Page 11

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 11
Bosch Security Systems | 1/04 | 47775E
2.0 9000MAIN
Use this programming module to define the
operating characteristics that affect panel-wide
functions. There are nine programming categories in
this module: Phone, Phone Parameters, Routing,
Enhanced Communications, Area Parameters,
Command Center, User Interface, Function List, and
Relay Parameters.
2.1 Phone
The control panel can dial up to four different
telephone numbers when sending event...

Page 12

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 12
Bosch Security Systems | 1/04 | 47775E
2.2 Phone Parameters
The program items in this category describe panel-
wide characteristics for telephone dialing, receiver
format, and supervision.
Modem Format
Default:Yes
Selection:Yes or No
Yes
Radionics’ Modem IIIa2
Communication Format: Reports
identify points as 001 through 247 and
passcode User ID codes as 000 through
249 at the D6500/D6600 Receiver
(unless 
Point/User Flag is
programmed Yes; see the...

Page 13

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 13
Bosch Security Systems | 1/04 | 47775E
Table 6: Modem IIIa2 Communication Format
Data - User ID Numbers
Point/User Flag
NOPoint/User Flag
YES
000000
001 to 005 001 to 005
006 to 013601 to 608
014 to 021 701 to 708
022 to 029801 to 808
030 to 037 B01 to B08
038 to 045C01 to C08
046 to 053 D01 to D08
054 to 061E01 to E08
062 to 069 F01 to F08
070 to 249000
Table 7: Modem IIIa2 Communication Format
Data – Point Numbers
Point/User Flag
NOPoint/User...

Page 14

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 14
Bosch Security Systems | 1/04 | 47775E
Phone Supv Time
Default:Blank
Selection:Blank or 10 to 240
Blank No phone line supervision.
10 to 240 Enter the number of seconds (in 10
second increments) you wish to
supervise the phone line. After a faulted
phone line restores, it takes the same
amount of time to initiate restoral
responses.
Phone line trouble responses: Command centers
display SERVC PH LINE # to indicate which
phone line failed. The...

Page 15

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 15
Bosch Security Systems | 1/04 | 47775E
BFSK Duress Code
Default:0
Selection:0 to 9
If Duress Enable in Area Parameters is Yes and
Modem Format in Phone Parameters is No, you
must program a number to identify Duress Reports
at the central station.
Expand Test Rpt
Default:No
Selection:Yes or No
Yes Report events listed in Routing Group
Test Reports report to the central
station if they are off-normal.
No Does not report off-normal conditions
for the...

Page 16

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 16
Bosch Security Systems | 1/04 | 47775E
2.3.3 Programming a Primary and Backup
Destination
Each route number has an 
R# Primary Device and
an 
R# Backup Device. In typical applications
where two phone numbers are programmed, the 
R#
Primary Device
 destination is the phone number
the route group attempts to dial first. If the
 R#
Primary Device
 destination fails to connect to the
central station receiver after two dialing attempts, the
R# Backup...

Page 17

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 17
Bosch Security Systems | 1/04 | 47775E
Route #
Default:1
Selection:1 to 4
1 First group sent
2 Second group sent
3 Third group sent
4 Fourth group sent
Enter the number specifying the route group to
program. The route represents the group you wish to
send a group of reports. The groups are prioritized. 1
is the first group to report and 4 is the last group to
report. Each group has a primary and a backup
device. The primary device is the first...

Page 18

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 18
Bosch Security Systems | 1/04 | 47775E
Fire Reports
Selecting Yes enables a report to be sent when the
event occurs.
Table 9: Diagnostic Reports
Report Selections Description
R# Fire AlarmYes, NoReports Fire Event.
R# Fire Restore
(Alarm)Yes, NoReports fire restoral
from alarm.
R# Fire MissingYes, NoReports missing Fire
point.
R# Fire Trouble
Yes, NoReports fire trouble.
R# Fire
Supervis
Yes, NoReports fire
supervision.
R# Fire Restore
(T/M/S)Yes,...

Page 19

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 19
Bosch Security Systems | 1/04 | 47775E
Restoral Reports are not sent if the
control panel is reset after a point is
bypassed and then the point is
unbypassed. This is true for both Fire and
Non-fire points.
The 9000 Series Control Panels log a
Ground Fault Event as Trouble Point 256.
User Reports
Selecting Yes enables a report to be sent when the
event occurs.
Table 11: User Reports
Report Selections Description
R# Point
Bypass
Yes, NoReports...

Page 20

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 20
Bosch Security Systems | 1/04 | 47775E
Test Reports
0101
0101
0101To send a single Test Report (R# Test
Report), enable Sked Function Code #9
(Test Report) in the Skeds section of the
program.
To expand this Test Report to include any
off-normal point condition or other off-
normal conditions of events listed in Diag
Reports as a Non-status Event following a
Test Report, Expand Test Rpt in Section
2.2 Phone Parameters must be
programmed Yes....