Page 21

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 21
Bosch Security Systems | 1/04 | 47775E
Table 13: Diagnostic Reports
Report Selections Description
R# SDI Dev Fail*Yes, NoReports SDI device
failure.
R# SDI Dev RestlYes, NoReports restoral of SDI
device failure.
R# Watchdog
RsetYes, NoReports Watchdog
Reset Event.
R#
ParaChksmFailYes, NoReports parameter
checksum failure.
R# RebootYes, NoReports Reboot Event.
R# Ph Line Fail*
Yes, NoReports failure of phone
line.
R# Ph Line RstlYes, NoReports...

Page 22

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 22
Bosch Security Systems | 1/04 | 47775E
RAM Reports
Selecting Yes enables sending a report when the
RAM Passcode Event occurs.
RAM Access Fail can indicate a
wrong RAM passcode when
communicating with the control panel, or a
valid RAM session was terminated by a
means other than a Good-bye or Reset-
bye command. Remote Reset indicates
a Reset-bye command issued from RAM,
Bad Call to RAM indicates the control
panel called RAM but was unable to...

Page 23

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 23
Bosch Security Systems | 1/04 | 47775E
User Chng Reports
Selecting Yes enables a report to be sent when the
event occurs.
Table 18: User Change Reports
Report Selections Description
R# Date
Changed
Yes, NoReports Date
Change Event.
R# Time
ChangedYes, NoReports Time
Change Event.
R# Delete
User*
Yes, NoReports Delete User
Code Event.
R# User Code
ChgYes, NoReports User
Passcode Add or
Change Event.
R# Area WatchYes, NoReports area watch
start and...

Page 24

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 24
Bosch Security Systems | 1/04 | 47775E
2.4.2 Programming a Duplicate Report
To allow an event within a group to report to
multiple groups, the event should be Yes for each
route number available. For instance, programming
Fire Alarms for Route Group 1 and Route Group 2
results in the fire alarms first reporting to Route
Group 1 followed by a duplicate report to Route
Group 2.
Section 2.4 Enhanced Routing determines the route
groups and which...

Page 25

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 25
Bosch Security Systems | 1/04 | 47775E
RG# Primary Pager
Default:No
Selection:Yes or No
Determines if this route group sends events to a
numeric pager. To send events to a numeric pager, a
phone number must also be programmed in the
route group’s primary destination.
0101
0101
0101If programming the control panel to dial a
numeric pager, choose its route group
carefully. If there are any events to transmit
to a central station, be sure to place...

Page 26

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 26
Bosch Security Systems | 1/04 | 47775E
For example, the phone number 2773074***CC
(7 digit pager phone number followed by three
asterisks and two pauses) produces the following
pager display: [1234-001-011] (three fields display at
the pager).
Table 20 shows the description of each event, its
priority, and event number.
Table 20: Event Descriptions, Priorities, and
Numbers
Event DescriptionEvent
PriorityEvent
Number
Fire Alarm001011
Fire Restoral...

Page 27

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 27
Bosch Security Systems | 1/04 | 47775E
Table 20: continued
Event DescriptionEvent
PriorityEvent
Number
Parameters Changed008054
RAM Access OK 008 064
RAM Access Fail008065
Remote Reset 008 079
Program Access OKn/an/a
Program Access Fail n/a n/a
Service Start008029
Service End 008 030
Fire Walk Start008036
Fire Walk End 008 037
Walk Test Start008038
Walk Test End 008 039
Extra Point008023
Send Point Text n/a n/a
RF Low Battery006093
RF Battery...

Page 28

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 28
Bosch Security Systems | 1/04 | 47775E
• 9 (such as 9, 19, 29, 39, and so on): The AC
Fail Time interval is in minutes and an AC Fail
Event is transmitted after the loss of AC for this
amount of time.
An additional AC Fail Event is transmitted after
12 hours if the AC Fail condition is still present.
• 0 (such as 10, 20, 30, and so on): The AC Fail
Time interval is in seconds and an AC Fail
Event is transmitted after the loss of AC for this
amount...

Page 29

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 29
Bosch Security Systems | 1/04 | 47775E
AC/Battery Buzz
Default:No
Selection:Yes or No
Yes Initiates panel-wide trouble tone at all
command centers.
No Does not initiate panel-wide trouble
tone at command centers
Initiate a panel-wide trouble tone at command
centers when AC fails or battery is low or missing.
This program item does not prevent the SERVC AC
FAIL or SERVC BATT LOW displays.
0101
0101
0101To comply with NFPA standards and UL
864...

Page 30

D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 30
Bosch Security Systems | 1/04 | 47775E
When P## Supervised is set to Yes and
all Printer Event Groups (such as P##
Fire Events, P## Burglar Event, or P##
Usr Chng Evt) are set to No, the control
panel does not generate Trouble SDI ##
Reports for the printer if the D9131A
becomes disconnected.
P## Scope
Default:No Printer
Selection:No Printer, Area, Account, Panel
Wide, Custom
Panel
WidePrinter prints all designated events that
occur panel-wide. A...
Start reading Bosch 7412 G User Manual