Page 21
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 21 Bosch Security Systems | 1/04 | 47775E Table 13: Diagnostic Reports Report Selections Description R# SDI Dev Fail*Yes, NoReports SDI device failure. R# SDI Dev RestlYes, NoReports restoral of SDI device failure. R# Watchdog RsetYes, NoReports Watchdog Reset Event. R# ParaChksmFailYes, NoReports parameter checksum failure. R# RebootYes, NoReports Reboot Event. R# Ph Line Fail* Yes, NoReports failure of phone line. R# Ph Line RstlYes, NoReports...
Page 22
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 22 Bosch Security Systems | 1/04 | 47775E RAM Reports Selecting Yes enables sending a report when the RAM Passcode Event occurs. RAM Access Fail can indicate a wrong RAM passcode when communicating with the control panel, or a valid RAM session was terminated by a means other than a Good-bye or Reset- bye command. Remote Reset indicates a Reset-bye command issued from RAM, Bad Call to RAM indicates the control panel called RAM but was unable to...
Page 23
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 23 Bosch Security Systems | 1/04 | 47775E User Chng Reports Selecting Yes enables a report to be sent when the event occurs. Table 18: User Change Reports Report Selections Description R# Date Changed Yes, NoReports Date Change Event. R# Time ChangedYes, NoReports Time Change Event. R# Delete User* Yes, NoReports Delete User Code Event. R# User Code ChgYes, NoReports User Passcode Add or Change Event. R# Area WatchYes, NoReports area watch start and...
Page 24
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 24 Bosch Security Systems | 1/04 | 47775E 2.4.2 Programming a Duplicate Report To allow an event within a group to report to multiple groups, the event should be Yes for each route number available. For instance, programming Fire Alarms for Route Group 1 and Route Group 2 results in the fire alarms first reporting to Route Group 1 followed by a duplicate report to Route Group 2. Section 2.4 Enhanced Routing determines the route groups and which...
Page 25
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 25 Bosch Security Systems | 1/04 | 47775E RG# Primary Pager Default:No Selection:Yes or No Determines if this route group sends events to a numeric pager. To send events to a numeric pager, a phone number must also be programmed in the route group’s primary destination. 0101 0101 0101If programming the control panel to dial a numeric pager, choose its route group carefully. If there are any events to transmit to a central station, be sure to place...
Page 26
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 26 Bosch Security Systems | 1/04 | 47775E For example, the phone number 2773074***CC (7 digit pager phone number followed by three asterisks and two pauses) produces the following pager display: [1234-001-011] (three fields display at the pager). Table 20 shows the description of each event, its priority, and event number. Table 20: Event Descriptions, Priorities, and Numbers Event DescriptionEvent PriorityEvent Number Fire Alarm001011 Fire Restoral...
Page 27
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 27 Bosch Security Systems | 1/04 | 47775E Table 20: continued Event DescriptionEvent PriorityEvent Number Parameters Changed008054 RAM Access OK 008 064 RAM Access Fail008065 Remote Reset 008 079 Program Access OKn/an/a Program Access Fail n/a n/a Service Start008029 Service End 008 030 Fire Walk Start008036 Fire Walk End 008 037 Walk Test Start008038 Walk Test End 008 039 Extra Point008023 Send Point Text n/a n/a RF Low Battery006093 RF Battery...
Page 28
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 28 Bosch Security Systems | 1/04 | 47775E • 9 (such as 9, 19, 29, 39, and so on): The AC Fail Time interval is in minutes and an AC Fail Event is transmitted after the loss of AC for this amount of time. An additional AC Fail Event is transmitted after 12 hours if the AC Fail condition is still present. • 0 (such as 10, 20, 30, and so on): The AC Fail Time interval is in seconds and an AC Fail Event is transmitted after the loss of AC for this amount...
Page 29
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 29 Bosch Security Systems | 1/04 | 47775E AC/Battery Buzz Default:No Selection:Yes or No Yes Initiates panel-wide trouble tone at all command centers. No Does not initiate panel-wide trouble tone at command centers Initiate a panel-wide trouble tone at command centers when AC fails or battery is low or missing. This program item does not prevent the SERVC AC FAIL or SERVC BATT LOW displays. 0101 0101 0101To comply with NFPA standards and UL 864...
Page 30
D9412G/D7412G | Program Entry Guide | 2.0 9000MAINEN | 30 Bosch Security Systems | 1/04 | 47775E When P## Supervised is set to Yes and all Printer Event Groups (such as P## Fire Events, P## Burglar Event, or P## Usr Chng Evt) are set to No, the control panel does not generate Trouble SDI ## Reports for the printer if the D9131A becomes disconnected. P## Scope Default:No Printer Selection:No Printer, Area, Account, Panel Wide, Custom Panel WidePrinter prints all designated events that occur panel-wide. A...
All Bosch manuals