Home > Bosch > Home Security System > Bosch 7412 G User Manual

Bosch 7412 G User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Bosch 7412 G User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 101 Bosch manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 91
    Bosch Security Systems | 1/04 | 47775E
    P## Alarm Verify
    Default:See Program Record Sheet
    Selection:Yes or No
    Yes Enable alarm verification on this point.
    Alarm verification points must be
    programmed as resettable.
    No
    Disable alarm verification on this
    point.
    Use this option only with Fire points to designate
    them for alarm verification.
    When an Alarm Verification point goes into alarm,
    the control panel removes power to all Resettable
    points for the duration programmed in 
    A# Verify
    Time
     in Section 2.9 Area Parameters. If the point (or
    another Resettable point in the area) is still in alarm,
    or goes back into alarm within 60 seconds after the
    initial verification time reset, an alarm is generated.
    During a Fire Walk Test the reset time is 5
    seconds. The time programmed in A#
    Verify Time is ignored. Use the Cross
    point function for Fire points.
    P## Resettable
    Default:See Program Record Sheet
    Selection:Yes or No
    Yes This point is reset by the Reset Sensor?
    function and during the alarm
    verification sequence.
    No This point is not resettable.
    Use this option if this is a Powered point that
    requires interruption of power to reset a latched
    alarm condition. The Resettable point option is
    typically used with smoke detectors and glass break
    detectors.
    When initiated (either through a Fire Walk Test or
    the command center’s Reset Sensor? Function) or
    when the RAM interrupts power to the device for 5
    seconds, Sensor Reset is reported to the central
    station receiver.
    When a sensor reset is initiated, the
    control panel does not accept alarms from
    any points with P## Resettable
    programmed as Yes. During the 5-second
    reset time, alarms from these points are
    ignored.
    Do not mix fire and intrusion devices on
    the same powered loop.
    4.2 Point Assignments
    These entries assign point indexes to Points 1 to 127,
    129 to 247 for the D9412G and Points 1 to 75 for the
    D7412G, and assigns the points to the areas. Also
    included in this section are parameters used to set
    the point’s debounce count, BFSK/Relay (for use
    when transmitting in BFSK or assigning relays to
    follow alarms for a group of points), and custom
    command center and report text for each point.
    Point Number
    Default:1
    Selection:1 to 127, 129 to 247
    Enter the point number you are programming.
    When transmitting in Modem IIIa2, the three-digit
    point number is reported to the D6500/D6600.
    When transmitting in BFSK, you must assign a zone
    number in BFSK/Relay.
    0101
    0101
    0101
    Point numbers 128 and 248 are reserved
    for Zonex bus 1 and 2 supervision. 
    						
    							D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 92
    Bosch Security Systems | 1/04 | 47775E
    P### Point Index
    Default:See Program Record Sheet
    Selection:Blank (00) to 31
    This entry selects one of the 31 P## Index codes
    that define the point’s characteristics and determines
    how the control panel responds to various point
    conditions.
    Blank (00) disables the point.
    Missing Point Reports occur if a point
    address does not exist for a point assigned
    a point index. Extra Point Events occur if
    more than two devices have the same
    address.
    When a POPIT is missing, the control panel
    generates the following responses based
    on the point type:
    • Fire points generate missing trouble
    responses.
    • Non-fire 24-hour points generate
    missing alarm responses.
    • Non-fire, non 24-hour points generate
    missing alarm responses while armed,
    and trouble responses while disarmed.
    Exception: Non-fire, non-24-hour points
    with a point response of 9 to D
    generate a missing alarm response
    while disarmed.
    POPIT modules monitor their sensor loops
    for three conditions: loop normal, loop
    open, and loop shorted. They report these
    three conditions to the control panel. The
    control panel uses point programming to
    interpret the sensor loop information
    reported by the POPITs and to make the
    appropriate system response.
    P### Area Assign
    Default:1
    Selection:1 to 8
    The areas are numbered 1 to 8. Select the area
    number to which the point is assigned.
    P### Debounce
    Default:2
    Selection:1 to 15
    1 .300 seconds
    2 .600 seconds
    3 .900 seconds
    4 1.2 seconds
    5 1.5 seconds
    6 1.8 seconds
    7 2.1 seconds
    8 2.4 seconds
    9 2.7 seconds
    10 3.0 seconds
    11 3.3 seconds
    12 3.6 seconds
    13 3.9 seconds
    14 4.2 seconds
    15 4.5 seconds
    The debounce count is the number of times the
    control panel scans a point before initiating an
    alarm. Scan cycles are 300 ms.
    For appropriate settings consult the manufacturer’s
    instructions for the device connected to this point.
    0101
    0101
    0101Bosch Security Systems recommends an
    entry of two or higher. Interior Follower
    points need a debounce of at least three.
    Door points assigned to D9210B modules
    need a debounce of at least four. 
    						
    							D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 93
    Bosch Security Systems | 1/04 | 47775E
    P### BFSK/Relay
    Default:See Program Record Sheet
    Selection:0 to 9
    Use this option to:
    2. Determine the point number reported in BFSK
    when this point is tripped.
    3. Activate a relay when the point goes into an
    alarm condition, even if the control panel is
    programmed for Modem reporting as shown in
    Table 29.
    BFSK/Relays do not activate for Fire
    Supervisory or Non-Fire Supervisory
    points.
    Table 29: P### BFSK/Relay Codes/Relays
    Trips Relay
    BFSK CodeD8129 on Zonex
    Bus 2 for
    D9412G*D8129 on Zonex
    Bus 2 for
    D7412G*
    1739
    27410
    37511
    47612
    57713
    67814
    77915
    88016
    * Address setting = 1 (on), 2 (off), 3 (on), 4 (on)
    Local annunciation on the command
    centers and Local Printer reporting and
    the View Log display the actual point
    number (1 to 247), not the BFSK report
    code
    0101
    0101
    0101Do not assign a BFSK/Relay to Invisible
    points. To avoid triggering a BFSK/Relay,
    program this prompt as 0.
    On the D9412G, do not use relays 73
    through 80 for Area or Panel-Wide Relay
    functions when using BFSK relays. Doing
    so prevents the BFSK relays from
    triggering.
    On the D7412G, do not use relays 9
    through 16 for Area or Panel Wide Relay
    functions when using BFSK relays. Doing
    so prevents BFSK relays from triggering.
    Two relays can activate when this point
    goes into alarm if the P## Rly Resp Type
    for this point is programmed.
    Use these codes to activate relays on the
    D8129 OctoRelay (or C8137 Transmitter
    Interface). You can assign the same code
    to several points providing a summary
    zone alarm output. When the point goes
    into alarm, the relay activates. When the
    alarm is acknowledged and is no longer
    scrolling in the command center display,
    the relay resets.
    P### Point Text
    Default:See Program Record Sheet
    Selection:Up to sixteen alphanumeric
    characters
    Enter alphabetic characters (A to Z) in capital letters.
    Enter up to sixteen characters of text to describe the
    point. This point text is displayed at command
    centers, if the point is programmed as visible, and
    reported to the D6500/D6600 when transmitting in
    Radionics Modem IIIa
    2 format (if it is a reporting
    point).
    Include the point number in custom point text. This
    helps the user when viewing events, initiating
    bypasses, and so on. It can also simplify
    troubleshooting.
    When a D1260 Command Center is
    installed on the system, the point text for
    Points 240 to 247 can be used for Area
    Name Text for Areas 1 to 8, respectively.
    See Table 30:
    Table 30: Point Text for Points 240 to 247
    Point Text Corresponding Area Name Text
    Point 240Area 1
    Point 241 Area 2
    Point 242Area 3
    Point 243 Area 4
    Point 244Area 5
    Point 245 Area 6
    Point 246Area 7
    Point 247 Area 8 
    						
    							D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 94
    Bosch Security Systems | 1/04 | 47775E
    4.3 COMMAND 7 and COMMAND 9
    These entries assign point indexes, BFSK report
    code, BFSK relay that trips, and the text for the
    COMMAND 7 and COMMAND 9 command
    center functions.
    CMD7 Point Index
    Default:31
    Selection:Blank (00) to 31
    This entry selects one of the 31 P## Index codes
    that define how the control panel reacts when a
    COMMAND 7 is initiated.
    0101
    0101
    0101The point index code used for COMMAND
    7 must not be used for any other points on
    the system.
    If the point index for COMMAND 7 has
    Fire points programmed Yes, this causes
    access control doors to unlock if Fire
    Unlock is also programmed Yes (see the
    D9210B Program Entry Guide).
    CMD7 BFSK/Relay
    Default:1
    Selection:0 to 9
    Selects one of the digits shown for reporting in BFSK
    or for activating relays 73 to 80 (on the D9412G) or
    relays 9 to 16 (for the D7412G) when COMMAND
    7 is initiated (see the 
    P### BFSK/Relay prompt in
    Section 4.2 Point Assignments).
    COMMAND 7 does not activate the
    Summary Fire Alarm relay.
    CMD7 Point Text
    Default:[COMMAND][7]
    Selection:Up to sixteen alphanumeric
    characters
    Enter alphabetic characters A to Z in capital letters
    Enter up to sixteen characters of text to describe the
    point. This point text is displayed at command
    centers (if the point is programmed as visible) and
    reported to the D6500/D6600 when transmitting in
    Radionics’ Modem IIIa
    2 format (if it is a reporting
    point).
    CMD9 Point Index
    Default:31
    Selection:Blank (00) to 31
    This entry selects one of the 31 P## Index codes
    that define how the control panel reacts when a
    COMMAND 9 is initiated.
    0101
    0101
    0101The point index code used for COMMAND
    9 must not be used for any other points on
    the system.
    If the point index for COMMAND 9 has
    Fire points programmed as Yes, this
    causes access control doors to unlock if
    Fire Unlock is also programmed Yes (see
    the D9210B Program Entry Guide).
    CMD9 BFSK/Relay
    Default:1
    Selection:0 to 9
    This entry selects one of the digits shown for
    reporting in BFSK or for activating relays 73 to 80
    (on the D9412G) or relays 9 to 16 (for the D7412G)
    when a COMMAND 9 is initiated (see the 
    P###
    BFSK/Relay
     prompt in Section 4.2 Point Assignments).
    COMMAND 9 does not activate the
    Summary Fire Alarm relay.
    CMD9 Point Text
    Default:[COMMAND][9]
    Selection:Up to sixteen alphanumeric
    characters
    Enter alphabetic characters (A to Z) in capital letters
    Enter up to sixteen characters of text to describe the
    point. This point text is displayed at command
    centers (if the point is programmed as visible) and
    reported to the D6500/D6600 when transmitting in
    Radionics’ Modem IIIa
    2 format (if it is a reporting
    point). 
    						
    							D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 95
    Bosch Security Systems | 1/04 | 47775E
    5.0 RADXSKED
    5.1 Windows
    Use this programming module to define the
    windows for Opening and Closing and User Access.
    5.1.1 Opening and Closing
    Use these windows to set a schedule for disarming
    and arming. The disarming and arming schedules
    provide several independent features:
    • Suppress normal Opening and/or Closing
    Reports when 
    A# Disable O/C in Windows is
    programmed Yes.
    • Generate a Fail to Open Report if the area is not
    disarmed on schedule when 
    A# Fail To Open
    is programmed Yes.
    • Provide a warning tone and a PLEASE CLOSE
    NOW display at the command center when it is
    time to arm the area.
    • Generate a Fail to Close Report if the area is not
    armed on schedule when 
    A# Fail To Close is
    programmed Yes.
    • Automatically arm the area at the end of the
    Closing Window when 
    A# Auto Close is
    programmed Yes.
    Opening and closing schedules can be set up
    independently. For example, if you only want to use
    features provided by Closing Windows, leave times
    blank in the Opening Windows prompts and
    program Closing Window times.
    A worksheet is provided at the end of this section for
    your convenience. Following the worksheet are
    examples of how to program Opening and Closing
    Windows for particular applications (see Table 35
    through Table 39.
    About the Program Record Sheet: A column
    labeled Sked # is found on the Program Record Sheet
    provided with the control panel. These numbers
    appear in D6500/D6600 reports and local printer
    reports when the window Begin Time executes.
    Window selections 1 through 8 correspond with odd
    numbered Skeds 41 through 55 for Open Window
    and correspond with even numbered Skeds 42
    through 56 for Close Window. For example, when
    the Opening Window for Window 1 executes, a
    Sked 41 Executed Event is generated. See Table 31.Table 31: Window Selections
    Selection Sked # Window Sked # Windo
    w
    141Open42Close
    243Open44Close
    345Open46Close
    447Open48Close
    549Open50Close
    651Open52Close
    753Open54Close
    855Open56Close
    Window
    Default:1
    Selection:1 to 8
    Enter the window number you want to program.
    W# Sunday
    Default:No
    Selection:Yes or No
    Yes Activate this window on Sundays.
    No Do not activate this window on
    Sundays.
    This prompt, and the next six day of the week
    prompts, select the days of the week the Opening
    and/or Closing Windows are active.
    Exceptions:
    To prevent the windows from activating on certain
    days of the year, program 
    Xept Holiday Yes, and
    enable at least one Holiday Index. When 
    Xept
    Holiday
     is Yes, the window executes on the days of
    the week programmed unless the Holiday Index
    designates the date as a holiday.
    If Opening and/or Closing Windows are only
    needed on certain days of the year, do not program
    the windows to execute on any days of the week.
    Instead, program 
    Xept Holiday No and select a
    Holiday Index with the days of the year you want
    the window to be active. 
    						
    							D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 96
    Bosch Security Systems | 1/04 | 47775E
    W# Monday
    Default:No
    Selection:Yes or No
    W# Tuesday
    Default:No
    Selection:Yes or No
    W# Wednesday
    Default:No
    Selection:Yes or No
    W# Thursday
    Default:No
    Selection:Yes or No
    W# Friday
    Default:No
    Selection:Yes or No
    W# Saturday
    Default:No
    Selection:Yes or No
    W# Open Early Begin
    Default:00:00
    Selection:HH:MM (hours and minutes)
    00:00 to 23:59
    Open Early Begin: This program item is one of
    three required to create an Opening Window. To
    finish programming an Opening Window, Open
    Window Start and Open Window Stop must be
    programmed.
    Use Open Early Begin to set the time the control
    panel looks for an Opening Window. When
    Opening and Closing Reports are enabled,
    disarming the area between midnight and the Open
    Early Begin time generates an Opening Report. In
    addition:
    • If Disable O/C in Window is Yes: Disarming
    the area between the Open Early Begin and the
    Open Window Start time generates an Early to
    Open Event (if the Open Early Begin time is the
    same as the Open Window Start time, the Early
    to Open Event is not sent).
    Disarming the area between the Open WindowStart and Open Window Stop time creates a
    local event in the Panel log but does not send
    the Opening Report to the central station.
    Disarming the area after the Open Window Stop
    and the next window’s Open Early Begin time
    (or midnight, whichever comes sooner)
    generates a Late to Open Event.
    • If Disable O/C in Window is Yes: Disarming
    the area generates an Opening Report without
    the early or late modifier, regardless of when the
    area is disarmed.
    When you are programming multiple windows
    to activate on a single day, program the
    windows in chronological order. Be careful not
    to program a window’s Open Early Begin time
    for a time that is between any other window’s
    Open Window Start and Open Window Stop
    time.
    0101
    0101
    0101
    Do not program a window to cross the
    midnight boundary.
    Disabled windows have a blank begin time. If the
    entry for this prompt is blank, but times are
    programmed for Open Window Start and Open
    Window Stop, the window is disabled.
    To disable the window, both the hours and minutes
    spaces must be Blank.
    00:00 is midnight, 23:59 is 11:59 PM. Make entries
    using a 24-hour clock (for example, 7:00 AM is
    entered as 07:00, 2:45 PM is entered as 14:45).
    Disable/Restart the control panel to activate today’s
    window. If you are programming a window that
    must activate on the same day you are programming
    it, do a disable/restart after programming.
    W# Open Window Start
    Default:00: 00
    Selection:HH:MM (hours and minutes)
    Enter the time you want the control panel to start
    the Opening Window. The window goes into effect
    at the beginning of the minute.
    00:00 is midnight, 23:59 is 11:59 PM. Make entries
    using a 24-hour clock (for example, 7:00 AM is
    entered as 07:00, 2:45 PM is entered as 14:45).
    This program item is one of three required to create
    an Opening Window. To program an Opening
    Window, Open Early Begin and Open Window
    Stop must also be programmed. See the 
    W# Open
    Early Begin
     prompt in this section  for report
    feature explanations. 
    						
    							D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 97
    Bosch Security Systems | 1/04 | 47775E
    W# Open Window Stop
    Default:00: 00
    Selection:HH:MM (hours and minutes)
    Enter the time you want the control panel to end the
    Opening Window. The window stops at the end of
    the minute.
    00:00 is midnight, 23:59 is 11:59 PM Make entries
    using a 24-hour clock (for example, 7:00 AM is
    entered as 07:00, 2:45 PM is entered as 14:45).
    This program item is one of three required to create
    an Opening Window. To program an Opening
    Window, Open Early Begin and Open Window
    Start must also be programmed.If the area is not disarmed by the time the Open
    Window Stop time expires, the control panel
    generates a Fail to Open Report if enabled in Fail
    To Open.
    Opening Reports generated between the Open
    Window Start time and Open Window Stop time
    can be suppressed by programming 
    Disable O/C in
    Window
     Yes. See the Open Early Begin prompt
    for other report feature explanations.
    Do not use a time of 23:59 as a window stop time
    unless another window begins on the next day at
    00:00.
    0101
    0101
    0101
    Fail to Open Reports are not sent for
    windows that stop at 23:59.
    Figure 4: Example Opening Window Timeline (using two Opening Windows on same day)
    1
    2
    3
    4
    5
    6
    7
    8
    9
    1 - Areas disarmed between midnight and 6 AM
    generate Opening Reports.
    2 - Areas disarmed between 6 AM and 7 AM
    generate Early to Open Reports.
    3 - If the area is disarmed between 7 AM and 8 AM
    regular Opening Reports are generated. If Disable
    O/C in Window is programmed Yes the Opening
    Report is not transmitted to the central station.
    4 - If the area is not disarmed by 8:01 AM, a Fail to
    Open Event is generated if Fail to Open is
    programmed Yes in Opening and Closing Options.
    5 - If the user disarms the area between 8:01 AM and
    12:59, PM a Late to Open Event is generated.6 - Areas that are disarmed between 1 PM and 2 PM
    generate Early to Open Reports.
    7 - If the area is disarmed between 2 PM and 3 PM
    regular Opening Reports are generated. If Disable
    O/C in Window is programmed Yes, the Opening
    Report is not transmitted to the central station.
    8 - If the area is not disarmed by 3:01 PM, a Fail to
    Open Event is generated if Fail to Open is
    programmed Yes in Opening and Closing Options.
    9 - If the user disarms the area between 3:01 PM and
    11:59 PM, a Late to Open Event is generated. 
    						
    							D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 98
    Bosch Security Systems | 1/04 | 47775E
    Table 32: Programming for Two Same Day Opening Windows (see Figure 4)
    Open Close
    W# Day of Week
    Early
    BeginStart StopEarly
    BeginStart StopeXcept
    On
    HolidayHoliday
    Index Area(s)
    1S  M  T  W  T  F  S06: 0007 : 0008: 00Yes / No1   2   3   41  2  3  4  5  6  7  8
    2
    S  M  T  W  T  F  S13 : 00 14 : 00 15 : 00
    Yes / No1   2   3   4
    1  2  3  4  5  6  7  8
    Do not program a single window to cross the midnight boundary. The window stop time must be later than the
    window start time. To program a window that effectively crosses the midnight boundary, you must program two
    windows.
    For example, to program windows for an area that opens between 11:30 PM and 12:30 AM, five days a week, use
    two windows as shown in Table 33.
    Table 33: Programming to Link Two Days over Midnight
    Open Close
    W# Day of Week
    Early
    Begin Start StopEarly
    Begin Start StopeXcept
    On
    HolidayHoliday
    Index Area(s)
    1S  M  T  W  T  F  S22 : 0023 : 3023 : 59Yes    No1   2   3   41  2  3  4  5  6  7  8
    2
    S  M  T  W  T  F  S00 : 00 00 : 00 00 : 30
    Yes    No1   2   3   4
    1  2  3  4  5  6  7  8
    W# Close Early Begin
    Default:00: 00
    Selection:HH:MM (hours and minutes)
    00:00 to 23:59
    Close Early Begin: This program item is one of
    three required to create a Closing Window. To finish
    programming a Closing Window, Close Window
    Start and Close Window Stop must be programmed.
    Use Close Early Begin to set the time that you want
    the control panel to look for a Closing Window.
    When Opening and Closing Reports are enabled,
    arming the area between midnight and the Close
    Early Begin time generates a Closing Report. In
    addition:
    • If Disable O/C in Window is Yes: Arming the
    area between the Close Early Begin time and
    the Close Window Start time generates a
    Closing Early Event (if the Close Early Begin
    time is the same as the Close Window Start
    time, the Closing Early Event is not sent).
    Arming the area between the Close Window
    Start and Close Window Stop time creates a
    local event in the Panel log but does not send
    the Closing Report to the central station.Arming the area after the Close Window Stop and
    the next window’s Close Early Begin time (or
    midnight, whichever comes sooner) generates a
    Closing Late Event.
    • If Disable O/C in Window is No: Disarming
    the area generates a Closing Report without the
    early or late modifier, regardless of when the
    area is armed.
    When you are programming multiple windows
    to activate on a single day, program the
    windows in chronological order. Be careful not
    to program a window’s Close Early Begin time
    for a time that is between any other window’s
    Close Window Start and Close Window Stop
    time.
    Disabled windows have a blank begin time. If
    the entry for this prompt is blank, but times are
    programmed for Close Window Start and Close
    Window Stop, the window is disabled.
    To disable the window, both the hours and
    minutes spaces must be blank.
    00:00 is midnight, 23:59 is 11:59 PM. Make
    entries using a 24-hour clock (for example, 7:00
    AM is entered as 07:00, 2:45 PM is entered as
    14:45). 
    						
    							D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 99
    Bosch Security Systems | 1/04 | 47775E
    Disable/Restart the control panel to activate
    today’s window. If you are programming a
    window that needs to activate on the same day
    that you are programming it, do a disable/restart
    after programming.
    W# Close Window Start
    Default:00: 00
    Selection:HH:MM (hours and minutes)
    Enter the time that you want the control panel to
    start the Closing Window. The window goes into
    effect at the beginning of the minute.
    00:00 is midnight, 23:59 is 11:59 PM. Make entries
    using a 24-hour clock (for example, 7:00 AM is
    entered as 07:00, 2:45 PM is entered as 14:45).
    This program item is one of three required to create
    a Closing Window. To program a Closing Window,
    Close Early Begin and Close Window Stop must
    also be programmed.
    If the area is not armed when the Close Window
    Start time comes, a warning tone sounds and
    PLEASE CLOSE NOW displays at the command
    center. To temporarily silence the tone, press the
    [ESC] key on the command center. The warning
    tone restarts in 10 minutes if the area is not armed.
    See the 
    W# Close Early Begin prompt in this
    section for report feature explanations.
    W# Close Window Stop
    Default:00: 00
    Selection:HH:MM (hours and minutes)
    Enter the time that you want the control panel to
    end the Closing Window. The window stops at the
    end of the minute.
    00:00 is midnight, 23:59 is 11:59 PM. Make entries
    using a 24-hour clock (for example, 7:00 AM is
    entered as 07:00, 2:45 PM is entered as 14:45).
    This program item is one of three required to create
    a Closing Window. To program a Closing Window,
    Close Early Begin and Close Window Start must
    also be programmed.
    If the area is not armed by the time the Close
    Window Stop time expires, the control panel
    generates a Fail to Close Report if enabled in Fail To
    Close.
    Closing Reports generated between the Close
    Window Start time and Close Window Stop time
    can be suppressed by programming 
    Disable O/C in
    Window
     Yes. See the W# Close Early Begin
    prompt for other report feature explanations.
    Do not use a time of 23:59 as a window stop time
    unless the window continues on the next day at
    00:00. Fail to Close Reports are not sent, and the
    Auto Close feature does not work for windows that
    stop at 23:59.
    Do not program a single window to cross the
    midnight boundary. The window stop time must be
    later than the window start time. To program a
    window that effectively crosses the midnight
    boundary, you must program two windows.
    For example, to program windows for an area that
    closes between 11:30 PM and 12:30 AM, five days a
    week, use two windows as shown in Table 34.
    Table 34: W# Close Window Stop Programming Example
    Open Close
    W# Day of Week
    Early
    Begin Start StopEarly
    Begin Start StopeXcept
    On
    HolidayHoliday
    Index Area(s)
    1S  M  T  W  T  F  S22 : 0023 : 3023 : 59Yes    No1   2   3   41  2  3  4  5  6  7  8
    2
    S  M  T  W  T  F  S00 : 00 00 : 00 00 : 30
    Yes    No1   2   3   4
    1  2  3  4  5  6  7  8 
    						
    							D9412G/D7412G | Program Entry Guide | 5.0 RADXSKEDEN | 100
    Bosch Security Systems | 1/04 | 47775E
    W# Xept Holiday
    Default:No
    Selection:Yes or No
    Yes Do not activate this window on
    holidays.
    To use this selection, the window must
    be programmed to activate on at least
    one day of the week and a Holiday
    Index must be enabled.
    No A holiday does not prevent this
    window from activating.
    You also use this selection if Opening
    and/or Closing Windows are only
    needed on certain days of the year. Do
    not program the windows to execute
    on any days of the week. Instead,
    program 
    Xept Holiday No, and select
    at least one Holiday Index with the
    days of the year you want the window
    to be active.
    Determine if the window is disabled on holidays, or
    is active only on holidays.
    To prevent the windows from activating on certain
    days of the year, program 
    Xept Holiday Yes, and
    enable at least one Holiday Index. When 
    Xept
    Holiday
     is programmed Yes, the window executes
    on the days of the week programmed unless the date
    is designated as a Holiday by the Holiday Index(es)
    selected.
    Holiday Indexes for O/C Windows
    You can enable up to four Holiday Indexes for use
    with Opening/Closing Windows. Enable at least one
    Holiday Index if
     W# Xept Holiday is programmed
    Yes for this window, or if you want this window to
    activate only on specific dates. Holidays are
    programmed in Section 5.3 Holiday Indexes.
    W# Holiday 1
    Default:No
    Selection:Yes or No
    Yes Use Holiday Index 1 with this window.
    No
    Do not use Holiday Index 1 with this
    window.
    W# Holiday 2
    Default:No
    Selection:Yes or No
    W# Holiday 3
    Default:No
    Selection:Yes or No
    W# Holiday 4
    Default:No
    Selection:Yes or No
    W# Area 1 [through 8]
    Default:No
    Selection:Yes or No
    Yes Activate the window in the area
    number (#) specified.
    No
    Disable the window in the area
    number (#) specified.
    Eight separate program items determine whether a
    particular window activates in each of the eight areas
    of the control panel. 
    						
    All Bosch manuals Comments (0)