D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 61 Bosch Security Systems | 1/04 | 47775E To Walk Test a Door point connected to a D9210B Access Interface Module, the door must be opened without activating the door sequence or allowing it to time out past the extended shunt time. L## Fire Test Default:See Program Record Sheet Selection:Blank or E #12 Fire Test [COMMAND][5][8] Initiate a Fire Walk Test for all 24-hour points in the area where this command center is assigned. When a Fire Test is...
Page 62
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 62 Bosch Security Systems | 1/04 | 47775E L## Unlock Door Default:See Program Record Sheet Selection:Blank or E Unlock Door (MENU FUNCTION only) Press the command center number keys [1] through [8] that correspond to the door number to unlock/relock doors. For example, pressing [2] and [ENTER] unlocks door number 2, which is indicated by U in the display. Unlock Door allows the user with this authority level to access the UNLOCK? 12345678 function....
Page 63
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 63 Bosch Security Systems | 1/04 | 47775E L## Chg Display Default:See Program Record Sheet Selection:Blank or E #15 Change Display [COMMAND][4][9] Change the display (bright display, dim display, and time display) in the area where this command center is assigned. L## Chg Time/Date Default:See Program Record Sheet Selection:Blank or E #16 Change Time and Date [COMMAND][4][5] Change the date and time for the control panel in this area. L## Chg...
Page 64
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 64 Bosch Security Systems | 1/04 | 47775E L## User Cmd 9 Default:See Program Record Sheet Selection:Blank or E #24 User COMMAND 9 [COMMAND][9] Can be used in Function Menu. Generate the alarm programmed at COMMAND 9 in the RADXPNTS Handler. L## Bypass a Pt Default:See Program Record Sheet Selection:Blank or E #25 Bypass a Point [COMMAND][0] Bypass points with this authority level L## Unbypass a Pt Default:See Program Record Sheet Selection:Blank or...
Page 65
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 65 Bosch Security Systems | 1/04 | 47775E - D1255 command center displays a sequential count after each point is activated and restored as well as the text for the point. - The D1255 command center displays ALL PNTS TESTED. - If enabled in Routing, Service Start and Service End are reported at the central station receiver for the beginning and end of the test. Point 128 and Point 248 appear as missing. This is normal. These points are used for...
Page 66
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 66 Bosch Security Systems | 1/04 | 47775E L## Passcode Disarm Default:See Program Record Sheet Selection:Blank or E Disarm an area by entering a passcode and pressing [ENTER]. Access Control Levels L## Security Level Default:See Program Record Sheet Selection:M, P, D, or Blank M Users have access rights for this area when the area is in any armed state. P Users have access rights for this area when the area is Perimeter Armed or disarmed but not...
Page 67
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 67 Bosch Security Systems | 1/04 | 47775E 2.12 Function List The Function List is accessed when the user presses [MENU] (or the key corresponding to menu) on the D1260) while the command center is displaying the idle text. Up to 32 functions M### Function(s) can be programmed. Each CC # command center address can display a combination of all/each of the 32 menu items. The D1255 displays one menu item at a time. The D1260 displays up to two menu items...
Page 68
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 68 Bosch Security Systems | 1/04 | 47775E • Relay Reports: When relay activity is reported to the receiver (see Section 2.3 Routing), on-board relays are reported as follows: A = 253, B = 254, C = 255. The others report as 001 to 128. The Relay Report is RELAY SET RELAY # rrr when the relay is turned on and RELAY RESET RELAY # rrr when the relay is turned off. Relay Reports are also printed on the local printer and stored in the control panel memory...
Page 69
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 69 Bosch Security Systems | 1/04 | 47775E A# Fire Bell Default:A Selection:Blank, 1 to 128 (1 to 64 for D7412G), A, B, or C This voltage output relay activates and provides 12 VDC output when a Fire point ( P## Fire is Yes) assigned to this area goes into alarm. 0101 0101 0101Fire Time and Fire Pat must be programmed in Bell Parameters. This relay activates according to the bell pattern and remains active until the bell time expires. P## Silent Bell...
Page 70
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 70 Bosch Security Systems | 1/04 | 47775E A# Area Armed Default:Blank Selection:Blank, 1 to 128 (1 to 64 for D7412G), A, B, or C Activates when the specified area becomes master armed (exit delay must expire before the relay activates). The relay remains activated until the area is disarmed. It does not deactivate during the entry delay time. If multiple areas use the same relay, the relay activates when all areas are armed. It deactivates when the...