Home > ATT > Communications System > ATT System 25 Reference Manual

ATT System 25 Reference Manual

    Download as PDF Print this page Share this page

    Have a look at the manual ATT System 25 Reference Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 164 ATT manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 613
    							ENVIRONMENTAL REQUIREMENTS
    The base should be located at least; three feet away from any metal object (such as metal
    window frames), six feet away from any computing equipment, and six feet (20 feet for
    minimum interference) away from electromagnetic sources.Avoid using the handset in areas
    with metal objects in the line of sight between the handset and the base.
    If RFI is experienced while using the set, moving the base to a different location can
    significantly increase the range. Moving the base to a higher level, perhaps to a different
    floor, moving it near a window (if the handset is used outside), or even moving the base a
    couple of feet can significantly improve the transmission range.
    6-7 
    						
    							ENVIRONMENTAL REQUIREMENTS
    AC Power Requirements
    Each System 25 cabinet requires 500 Watts at 115V ac (maximum).
    The System 25 power service must be a dedicated branch circuit with no other equipment
    served (see Figure 6-3). The customer should provide a load center of appropriate current
    rating (ITE EQ4 typical) equipped with 120V ac, 15 ampere (AMP), single pole magnetic
    circuit breaker(s) (ITE QP1-BO15 typical).Each breaker is to protect 2 associated wall
    mounted 115 V ac, 15 AMP, receptacles (HUBBELL 5262 typical). Grounding of this load
    center is to be provided by a “Green Wire” ground extended from the grounding electrode
    conductor at the AC service entrance to the load center.
    The following materials are required:
    l Single Cabinet System
    1 - 15 AMP 3 Wire Dedicated Branch Service
    1 - 4 Box (RACO 230 or Equiv.)
    1 - 4 Cover (RACO 807 or Equiv.)
    1 - Ground Bar (Square D PK9GTA or Equiv.)
    2 - Recpt. (Hubbell 5262 15 AMP or Equiv.)
    l Multiple Cabinet System
    2 - 15 AMP 3 Wire Dedicated Branch Service
    2 - 4 Box (RACO 230 or Equiv.)
    2 - 4 Cover (RACO 807 or Equiv.)
    1 - Ground Bar (Square D PK9GTA or Equiv.)
    4 - Recpt. (Hubbell 5262 15 AMP or Equiv.)
    Typically, multiple cabinet systems can be powered from a single phase 120V ac, 60 Hertz
    service (two 15-amp circuits required). There are no phase restrictions between cabinets.
    Therefore, the two 15-amp circuits required may be
    service.
    The receptacles should be located at least 1 foot above
    located further than 4 feet from the cabinets.
    DANGER
    derived from single or three-phase
    the floor. Receptacles should not be
    Under no circumstances should this equipment
    be connected to 220V ac; doing so poses a
    serious fire hazard.
    6-8 
    						
    							ENVIRONMENTAL REQUIREMENTS
    Figure 6-3.AC Power Distribution - Multiple Cabinet System
    6-9 
    						
    							ENVIRONMENTAL REQUIREMENTS
    Grounding
    Connection of an approved ground to the system cabinets is essential. An approved ground
    may consist of any of the following:
    l Grounded Building Steel—The metal frame of the building.
    l Water Pipe—A continuous metal water pipe, not less than 1/2 inch diameter, that is
    connected to an underground metal water pipe that is in direct contact with earth for
    10 feet or more.
    l Concrete-Encased Ground—An electrode encased by at least 2 inches of concrete
    and located within and near the bottom of a concrete foundation or footing in direct
    contact with the earth. The foundation must consist of at least 20 feet of one or
    more steel reinforcing bars or rods of not less than 1/2 inch diameter, or at least 20
    feet of bare, solid copper wire no smaller than No. 4 gauge.
    l Ground Ring—A ring that encircles a building or structure in direct contact with earth
    at a depth of at least 2-1/2 feet.The ring must consist of at least 20 feet of bare
    copper conductor no smaller than No. 2 gauge.
    Lightning Protection
    The System 25 lightning protections plan requires five distinct but interdependent items at
    each installation:
    l Primary protection in the form of voltage limiters (typically carbon blocks or gas
    tubes). These devices bypass surges to approved building ground and limit potential
    differences between T/R pairs and building ground to less than 1500 volts.
    l A single-point ground (SPG) system that connects green wire ground, System 25
    system ground, and telephone company (TelCo) ground together and to approved
    building ground (Figure 6-3).
    l Coupled bonding conductor (CBC) connected between the TelCo ground at the
    building entrance and System 25’s SPG.
    CBC is tie-wrapped to all trunks to provide lightning protection; it can be a 16-gauge
    ground wire or continuous cable sheath. The CBC should also be run from the
    TelCo-provided network interface to the ground block of cabinet 1 (see Figure 3-4 in
    the “Functional Description”section). If the TelCo has not extended the CBC from
    the facility entrance to the network interface, the installer should run the CBC along
    the same route as the incoming facilities where feasible.
    l Secondary protection provided within TN742 and all trunk CPs; such ports can
    withstand 800 volt metallic (differential) and 1500 volt longitudinal (common mode)
    surges.
    6-10 
    						
    							ENVIRONMENTAL REQUIREMENTS
    l Surge protection on the AC power to System 25 and associated equipment (SAT,
    SMDR, DTU, etc.) provided by the TII 428 Unit.
    The protection outlined above is adequate for more than 99 percent of all lightning strikes.
    For the few remaining cases, external secondary protection, located at the trunk access area
    of the cross-connect field, can be employed.Several commercially available units can be
    used. If 66-type block terminations are used, a very convenient device is the LP3-230-220
    Fused Lightning Protector manufactured by ITW-LINX, 195 Algonquin Road, Des Plaines,
    Illinois 60016. This unit plugs into the 66-block (in place of the shorting bars) and includes
    the sneak current fuse. One unit is required per protected pair. A ground bar is provided
    with the lightning protection units or can be ordered separately (Comcode 901007120). Porta
    Systems is another supplier of surge protection devices.Regardless of the type installed, all
    lightning protectors located in the cross-connect area must be grounded to System 25’s SPG
    via a No. 6 AWG copper wire.
    Transmission facilities (voice pairs) that extend out-of-building and are not included in the
    network interface may be installed by the TelCo or through other means (for example, by the
    building owner and/or the property owner).These facilities, aerial or buried, must be
    protected with voltage limiting devices and sneak current fuses. The only exception to this
    rule is buried cable less than 140 feet long that is enclosed in a continuous metallic conduit
    from one building entrance to the other. The conduit must be connected to an approved
    building ground at each end.
    If single-line sets are extended out-of-building, primary protection devices for voice pairs
    should be used. If MERLIN Communications System voice terminals are extended out-of-
    building, the facilities must be protected with the TII Model 341 (PEC 32918, Comcode
    403865785) at each end.Terminals J1-3 and J1-6 of the Model 341 should not be
    connected. Maximum distance between a MERLIN System voice terminal and the System 25
    cabinet is 2000 feet. There is no limit on how much of the 2000 feet can be out-of-building.
    However, out-of-building stations cannot be powered over the line; they must be powered
    locally using PEC 62510.
    6-11 
    						
    							PARTS INFORMATION
    Parts Listed by PEC                                7-1
    Parts Listed by COMMODE                               7-9
    -i- 
    						
    							PARTS INFORMATION
    PARTS INFORMATION
    This section contains information that may assist you in cross-referencing Apparatus Codes
    Component Codes (COMCODEs) and Price Element Codes (PECs). The first table is grouped by
    descriptive PEC. The second table is arranged by COMCODE.
    Parts Listed by PEC
    PECDESCRIPTIONAPPARATUS CODE
    COMCODE
    6250-031System 25 Control Unit (R3V2)includes105243810
    CarrierJ58901A2 L-13 (e/w)
    Consists of:
    Power SupplyWP90510 L2 (MD)
    403954761
    WP90510 L3406846733
    Fans (2)WP90677 L1845416379
    Air Filter21985-1403957129
    Address Plug*
    845416635
    TDM Bus TermZHAF1405522780
    CPU/MEM CPZTN130
    106428907
    Service Circuit CPZTN131106035066
    SLAC Graphics Overlays (2)*845875772
    62501System 25 Expansion Unitincludes
    CarrierJ58901A1 L4 (e/w)
    Consists of:
    Power SupplyWP90510 L2 (MD)
    403954761
    WP90510 L3
    406846733
    Fans (2)WP90677 L1
    845416379
    Air Filter21985-1403957129
    Address Plug*
    845416635
    TDM Bus CableJ58901A4 L3
    403961519
    62502
    GS Trunk CPZTN76103965232
    62503
    LS Trunk CPZTN77103965240
    62504
    TR Line CPZTN78103965257
    62505
    ATL Line CPZTN79103965265
    62506
    Asynchronous Data UnitD181521 includes105105506
    Consists of:
    Mod Cord (14 ft)D8W-87
    103786802
    ATL ADU
    Z3A5103975349
    Power SupplyKS-22911 L1403242639
    November 19957-1 
    						
    							PARTS INFORMATION
    PECDESCRIPTIONAPPARATUS CODE
    COMCODE
    62507Digital Tape UnitTS-555A
    404079436
    62508System Administration Terminal    TI-703
    404079428
    (SAT)
    62509
    Direct Extension Selector23A1-003 e/W103969424
    Console
    Consists of:
    Mod CordD6AP-87102937620
    Mod Cord (14 ft)D8W-87103786802
    Power SupplyKS-22911 L1403242639
    Adapter400B103848859
    62510
    MERLIN® 9 Sys. Voice Terminal      D181522 includes105105514
    (VT) local power
    Consists of:
    AdapterZ400F
    103942857
    Mod CordD6AP-87
    102937620
    Power SupplyKS-22911 L1403242639
    62511Auxiliary Trunk InterfaceD181523 includes105105522
    Consists of:
    Connecting Block
    66E3-25
    100009968
    Cable (15 ft DE)B25A100017334
    62512
    Paging/DictationD181524 includes105105530
    (Aux Trunk Interface)
    Consists of:
    Adapter278A
    103871844
    Power SupplyKS-22911 L1
    403242639
    Mod/Spd Tip CordD4BY
    102999059
    Zener KitD181321
    105031181
    62513Music-on-Hold InterfaceD181575 includes
    *
    Consists of:
    InterfaceKS-23395405143186
    Transformer
    2012D102600517
    Voice Coupler36A103558916
    7-2November 1995 
    						
    							PARTS INFORMATION
    PECDESCRIPTIONAPPARATUS CODE
    COMCODE
    62514Emergency Transfer Unit10B ETU103984118
    Consists of:
    Cables (2) (15 ft DE)B25A
    100017334
    Mod Cord (7 ft)
    D8W-87103786786
    62515
    Peripheral Interface for On-D-181558
    Premises Direct or Switched
    Connection
    Consists of:
    Adapter248B
    102802113
    Adapter355AF105012645
    Adapter400B2104152558
    Mod CordD6AP-87102937620
    ADU Crossover CordD8AM-87104154430
    Mod cords (2) (7 ft)D8W-87103786786
    EIA Crossover CordM7U-87104246616
    ADU
    Z3A4103964185
    Transformer2012D102600517
    62518
    STARLAN Interface CPZTN84103965315
    62520
    STARLAN/ATL InterfaceD181807 includes105355374
    Consists of:
    Y-Adapter
    WP90851 L1405010620
    AdapterKS-23475405462904
    Power Supply
    KS-22911 L1
    403242639
    MERLIN
    ® Sys. Headset Adapter         502B105471304
    62525AR3V2 Upgrade (R1 or R2 to R3V2)
    Consists of:
    CPU/MEM CPZTN130C
    106428907
    Service CPZTN131
    106035066
    Documentation & Tapes for555-540-013
    105528814
    System 25 Upgrade
    SLAC Graphics Overlays (2)         *
    845875772
    62526N
    R3V3 Upgrade (R1 or R2 to R3V3)
    Consists of:
    CPU/MEM CPZTN142
    107057754
    Service CPZTN131105275671
    SLAC Graphics Overlays (2)          *845875772
    November 19957-3 
    						
    							PARTS INFORMATION
    PECDESCRIPTIONAPPARATUS CODE
    COMCODE
    62527NR3V3 Upgrade (R3V1/V2 to R3V3)
    Consists of:
    CPU/MEM CPZTN142
    107057754
    --Service Circuit CPZTN131105275671
    63111
    Analog Line CPTN742
    103556957
    63112
    MET Line CPTN735103556882
    63113
    Hybrid Line CPTN762B103976171
    63115
    CO Trunk CPTN747B105167266
    63116
    DID Trunk CPTN753
    103557062
    63118
    Aux Trunk CPTN763D10605616
    63119
    Pooled Modem CPTN758103557112
    63123
    Tone Detector CPTN748D
    106502552
    63130
    Data Line CPTN726103556791
    63136Analog Line CPTN746B106361421
    63140Tie Trunk CPTN760D
    106360142
    63166
    DS1 Interface CPTN767103557203
    21691ADU Aux Power
    Consists of:
    Adapter248B
    102802113
    Adapter400B103848859
    Mod Cord
    D6AP-87102937620
    Transformer2012D
    102600517
    1020-S90
    ACCESS Software*105341218
    1020-S91CAM Software
    *105341382
    1203-033n,
    Advanced Admin. Software
    *107058372
    Rel 3 V3
    (MS-DOS)
    1203-034n,Advanced Admin. Software
    *107058398
    Rel 3 V3(UNIX)
    1207-030
    CMS Software
    *105517106
    2169-001Tip Ring ADUZ3A1103963963
    2169-002
    Tip Ring ADUZ3A2
    *
    2169-004Tip Ring ADUZ3A4103964185
    2169-005
    Multiple ADU (MADU)*
    *
    2301-SAASupplemental Alert Adapter
    **
    7-4November 1995 
    						
    All ATT manuals Comments (0)

    Related Manuals for ATT System 25 Reference Manual