D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 91 Bosch Security Systems | 1/04 | 47775E P## Alarm Verify Default:See Program Record Sheet Selection:Yes or No Yes Enable alarm verification on this point. Alarm verification points must be programmed as resettable. No Disable alarm verification on this point. Use this option only with Fire points to designate them for alarm verification. When an Alarm Verification point goes into alarm, the control panel removes power to all Resettable points for...
Page 92
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 92 Bosch Security Systems | 1/04 | 47775E P### Point Index Default:See Program Record Sheet Selection:Blank (00) to 31 This entry selects one of the 31 P## Index codes that define the point’s characteristics and determines how the control panel responds to various point conditions. Blank (00) disables the point. Missing Point Reports occur if a point address does not exist for a point assigned a point index. Extra Point Events occur if more than two...
Page 93
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 93 Bosch Security Systems | 1/04 | 47775E P### BFSK/Relay Default:See Program Record Sheet Selection:0 to 9 Use this option to: 2. Determine the point number reported in BFSK when this point is tripped. 3. Activate a relay when the point goes into an alarm condition, even if the control panel is programmed for Modem reporting as shown in Table 29. BFSK/Relays do not activate for Fire Supervisory or Non-Fire Supervisory points. Table 29: P###...
Page 94
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 94 Bosch Security Systems | 1/04 | 47775E 4.3 COMMAND 7 and COMMAND 9 These entries assign point indexes, BFSK report code, BFSK relay that trips, and the text for the COMMAND 7 and COMMAND 9 command center functions. CMD7 Point Index Default:31 Selection:Blank (00) to 31 This entry selects one of the 31 P## Index codes that define how the control panel reacts when a COMMAND 7 is initiated. 0101 0101 0101The point index code used for COMMAND 7 must...
Page 95
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 95 Bosch Security Systems | 1/04 | 47775E 5.0 RADXSKED 5.1 Windows Use this programming module to define the windows for Opening and Closing and User Access. 5.1.1 Opening and Closing Use these windows to set a schedule for disarming and arming. The disarming and arming schedules provide several independent features: • Suppress normal Opening and/or Closing Reports when A# Disable O/C in Windows is programmed Yes. • Generate a Fail to Open Report if...
Page 96
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 96 Bosch Security Systems | 1/04 | 47775E W# Monday Default:No Selection:Yes or No W# Tuesday Default:No Selection:Yes or No W# Wednesday Default:No Selection:Yes or No W# Thursday Default:No Selection:Yes or No W# Friday Default:No Selection:Yes or No W# Saturday Default:No Selection:Yes or No W# Open Early Begin Default:00:00 Selection:HH:MM (hours and minutes) 00:00 to 23:59 Open Early Begin: This program item is one of three required to create an...
Page 97
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 97 Bosch Security Systems | 1/04 | 47775E W# Open Window Stop Default:00: 00 Selection:HH:MM (hours and minutes) Enter the time you want the control panel to end the Opening Window. The window stops at the end of the minute. 00:00 is midnight, 23:59 is 11:59 PM Make entries using a 24-hour clock (for example, 7:00 AM is entered as 07:00, 2:45 PM is entered as 14:45). This program item is one of three required to create an Opening Window. To program...
Page 98
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 98 Bosch Security Systems | 1/04 | 47775E Table 32: Programming for Two Same Day Opening Windows (see Figure 4) Open Close W# Day of Week Early BeginStart StopEarly BeginStart StopeXcept On HolidayHoliday Index Area(s) 1S M T W T F S06: 0007 : 0008: 00Yes / No1 2 3 41 2 3 4 5 6 7 8 2 S M T W T F S13 : 00 14 : 00 15 : 00 Yes / No1 2 3 4 1 2 3 4 5 6 7 8 Do not program a single window to cross the midnight boundary....
Page 99
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 99 Bosch Security Systems | 1/04 | 47775E Disable/Restart the control panel to activate today’s window. If you are programming a window that needs to activate on the same day that you are programming it, do a disable/restart after programming. W# Close Window Start Default:00: 00 Selection:HH:MM (hours and minutes) Enter the time that you want the control panel to start the Closing Window. The window goes into effect at the beginning of the minute....
Page 100
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 100 Bosch Security Systems | 1/04 | 47775E W# Xept Holiday Default:No Selection:Yes or No Yes Do not activate this window on holidays. To use this selection, the window must be programmed to activate on at least one day of the week and a Holiday Index must be enabled. No A holiday does not prevent this window from activating. You also use this selection if Opening and/or Closing Windows are only needed on certain days of the year. Do not program the...