page 82

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 82
Bosch Security Systems | 1/04 | 47775E
P## Pt Response
Default:See Program Record Sheet
Selection:0 to F
Controlled (Non-24-Hour Points)
Point Response 0123456789ABCDEF
Armed OpenIIIIDDIIDIIIIIT
Armed ShortIIIIIIDDDIIIIII
Disarmed OpenTT TIITIT
Disarmed ShortTT T ITI I
24-Hour Points
Point Response 0123456789ABCDEF
Open ITIT ITSTS S
Short I I T T I T T S S S
Key:  I = Instant alarm
D = Delayed alarm
T = Trouble
S = Supervisory
Blank =...

Page 83

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 83
Bosch Security Systems | 1/04 | 47775E
P## Entry Delay
Default:See Program Record Sheet
Selection:5 seconds to 600 seconds
Use this option to enter the amount of entry delay
time that a user has after faulting a Controlled point
(
P## Type 1, 2, 3) with a delayed response (D)
(
P## Pt Response) of 4, 5, 6, 7, or 8. DISARM NOW
displays for the duration of the time programmed
when the point is faulted in the delay condition.
0101
0101
0101Beginning...

Page 84

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 84
Bosch Security Systems | 1/04 | 47775E
If the point restores and the fire alarm is
not silenced from the command center,
the fire alarm output continues until Fire
Bell time expires. If the point does not
restore, the fire alarm output continues
even after bell time expires.\
Use this option for fire applications to meet
the requirement that audible alarms cannot
be silenced until the fault condition clears
or the Fire Bell time expires.
P##...

Page 85

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 85
Bosch Security Systems | 1/04 | 47775E
P## Buzz On Fault
Default:Blank
Selection:Blank, 1 to 3
Selection Operation for Controlled Points
(Point Types 1, 2, and 3)Operation for 24-hour Points
(Point Type 0)
Blank
The point only generates a buzz at the command
center if it goes into the trouble condition
indicated in the P## Point Response.Same
1 The point generates a Buzz Until Restore at the
command center for any fault condition while the
point...

Page 86

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 86
Bosch Security Systems | 1/04 | 47775E
P## RlyResp Type
Default:See Program Record Sheet
Selection:Blank, 1 to 2
Blank Point state does not affect the operation
of the corresponding relay.
1
Relay Follow Point: The relay
corresponding with this point activates
when the point is faulted to any off
normal condition. The relay
automatically resets when the point is
returned to normal.
2
Relay Latches: The relay
corresponding with this point latches...

Page 87

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 87
Bosch Security Systems | 1/04 | 47775E
*Restoral Reports are still transmitted if the alarm,
trouble, or bypass (by Sked, RAM, or Swinger bypass)
condition occurred when the area disarmed, and the
point restored.
Allows a controlled point (P## Type 1, 2, 3), to
report Alarms, Troubles, and Restoral Reports only
when the area is disarmed. This prompt does not
affect local annunciation.
Local While Armed suppresses all reports
from 24-hour points....

Page 88

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 88
Bosch Security Systems | 1/04 | 47775E
P## Bypassable
Default:No
Selection:Yes or No
Yes This point can be bypassed and force
armed.
No
This point cannot be bypassed or force
armed from the command center or
RAM. However, it can be force armed
by automatic arming at the end of the
Closing Window (see the 
A# Auto
Close
 prompt in Section 2.9.5
Open/Close Options) or by a Sked
programmed to arm the area.
Use this option to allow this point to be...

Page 89

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 89
Bosch Security Systems | 1/04 | 47775E
P## Defer BP Report
Default:No
Selection:Yes or No
Yes Send a Point Bypass Report with the
Closing Report instead of a Command
Bypass Report when a user bypasses
the point.
No Do not defer Bypass Reports.
Use this option to prevent (P## Type 0 to F) points
that are bypassed by the user (COMMAND
BYPASS) from occurring until the area is armed.
Once the area is armed, the bypassed points and any
point being...

Page 90

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 90
Bosch Security Systems | 1/04 | 47775E
P## Fire Point
Default:No
Selection:Yes or No
Yes This point is a Fire point.
No This point is not a Fire point.
Use this option to make a 24-hour point a Fire point.
This option makes this point the highest priority
event in the control panel when an alarm occurs for
both reporting and displaying on the command
center.
Characteristics of a Fire Point
Reporting:  When a group of events
occur, the control...