Bosch 7412 G User Manual
Have a look at the manual Bosch 7412 G User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 101 Bosch manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 81 Bosch Security Systems | 1/04 | 47775E 4.1.1 Point Responses Applications for Point Responses 9, D, and E: Combine Point Responses 9, D, and E with Perimeter point types to create more flexible 24-hour protection. Unlike 24-hour points, a faulted Perimeter point with a Point Response of D and E displays at the command center when arming. Like a 24- hour point, a point programmed this way can generate alarms whether the area is armed or disarmed. Combining Point Response 9 with the Local While Disarmed feature provides off-site reporting when the area is armed, but only local alarm annunciation when the area is disarmed. Combining Point Response 9 with the Local While Armed feature provides off-site reporting when the area is disarmed, but only local alarm annunciation when the area is armed. Point Response E: Use this for Zonex/Asic motion detectors. The control panel can report troubles while Master Armed. Point Response F: Does not sound at local command centers but activates RlyResp Type 1 and command center faults. To annunciate the off-normal state at a command center, program Disp as Dvc as Yes and/or BuzzOn Fault as 1 or 2. This point response does not generate alarms or activate an alarm relay. Point Response 8, 9, A, B, and C provide supervisory (24-hour) reporting. Characteristics of a Fire Point: Reporting: When a group of events occur, the control panel routes and prints out Fire Reports first. Visual Annunciation: Fire troubles continue to scroll until the trouble is cleared. Once acknowledged, FIRE TROUBLE scrolls to let the end user know that a Fire point, or group of Fire points, is still in trouble. Panel- Wide Relays, Summary Fire, and Summary Fire Tbl activate if a relay is assigned when any Fire point goes into alarm or is in trouble. Audible Annunciation: A Fire point activates the A# Fire Bell relay programmed in Relay Parameters. The amount of time and pattern of the relay activation is programmed by area in Bell Parameters, A# Fire Time, and A# Fire Pat. Supervisory: A Fire point can send a Fire Supervisory Report and activate the Summary Fire, Sup and Summary Fire Tbl, Panel-Wide Relays with a P## Response of 8-9-A-B-C. Alarm Verification: A Fire point can delay an alarm by the time programmed in A# Verify Time in the Area Parameters. Combined with A# Resettable, a Fire point also resets the electrical circuit for the verify time amount. Reset Sensor: A fire device that requires resetting can be manually reset using the reset sensor relay for the area it is assigned to. Fire Walk: Use the Fire Walk function to test Fire points in the system. To provide an audible tone for a restored Fire Supervisory point, use P## RlyResp Type 1 and connect to a graphic annunciator.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 82 Bosch Security Systems | 1/04 | 47775E P## Pt Response Default:See Program Record Sheet Selection:0 to F Controlled (Non-24-Hour Points) Point Response 0123456789ABCDEF Armed OpenIIIIDDIIDIIIIIT Armed ShortIIIIIIDDDIIIIII Disarmed OpenTT TIITIT Disarmed ShortTT T ITI I 24-Hour Points Point Response 0123456789ABCDEF Open ITIT ITSTS S Short I I T T I T T S S S Key: I = Instant alarm D = Delayed alarm T = Trouble S = Supervisory Blank = Audible/visual response Example of Controlled point: Point Type = 1 Point Response = 8 Perimeter point with delayed alarm response when armed (opened or shorted) and no response when disarmed. Example of 24-hour point: Point Type = 0 Point Response = 8 24-hour point with supervisory response when open and a trouble response when shorted. 0101 0101 0101When programming the point response for Inovonics Wireless Transmitters, regardless of how the transmitter is programmed, the D8125INV Wireless Interface always sends the off-normal state to the control panel as a short and a tamper condition as an open. As a result, typical point responses for the Inovonics transmitters would include 0, 1, 6, 7, and E for Controlled points, and 0 and 1 for 24-hour Burg points. When programming a transmitter as a Fire point, a Point Response of 1 is recommended. Note: Wireless transmitters are NOT UL Listed with the D9412G/D7412G in fire or burglary applications. At present, Inovonics Wireless Transmitters, when used with the D8125INV Wireless Interface on a 9000 Series Control Panel, are not UL Listed for use with fire or burglary applications. With Supervisory Pt Response (S = Supervisory), the BFSK format does not transmit fire supervisory or Non-fire Supervisory Events. Modem format must be used with Supervisory Point Responses.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 83 Bosch Security Systems | 1/04 | 47775E P## Entry Delay Default:See Program Record Sheet Selection:5 seconds to 600 seconds Use this option to enter the amount of entry delay time that a user has after faulting a Controlled point ( P## Type 1, 2, 3) with a delayed response (D) ( P## Pt Response) of 4, 5, 6, 7, or 8. DISARM NOW displays for the duration of the time programmed when the point is faulted in the delay condition. 0101 0101 0101Beginning with firmware revision 6.30 and higher, the D1255 alternates between DISARM NOW and the point text of the point that caused the area to go into entry delay. If this time expires before disarming, or if the point is faulted to an instant response (I), an alarm occurs. 0101 0101 0101Make entries in 5 second increments. The programmer does not allow off-increment entries. If another Perimeter or Interior Follower Delay point trips while the area is already in entry delay, the control panel adjusts the delay time to the Delay point with the least amount of delay time. Use P## Type 3 Interior Follower to program points that do not go into instant alarm the user must fault in order to get to the command center and disarm during the entry or exit delay period. P## Ent Tone Off Default:No Selection:Yes or No Yes Disable entry delay tone when this point is faulted to the delay response. No A tone sounds at command centers when this point initiates entry delay. This option enables/disables the entry delay warning tone for this point. Do not set points to No if they are actually used to notify the user to disarm the system. The possibility of false alarms increases if the entry delay warning is not used. 0101 0101 0101Entry Tone can also be turned off when programming your CC Entry Tone, in Section 2.10 Command Center, which allows you to manage the tone by command center. You may want to disable the entry tone in high security applications where you do not want to annunciate entry delay. P## Silent Bell Default:No Selection:Yes or No Yes Activate the Silent Alarm relay when this point goes into alarm. Command centers do not sound the alarm tone for Non-fire points. No Activate either the Fire Bell relay or Alarm Bell relay and sound the alarm tone at command centers when this point goes into alarm. If this is a Fire point, it activates the Fire Bell relay programmed in Relay Parameters. Otherwise, it activates the Alarm Bell relay. The amount of time and pattern of the relay activation is programmed by area in Bell Parameters. If you want this point to eventually ring the bell because the message failed to reach the central station receiver, program P## Audible After 2 Failures as Yes. P## Ring Til Rst Default:No Selection:Yes or No Yes The relay programmed to provide fire alarm output for this point cannot be de-activated until the point restores to normal. No The relay programmed to provide fire alarm output for this point can be de- activated before the point restores to normal. Use this option to determine if the bell continues to ring until the Fire Bell time expires. The point returns to a normal condition when the user acknowledges the alarm to silence the bell.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 84 Bosch Security Systems | 1/04 | 47775E If the point restores and the fire alarm is not silenced from the command center, the fire alarm output continues until Fire Bell time expires. If the point does not restore, the fire alarm output continues even after bell time expires.\ Use this option for fire applications to meet the requirement that audible alarms cannot be silenced until the fault condition clears or the Fire Bell time expires. P## Audible After 2 Failures Default:No Selection:Yes or No Yes A# Burg Alarm relay activates after two failed attempts. No P## Silent points do not cause the A# Burg Alarm relay to activate even if the report does not get to the central station receiver. Use this option for reporting Non-fire points programmed as P## Silent to eventually cause the alarm bell to ring if the control panel fails to report the Alarm Event at the end of two failed attempts to the remote central station receiver. 0101 0101 0101When a point that is programmed for P## Silent Bell is faulted, the timer for the A# Burg Time starts, even though the bell is not yet ringing. It can take up to 3 minutes before the second attempt fails. Ensure A# Burg Time is programmed to provide the amount of bell time you need, minus the 3 minutes it can take before the bell actually begins to ring. P## Invisible Pt Default:See Program Record Sheet Selection:Yes or No Yes Command centers do not display alarm activity from this point. No Activity from this point is visible at the command centers. Use this option to determine whether the point appears in the command center display upon an Alarm condition. For LED command centers, the LED does not illuminate upon an alarm condition. Point text appears and annunciation is made for Invisible points programmed for a trouble condition in point response. To prevent the command center alarm tone and the A# Burg Alarm bell from sounding, this point needs P## Silence Bell programmed as Yes. 0101 0101 0101ALARM SILENCED displays at the command center if this Invisible point causes a bell to ring upon an alarm and a valid passcode is entered.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 85 Bosch Security Systems | 1/04 | 47775E P## Buzz On Fault Default:Blank Selection:Blank, 1 to 3 Selection Operation for Controlled Points (Point Types 1, 2, and 3)Operation for 24-hour Points (Point Type 0) Blank The point only generates a buzz at the command center if it goes into the trouble condition indicated in the P## Point Response.Same 1 The point generates a Buzz Until Restore at the command center for any fault condition while the point is disarmed. The buzz continues until the point restores and the user acknowledges the condition using a passcode or COMMAND 4. The point must be normal before the user can silence the buzz.The point generates a Buzz Until Restore at the command center for any fault condition regardless of the armed state. The buzz continues until the point restores and the user acknowledges the condition using a passcode or COMMAND 4. The point must be normal before the user can silence the buzz. 2 The point generates a buzz at the command center for any fault condition when the point is disarmed. The point does not need to be normal before the user can silence the buzz.The point generates a buzz at the command center for any fault condition regardless of the armed state. The point does not need to be normal before the user can silence the buzz. 3 The point generates a buzz at the command center for any fault condition when the area is disarmed. The user cannot silence this buzz, but it silences automatically when the point is restored. If the fault condition results in a trouble response, the command center continues to buzz even after the user acknowledges the condition if the fault is still present.The point generates a buzz at the command center for any fault condition regardless of the armed state. The user cannot silence this buzz, but it silences automatically when the point is restored. If the fault condition results in a trouble response, the command center continues to buzz even after the user acknowledges the condition if the fault is still present. The buzz does not automatically stop once the point is restored when using Option 1 or 2. The user must acknowledge the buzz prior to the buzz stopping. However, when using Option 3, the buzz automatically stops when the point restores to normal without user intervention. Points bypassed (by the user, Sked, Swinger Bypass, or RAM) do not generate a Buzz On Fault condition at the command center. P## Watch Point Default:See Program Record Sheet Selection:Yes or No Yes This point activates Watch Mode responses if it is faulted while the control panel is in Watch Mode. No Do not activate Watch Mode responses for this point. Use this option to allow a Controlled point to generate a watch tone as long as the area is disarmed and not being faulted into a trouble or alarm condition.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 86 Bosch Security Systems | 1/04 | 47775E P## RlyResp Type Default:See Program Record Sheet Selection:Blank, 1 to 2 Blank Point state does not affect the operation of the corresponding relay. 1 Relay Follow Point: The relay corresponding with this point activates when the point is faulted to any off normal condition. The relay automatically resets when the point is returned to normal. 2 Relay Latches: The relay corresponding with this point latches when the point goes into an alarm condition. This relay provides a steady output until the alarm is acknowledged by a valid passcode then cleared from alarm memory with an acknowledgment at the command center. Use this option to cause a relay (1 to 127 for D9412G; 1 to 64 for D7412G) to respond when a corresponding point with the same number (1 to 127) is faulted. [This requires connecting D8129 OctoRelays to Zonex Bus 1 and/or Zonex Bus 2 (D9412G only). See address settings on the back of the D9412G/D7412G Program Record Sheet (P/N: 47488)]. Point 128 is reserved for other use than an actual point. Only the first 127 points can have an associated relay. Relays are not available for Points 129 to 247. Do not use the Chg Relays? function to toggle relays reserved for special functions. Special function relays are Area and Panel Wide Relay functions as well as relays assigned to CC Entr Key Rly and P## RlyResp Type. P## Disp as Dvc Default:No Selection:Yes or No Yes Display CHECK DEVICE when this point is off normal. No Do not display CHECK DEVICE when this point is off normal. Use this option to cause the command center to display CHECK DEVICE once a point is off normal or was acknowledged after going into alarm. Use this function for devices with a dry contact output which faults a point once the device is in a trouble condition. P## Local While Disarmed Default:See Program Record Sheet Selection:Yes or No Yes Suppress Alarm, Trouble and Restoral* Reports from this point while the area it is assigned to is disarmed. No Report events occurring from this point while the area is disarmed. *Restoral Reports are still transmitted if the alarm, trouble, or bypass (by Sked, RAM, or Swinger bypass) condition occurred when the area disarmed, and the point restored. Use this option to allow a Controlled point (P## Type 1, 2, 3 ), to report Alarms, Troubles, and Restoral Reports only when the area is armed. This prompt does not affect local annunciation. Local While Disarmed suppresses all reports from 24-hour points. Do not use P## Type 0 for this prompt. Remember that this only works for Disarmed points, and a Type 0 is a 24-hour Always Armed point. Instead, choose any type other than 0, and use a point response that reports an alarm whether the point is armed or not. For instance, P## Type 1 and P## Response 9 reports an alarm on an open or a short (I) whether the area is armed or not. Local While Disarmed affects Keyswitch points. This prompt suppresses keyswitch (troubles/restorals) and D279 (alarms/troubles/restorals). Do not use this parameter for these applications. P## Local While Armed Default:No Selection:Yes or No Yes Suppress Alarm, Trouble and Restoral* Reports from this point while the area it is assigned to is armed. No Report events occurring from this point while the area is armed.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 87 Bosch Security Systems | 1/04 | 47775E *Restoral Reports are still transmitted if the alarm, trouble, or bypass (by Sked, RAM, or Swinger bypass) condition occurred when the area disarmed, and the point restored. Allows a controlled point (P## Type 1, 2, 3), to report Alarms, Troubles, and Restoral Reports only when the area is disarmed. This prompt does not affect local annunciation. Local While Armed suppresses all reports from 24-hour points. Do not use P## Type 0 for this prompt. This only works for disarmed points. Type 0 is a 24-hour always armed point. Choose any Type other than 0, and use a point response that reports an alarm whether the point is armed or not. For instance, P## Type 1 and P## Response 9 reports an alarm on a trouble or a short whether the area is disarmed or not. Local While Armed affects Keyswitch Points. This prompt suppresses keyswitch (alarms/troubles/restorals) and D279 (opening/closing/troubles/restorals). Do not use this parameter for controlled points that arm/disarm. P## Disable Rst Default:No Selection:Yes or No Yes Enable Restoral Reports form this point. No Disable Restoral Reports from this point. * Restoral Reports are still transmitted if the alarm, trouble, or bypass (by sked, RAM, or Swinger bypass) condition occurred when the area disarmed, and the point restored. Use this option to disable any Restoral Reports from this point after it returns to normal from an alarm or trouble condition. P## FA Retrnable Default:No Selection:Yes or No Yes This point automatically returns to the system when it restores to normal. No This point stays out of the system until the area is disarmed. Use this option to allow points that were force armed out of the area to return back to the armed state once they become normal again without having to disarm the system. Use on loading dock doors, which must be left open until loading is completed. Once the loading dock door is closed, the point detects any subsequent opening and reports an alarm. P## BP Retrnable Default:No Selection:Yes or No Yes This point automatically returns to the system when the area is disarmed. No This point stays out of the system through arming and disarming cycles. Use this option to return a point that was bypassed, force armed, or swinger bypassed back into the system once the area this point is assigned to is disarmed. Turn this item to No for Interlock points. When the point cannot return to the system through disarming, the point must be manually unbypassed using the Unbypass?, command center function, Sked Functions 4 and 5 or remotely unbypassed using RAM. 0101 0101 0101For Force Armed points to remain bypassed, ensure P## FA Retrnable is No.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 88 Bosch Security Systems | 1/04 | 47775E P## Bypassable Default:No Selection:Yes or No Yes This point can be bypassed and force armed. No This point cannot be bypassed or force armed from the command center or RAM. However, it can be force armed by automatic arming at the end of the Closing Window (see the A# Auto Close prompt in Section 2.9.5 Open/Close Options) or by a Sked programmed to arm the area. Use this option to allow this point to be bypassed and/or force armed. Bypassing a 24-hour point: When a 24-hour point or 24-hour Supervisory point is bypassed, 24 HOUR BYPASS continuously scrolls at the command center. 24 HOUR BYPASS scrolls to indicate a 24- hour Non-fire point, P## Fire No is bypassed. FIRE BYPASS scrolls to indicate a 24-hour Fire point or a Fire Supervisory point is bypassed. Alternative to a 24-hour Point: For alarm capability of a 24-hour point without the continuous scrolling, use a Perimeter point with a Point Response of 9 to E. 0101 0101 0101A point can be bypassed at the command center using the BYPASS? function, which reports as a Command Bypass. When bypassed by Sked Function 3, the report is Sked Bypass. When bypassed by RAM a RAM Bypass reports after RAM disconnects. When swinger shunted, a Swinger Shunt is reported. If the point is not bypassable, it cannot be bypassed in any of the above cases. Programming Bypassable as Yes for Cross points may cause missed Cross- Point alarms. For example, if Points 1 and 2 were programmed as Cross points and Point 1 was Bypassed or Force Armed, Point 2 cannot generate an Alarm Cross Point Event. Point 2 may, however, generate an Unverified or Alarm Event depending on how the point was tripped. Be careful when using this feature with Cross point applications. P## Swinger Byps Default:No Selection:Yes or No Yes Enable Swinger Bypass for this point. No Disable Swinger Bypass for this point. Use this option to allow the control panel to automatically bypass a point that erroneously reports four Alarm or Trouble Events within an hour of the first event. The control panel reports a Swinger Bypass P### upon the fourth report. If the point has a partial count (less than four events during an hour), the count is reset to zero and three more events are required upon the next report before the control panel initiates the bypass. 0101 0101 0101P## Bypassable does not need to be programmed Yes for swinger bypass to work. A Swinger Shunted point returns to the system if P## BP Returnable? is Yes. If not, return the point to the system as described in the application note for P## BP Returnable. P## Report Bypass at Occurrence Default:No Selection:Yes or No Yes Send a Command Bypass Report at the time the point is bypassed. No Do not send a Command Bypass Report at the time the point is bypassed. This option allows a point to generate a Command Bypass Report as soon as a user bypasses the point from the command center. This option should be enabled for all Bypassable 24-hour points. You may also elect to report a bypassed point at the time the area is armed. See P## Defer BP Report.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 89 Bosch Security Systems | 1/04 | 47775E P## Defer BP Report Default:No Selection:Yes or No Yes Send a Point Bypass Report with the Closing Report instead of a Command Bypass Report when a user bypasses the point. No Do not defer Bypass Reports. Use this option to prevent (P## Type 0 to F) points that are bypassed by the user (COMMAND BYPASS) from occurring until the area is armed. Once the area is armed, the bypassed points and any point being bypassed during the arming sequence report as POINT BYPASS along with the Closing Report. 0101 0101 0101Bypass Reports do not occur when arming the area if the Closing Report is suppressed by O/C Windows or are not reported. Bypass Reports for 24-hour points do not report If P## Report Bypass at Occurrence and P## Defer Bypass Report are both No. To report the bypass at occurrence and when the area is armed, program P## Report Bypass at Occurrence and P## Defer Bypass Report as Yes. A Command Bypass Report is sent as soon as it occurs and a Point Bypass Report is sent with the Closing Report. P## Cross Point Default:No Selection:Yes or No Yes This point is a Cross point. No This point is not a Cross point. The Cross point function is available only in Firmware revisions 6.30 and higher. Do not use Cross points for Fire points. The Cross point feature is available only on points programmed as having an Instant point response. Also, Controlled points (Point Types 1, 2 and 3) do not follow the Cross point operation (described as follows) during entry or exit delay. The Cross point option is designed to reduce false alarms. To achieve this, points can be programmed so the control panel must see an alarm condition within a programmed period of time (called Cross Point Time) from at least two points within a Cross Point Group before Cross Point Alarm Events are generated. These points need the Cross point option enabled in their corresponding point indexes to be able to generate this event. See Section 6.8 Cross Point Parameters for additional programming requirements to program the Cross Point Timer. Cross Point Groups were established in the D9412G and D7412G to support the Cross Point function. There are 31 Cross Point Groups in the D9412G and ten in the D7412G. Each Cross Point Group consists of eight points and is identified by the point numbers in them (such as, Cross Points 1 to 8, Cross Points 9 to 16, and so on). The Cross point function only applies to Alarm conditions. It does not apply to Trouble or Supervisory conditions.
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTSEN | 90 Bosch Security Systems | 1/04 | 47775E P## Fire Point Default:No Selection:Yes or No Yes This point is a Fire point. No This point is not a Fire point. Use this option to make a 24-hour point a Fire point. This option makes this point the highest priority event in the control panel when an alarm occurs for both reporting and displaying on the command center. Characteristics of a Fire Point Reporting: When a group of events occur, the control panel routes and prints out Fire Reports first. Visual Annunciation: FIRE TROUBLES continues to scroll until the trouble is cleared. Once acknowledged, a FIRE TROUBLE scroll lets the end user know that a Fire point, or group of Fire points, is still in trouble. Panel Wide Relays, Summary Fire, and Summary Fire Tbl activates if a relay is assigned when any Fire point goes into alarm or is in trouble. Audible Annunciation: A Fire point activates the A# Fire Bell relay programmed in Relay Parameters. The amount of time and pattern of the relay activation is programmed by area in Bell Parameters, A# Fire Time, and A# Fire Pat. Supervisory: A Fire point can send a Fire Supervisory Report and activate the Summary Fire Sup and Summary Fire Tbl Panel Wide Relays with a P## Response of 8-9-A-B-C. Alarm Verification: A Fire point can delay an alarm by the time programmed in A# Verify Time in the Area parameters. Reset Sensor: A fire device that requires resetting can be manually reset using the reset sensor relay for the area where it is assigned. Fire Walk: Fire points can be tested in the system using the Fire Walk Test which automatically resets each point for five seconds when it is tripped and rings the Fire Bell for two seconds. You should dedicate a fire annunciation device to all your Fire points if they are assigned to a single area in a multiple area system. Special red command centers and annunciators with specific keys for fire systems are designed for this type of application (D1256 and D1257). Do not use the Cross point function for Fire points.