Page 121

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 121
Bosch Security Systems | 1/04 | 47775E
In order to use an off-the-shelf external modem and a D9133DC serial module to connect to the control
panel using RAM, use the following settings:
1. RADXAUX1\ENHANCED COMM\Enhanced Comm\No
2. RADXAUX1\SDI RAM PARAMETERS\Enable SDI RAM\Yes
3. RADXAUX1\SDI RAM PARAMETERS\Callback Enabled\No
4. RADXAUX1\SDI RAM PARAMETERS\RAM IP Address 1-4\0
5. RADXAUX1\SDI RAM PARAMETERS\Enable Ext Modem\Yes
6. RADXAUX1\SDI...

Page 122

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 122
Bosch Security Systems | 1/04 | 47775E
Enable Ext Modem
Default:No
Selection:Yes or No
Yes Enable SDI Address 88 for use with an
external modem.
No
Disable SDI Address 88 for use with an
external modem.
Setting this item to Yes instructs the control panel
that SDI Address 88 is enabled for use with an
external modem. For further information on Local
RPS programming, see the RPS Operation Manual.
Setting this item to Yes disables
Enhanced...

Page 123

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 123
Bosch Security Systems | 1/04 | 47775E
Enhanced Comm
Default:No
Selection:Yes or No
Yes Enable enhanced communications over
the SDI bus.
No
Do not enable enhanced
communications over the SDI bus.
Determines if the control panel allows enhanced
communications over the SDI bus.
0101
0101
0101Modem Format must be set to Yes when
using enhanced communications.
Enable Ext Modem must be set to No if
enhanced communications are to be
used.
Enhanced Comm...

Page 124

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 124
Bosch Security Systems | 1/04 | 47775E
This prompt and the next two prompts determine
how the SDI Path is supervised between the SDI
device and the central station(s). Do not confuse with
the supervision of the SDI device (the connection of
the SDI device to the 9000 series control panel).
Each SDI Path can be configured to transmit a
Heartbeat Event to the central station for supervision
purposes. This ensures the integrity of the
connection at...

Page 125

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 125
Bosch Security Systems | 1/04 | 47775E
Once the control panel receives acknowledgement
from the central station, the control panel returns to
the normal Poll Rate (which, in this example is 120
seconds).
If more than one SDI Path is used, the control panel
handles them on a successive basis. For example, if
acknowledgement from SDI Path 1 is not received
within 10 seconds (using the previous example), the
control panel moves to SDI Path 2 to send...

Page 126

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 126
Bosch Security Systems | 1/04 | 47775E
Parity/Stop
Default:No/1
Selection:No/1, No/2, Odd/1, Even/1
No/1 No parity, 1 stop bit.
No/2 No parity, 2 stop bits.
Odd/1 Odd parity, 1 stop bit.
Even/1 Even parity, 1 stop bit.
This prompt addresses two items: Parity and the
number of stop bits for the D9133TTL-E. Pressing
the [SPACE] bar on the D5200 toggles through the
available options.
This item must be set to No/1 when using
the External Modem...

Page 127

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 127
Bosch Security Systems | 1/04 | 47775E
RG# 1 Attempt
Default:No
Selection:Yes or No
Yes This route group attempts the primary
destination once and, if unsuccessful,
attempts the backup destination. The
control panel still makes a total of ten
attempts (five to the primary, five to
the backup) before generating a route
group Comm Fail Event.
No This route group attempts the primary
destination twice and, if unsuccessful,
attempts the backup...

Page 128

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 128
Bosch Security Systems | 1/04 | 47775E
This item determines if a fire trouble condition,
previously acknowledged and silenced at a
command center, automatically (locally) resounds
the fire trouble tone at 12:00 PM, 12:00 AM, or not
at all if the point is still in an off-normal state. Events
are not generated at the time resound occurs.
6.8 Cross Point Parameters
This section discusses the requirements necessary to
program Cross Point functions....

Page 129

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 129
Bosch Security Systems | 1/04 | 47775E
Conversely, if a single Cross Point detects an alarm,
then restores, and no other conditions occur, an
Unverified Event is generated for that point. A
second alarm on the first point does not create an
Alarm Event but rather an Unverified Event.
Section 2.3 Routing determines whether these events
are transmitted to a central station. An Unverified
Event does not produce a corresponding Restoral
Event.
The...

Page 130

D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1EN | 130
Bosch Security Systems | 1/04 | 47775E
Notes 