Page 131

D9412G/D7412G | Program Entry Guide | 7.0 RADXAXSEN | 131
Bosch Security Systems | 1/04 | 47775E
7.0 RADXAXS
 7.1 Door Profile
This programming category is used to:
• Assign an area, that also activates the D9210B
• Assign a point to the door
• Program the door state to change when the arm
state changes
• Allow for the Strike relay to activate upon a fire
alarm
Door #
Default:20 seconds
Selection:1 seconds to 8 seconds
Enter the number of the door you are about to
program.
The D9412G supports up to eight...

Page 132

D9412G/D7412G | Program Entry Guide | 7.0 RADXAXSEN | 132
Bosch Security Systems | 1/04 | 47775E
 D# Interlock Point
Default:Blank
Selection:Blank, 1 to 127, 129 to 247
1 to 127,
129 to 247The point number assigned to the
Interlock point. Points 128 and 248 are
reserved by the control panel for
internal use.
Blank There is no point number assigned to
the Interlock point.
Enter the Interlock point number. This point, when
faulted, prevents the door controller from allowing
access upon a valid ID read or...

Page 133

D9412G/D7412G | Program Entry Guide | 7.0 RADXAXSEN | 133
Bosch Security Systems | 1/04 | 47775E
D# Card Type
Default:0
Selection:0 to 3
0 Card format is 26-bit Wiegand.
3 Do not use.
This item must be kept to a value of 0 (26 bit
Wiegand format).
7.2 Strike Profile
This programming category is used to create a
specific door profile for:
• Strike and shunt times.
• Extending strike and shunt times if a door is left
open.
• Resetting the strike when the door opens.
• Programming the Interlock point.
Door...

Page 134

D9412G/D7412G | Program Entry Guide | 7.0 RADXAXSEN | 134
Bosch Security Systems | 1/04 | 47775E
D# Deact On Open?
Default:Yes
Selection:Yes or No
Yes Strike deactivates when the door is
opened after a valid Access Granted
request.
No
Strike remains activated for the amount
of the programmed strike time whether
door is opened or closed.
Determines if the strike deactivates immediately
upon physically opening the door.
0101
0101
0101
In order for this function to work, a point
needs to be assigned to the...

Page 135

D9412G/D7412G | Program Entry Guide | 7.0 RADXAXSEN | 135
Bosch Security Systems | 1/04 | 47775E
D# Access Granted?
Default:No
Selection:Yes or No
Yes Access Events from this door controller
are sent to the control panel for
processing.
No
Access Events from this door controller
are not sent to the control panel for
processing.
This program item determines if Access Granted
and Door Request Events are sent to the control
panel for processing memory, printing, and remote
reporting.
0101
0101
0101A...

Page 136

D9412G/D7412G | Program Entry Guide | Programming Prompts DirectoryEN | 136
Bosch Security Systems | 1/04 | 47775E
Programming Prompts
Directory
9000MAIN ............................................................. 11
Phone............................................................... 11
Phone 1 ..................................................... 11
Phone 2 ..................................................... 11
Phone 3 ..................................................... 11
Phone 4...

Page 137

D9412G/D7412G | Program Entry Guide | Programming Prompts DirectoryEN | 137
Bosch Security Systems | 1/04 | 47775E
Area Parameters ........................................... 34
Area Parameters ............................................. 34
Area ........................................................... 34
A# Area On ............................................. 34
Error! Reference source not found.Error!
Bookmark not defined.
A# FA Bypass Max ................................. 36
A# Delay...

Page 138

D9412G/D7412G | Program Entry Guide | Programming Prompts DirectoryEN | 138
Bosch Security Systems | 1/04 | 47775E
User Cmd 7 .............................................. 57
User Cmd 9 .............................................. 57
Bypass a Pt ............................................... 57
Unbypass a Pt .......................................... 57
Reset Sensors ........................................... 57
Change Relay........................................... 57
Remote...

Page 139

D9412G/D7412G | Program Entry Guide | Programming Prompts DirectoryEN | 139
Bosch Security Systems | 1/04 | 47775E
Panel-Wide Relays ......................................... 71
AC Failure ................................................ 71
Battery Trouble ........................................ 71
Phone Fail................................................. 71
Comm Fail................................................ 72
Log % Full ................................................ 72
Summary Fire...

Page 140

D9412G/D7412G | Program Entry Guide | Programming Prompts DirectoryEN | 140
Bosch Security Systems | 1/04 | 47775E
W# Close Window Start ........................ 99
W# Close Window Stop......................... 99
W# Xept Holiday.................................. 100
W# Holiday 1 ........................................ 100
W# Holiday 2 ........................................ 100
W# Holiday 3 ........................................ 100
W# Holiday 4 ........................................ 100
W# Area 1...
Start reading Bosch 7412 G User Manual
All Bosch manuals